Vega VEGACAP 65 Operating Instructions Manual

Manual is about: Transistor NPN/PNP, Contactless electronic switch

Summary of VEGACAP 65

  • Page 1

    Operating instructions vegacap 65 - transistor (npn/pnp) document id: 30018 capacitive.

  • Page 2: Contents

    Contents 1 about this document 1.1 function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised...

  • Page 3

    9 supplement 9.1 technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.2 dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 supplementary documentation information: supplementary documents appropriate to the ordered version come with the delivery. You...

  • Page 4: About This Document

    1 about this document 1 .1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep...

  • Page 5: For Your Safety

    2 for your safety 2 .1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2 ....

  • Page 6

    2 .5 safety label on the instrument the safety approval markings and safety tips on the device must be observed. 2 .6 ce conformity this device fulfills the legal requirements of the applicable ec guidelines. By attaching the ce mark, vega provides a confirmation of successful testing. You can find the...

  • Page 7: Product Description

    3 product description 3 .1 configuration the scope of delivery encompasses: l vegacap 65 point level sensor l documentation - this operating instructions manual - safety manual - 31815 "vegacap series 60 - transistor (npn/pnp)" (optional) - supplementary instructions manual "plug connector for level ...

  • Page 8

    1 2 3 fig. 1: vegacap 65 - with plastic housing 1 housing cover 2 housing with electronics 3 process fitting the type label contains the most important data for identification and use of the instrument: l article number l serial number l technical data l article numbers, documentation the serial numbe...

  • Page 9

    Typical applications are overfill and dry run protection. The capacitive measuring principle places no special requirements on installation. Hence, many different applications can be equipped with vegacap 65. Probe, measured product and vessel wall form an electrical capacitor. The capacitance is influ...

  • Page 10

    L signal lamp for indication of the switching condition (green/red) l potentiometer for switching point adaptation l dil switch for measuring range selection l dil switch for mode adjustment 3 .4 storage and transport your instrument was protected by packaging during transport. Its capacity to handl...

  • Page 11: Mounting

    4 mounting 4 .1 general instructions make sure that all parts of the instrument exposed to the process, in particular the sensor element, process seal and process fitting, are suitable for the existing process conditions. These include above all the process pressure, process temperature as well as th...

  • Page 12

    The process fitting must be sealed if there is gauge or low pressure in the vessel. Before use, check if the seal material is resistant against the measured product and the process temperature. The max. Permissible pressure is specified in chapter "technical data" or on the type label of the sensor. I...

  • Page 13

    The probe should protrude into the vessel to avoid buildup. For that reason, avoid using mounting bosses for flanges and screwed fittings. This applies particularly to use with adhesive products. In silos with bulk solids, material cones can form which change the switching point. Please keep this in m...

  • Page 14

    D d 6 1 2 3 fig. 6: filling in the center, emptying laterally 1 vegacap 65 2 discharge opening 3 filling opening make sure that the max. Permissible tensile load of the suspension cable is not exceeded. The danger of this happening exists particularly with very heavy solids and large meas. Lengths. ...

  • Page 15: Connect To Power Supply

    5 connect to power supply 5 .1 prepare the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage connect the operating voltage according to the following diagrams. Take note of the general installation regulations. As a rule, connect...

  • Page 16

    11 screw the housing cover on the electrical connection is finished. Fig. 7: connection steps 5 and 6 5 .3 wiring plan, single chamber housing 1 4 4 4 2 3 fig. 8: material versions, single chamber housing 1 plastic (not with dust-ex) 2 aluminium 3 stainless steel 4 filter element for pressure compens...

  • Page 17

    4 5 6 3 2 1 fig. 9: electronics and connection compartment 1 potentiometer for switching point adaptation 2 dil switch for measuring range selection 3 dil switch for mode adjustment 4 ground terminal 5 connection terminals 6 control lamp we recommend connecting vegacap 65 in such a way that the swit...

