Summary of VEGAFLEX 61

  • Page 1

    Operating instructions vegaflex 61 profibus pa document id: 31835 guided microwave.

  • Page 2: Contents

    Contents 1 about this document 1.1 function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised...

  • Page 3

    8 maintenance and fault rectification 8.1 maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 8.2 rectify malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . 37 8.3 exchange or shorten cable/rod . . . . . . . . . . . . . . . . . 39 8.4 exchanging the electronics modu...

  • Page 4: 1 About This Document

    1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep ...

  • Page 5: 2 For Your Safety

    2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 ...

  • Page 6

    2.5 safety label on the instrument the safety approval markings and safety tips on the device must be observed. 2.6 ce conformity this device fulfills the legal requirements of the applicable ec guidelines. By attaching the ce mark, vega provides a confirmation of successful testing. You can find the c...

  • Page 7: 3 Product Description

    3 product description 3.1 structure the scope of delivery encompasses: l vegaflex 61 level sensor l documentation - this operating instructions manual - operating instructions manual 27835 "indicating and adjust- ment module plicscom" (optional) - supplementary instructions manual "plug connector fo...

  • Page 8

    L article numbers, documentation with the serial number, you can access the delivery data of the instrument via www.Vega.Com, "vega tools" and "serial number search". In addition to the type label outside, you can also find the serial number on the inside of the instrument. 3.2 principle of operation...

  • Page 9

    L with the suitable vega dtm in conjunction with an adjustment software according to the fdt/dtm standard, e.G. Pactware and pc l with the adjustment program pdm 3.4 packaging, transport and storage your instrument was protected by packaging during transport. Its capacity to handle normal loads duri...

  • Page 10: 4 Mounting

    4 mounting 4.1 general instructions make sure that all parts of the instrument exposed to the process, in particular the sensor element, process seal and process fitting, are suitable for the existing process conditions. These include above all the process pressure, process temperature as well as the...

  • Page 11

    Fig. 2: measures against moisture penetration the reference plane for the measuring range of the sensors is the sealing surface of the thread or flange. Keep in mind that a min. Distance must be maintained below the reference plane and possibly also at the end of the probe - measurement in these area...

  • Page 12

    Keep in mind that measurement down to the tip of the probe is not possible. The exact value of the min. Distance (lower dead band) is stated in chapter "technical data". Fig. 3: vessel with conical bottom plastic vessel/glass vessel the guided microwave principle requires a metal surface on the proc...

  • Page 13

    1 2 fig. 4: installation in plastic silo 1 flange 2 metal sheet concrete vessel when installed in thick concrete ceilings, vegaflex 61 should be mounted front flush to the lower edge. In concrete silos, the distance to the wall should be at least 500 mm (20 in). ø >160 mm (ø >6.3") fig. 5: installati...

  • Page 14

    If possible, avoid sockets. Mount the sensor flush with the vessel top. If this is not possible, use short sockets with small diameter. Higher sockets or sockets with a bigger diameter can generally be used. They simply increase the upper dead band. Check if this is relevant for your measurement. In ...

  • Page 15

    Standpipes or bypass tubes are normally metal tubes with a diameter of 30 … 200 mm (1.18 … 7.87 in). In measurement technology such a tube corresponds to a coax probe. It does not matter if the standpipe is perforated or slotted for better mixing. Lateral inlets with bypass tubes also do not influenc...

  • Page 16

    Make sure that the probe is not subjected to strong lateral forces. Mount vegaflex 61 at a position in the vessel where no disturbances, e.G. From filling openings, agitators, etc., can occur. Fig. 9: lateral load if there is a danger of the probe touching the vessel wall during operation due to prod...

  • Page 17

    5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage l if overvoltage surges are expected, overvoltage arresters should be installed according to profibus specifications tip: we recommend...

  • Page 18

    In systems with potential equalisation, connect the cable screen directly to ground potential at the power supply unit, in the connection box and at the sensor. The screen in the sensor must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be con...

  • Page 19

    7 insert the wire ends into the open terminals according to the wiring plan