  • Page 18

    1 fig. 10: wiring plan 1 power supply + - + - fig. 11: npn action + - + - fig. 12: pnp action 18 vegacap 65 • - transistor (npn/pnp) 5 connect to power supply 30018 -en -090604.

  • Page 19

    5 .4 wiring plan - version ip 66/ip 68, 1 bar 1 2 3 4 5 fig. 13: wire assignment connection cable. The numbers of the wires correspond to the terminals of the instrument. 1 brown (+) voltage supply 2 white 3 yellow 4 blue (-) voltage supply 5 shielding wire assignment, con- nection cable vegacap 65 ...

  • Page 20: Set Up

    6 set up 6 .1 general information the figures in brackets refer to the following illustrations. On the electronics module you will find the following indicating and adjustment elements: l potentiometer for switching point adaptation l dil switch for measuring range selection l dil switch for mode adju...

  • Page 21

    Note: screw the housing cover tightly up to the thread stop so that the inspection glass is above the control lamp (led). To adjust vegacap 65, first of all remove the housing cover. You can adapt the switching point to the solid with the potentiometer. With the potentiometer (1) and the measuring ra...

  • Page 22

    1 set mode switch (3) to mode min. 2 set meas. Range selection switch (2) to range 1. 3 lower the level to the requested min. Level. 4 turn the potentiometer (1) to 0, the control lamp (6) lights green. 5 turn the potentiometer (1) very slowly clockwise until the control lamp (6) lights red. If the ...

  • Page 23

    7 maintenance and fault rectification 7 .1 maintenance when used in the correct way, no special maintenance is required in normal operation. 7 .2 remove interferences the operator of the system is responsible for taken suitable measures to remove interferences. A maximum of reliability is ensured. Ne...

  • Page 24

    L shortcircuit in the probe, e.G. Because of moisture in the housing à remove the electronics module and check the resistance between the marked plug connections according to the following illustration. 1 2 3 fig. 25: check the resistance in the probe 1 shielding 2 probe 3 ground potential à there s...

  • Page 25

    7 .3 exchange of the electronics module in general, all electronics modules of series cp60 can be inter- changed. If you want to use an electronics module with a different signal output, you can download the corresponding operating instructions manual from our homepage under downloads. Proceed as fol...

  • Page 26

    11 insert the wire ends into the open terminals according to the wiring plan 12 press down the opening levers of the terminals, you will hear the terminal spring closing 13 check the hold of the wires in the terminals by lightly pulling on them 14 check cable gland on tightness. The seal ring must c...

  • Page 27

    70 m m (2 3 / 4 ") 200 mm (7 7 / 8 ") fig. 28: take the gravity weight into account and shorten the cable respectively 5 shift the gravity weight again flush to the cable and fix it with the two pins. 6 mount the probe into the vessel. Make sure that the probe is uncovered. 2 1 fig. 29: compensation k...

  • Page 28

    You can download a return form (23 kb) from our internet homepage www.Vega.Com under: "downloads - forms and certificates - repair form". By doing this you help us carry out the repair quickly and without having to call back for needed information. L print and fill out one form per instrument l clean ...

  • Page 29: Dismounting

    8 dismounting 8 .1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in reve...

  • Page 30: Supplement

    9 supplement 9 .1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting - thread 316l - process fitting - flange 316l - process seal klingersil c-4400 - insulation (partly insulated) pa, ptfe - probe (cable partly ptfe insulated: ø 6 mm/0.23...

  • Page 31

    Max. Tensile load (cable) - ptfe partly insulated: ø 6 mm (0.236 in) 10 kn (2248 lbs) - ptfe partly insulated: ø 8 mm (0.315 in) 10 kn (2248 lbs) - pa partly insulated: ø 11 mm (0.433 in) 10 kn (2248 lbs) max. Torque (process fitting - thread) 100 nm (74 lbf ft) frequency 430 khz output variable outp...

  • Page 32

    1 2 3 -50˚c (-58˚f) 50˚c (122˚f) 40˚c (104˚f) -40˚c (-40˚f) 80˚c (176˚f) 0˚c (32˚f) 100˚c (212˚f) 150˚c (302˚f) 200˚c (392˚f) fig. 30: ambient temperature - process temperature 1 process temperature 2 ambient temperature 3 temperature range with temperature adapter dielectric figure ≥ 1.5 electromech...

  • Page 33

    - tensile strength > 1200 n (270 pounds force) - standard length 5 m (16.4 ft) - max. Length 1000 m (3280 ft) - min. Bending radius 25 mm (with 25 °c/77 °f) - diameter approx. 8 mm - colour - standard pe black - colour - standard pur blue - colour - ex-version blue adjustment elements mode switch - ...

  • Page 34

    You can find detailed information in the supplied safety manual of the instrument series or under " www.Vega.Com", "downloads", "approvals". Approvals depending on the version, instruments with approvals can have different technical data. For these instruments, the corresponding approval documents hav...

  • Page 35

    9 .2 dimensions housing in protection ip 66/ip 67 and ip 66/ip 68; 0.2 bar ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 1 1 2 mm (4 1 3 / 3 2 ") m20x1,5/ ½ npt ~ 69 mm (2 23 / 32 ") ø 77 mm (3 1 / 32 ") 1 1 7 mm (4 3 9 / 6 4 ") m20x1,5/ ½ npt ~ 116 mm (4 9 / 16 ") ø 84 mm (3 5 / 16 ") 1 1 6 mm (4 9 / ...

  • Page 36

    L g 1 a g 1 ½ a 56 mm (2 13 / 64 ") 22 mm (2 55 / 64 ") ø 30 mm (1 3 / 16 ") 142 mm (5 19 / 32 ") 200 mm (7 7 / 8 ") ø 6 mm ( 15 / 64 ") fig. 33: vegacap 65 - cable version with ø 6 mm, threaded version g1 a (iso 228 t1) l = sensor length, see chapter "technical data" 36 vegacap 65 • - transistor (n...

  • Page 37

    L g 1 a g 1 1 / 2 a 56 mm (2 13 / 64 ") 22 mm (2 55 / 64 ") ø 30 mm (1 3 / 16 ") 142 mm (5 19 / 32 ") 200 mm (7 7 / 8 ") ø 8 mm ( 5 / 16 ") fig. 34: vegacap 65 - cable version with ø 8 mm, threaded version g1 a (iso 228 t1) l = sensor length, see chapter "technical data" vegacap 65 • - transistor (n...

  • Page 38

    200 mm (7 7 / 8 ") ø 11 mm ( 7 / 16 ") 182 mm (7 11 / 64 ") l 56 mm (2 13 / 64 ") ø 30 mm (1 3 / 16 ") 22 mm (2 55 / 64 ") sw 41 ( 1 39 / 64 ") g 1 a fig. 35: vegacap 65 - cable version with ø 11 mm, threaded version g1 a (iso 228 t1) l = sensor length, see chapter "technical data" 38 vegacap 65 • -...

  • Page 39

    1 0 2 mm (4 .0 2 ") ø 40 mm (1.58") fig. 36: temperature adapter ø 16 mm (0.63") l 7 mm (0 .2 8 ") fig. 37: vegacap 65 - screening tube - fro example against strong condensation vegacap 65 • - transistor (npn/pnp) 39 9 supplement 30018 - en -090604.

  • Page 40

    9 .3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com . Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte...

  • Page 41

    Vegacap 65 • - transistor (npn/pnp) 41 9 supplement 30018 - en -090604.

  • Page 42

    42 vegacap 65 • - transistor (npn/pnp) 9 supplement 30018 -en -090604.

  • Page 43

    Vegacap 65 • - transistor (npn/pnp) 43 9 supplement 30018 - en -090604.

  • Page 44

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com printing date: iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems co...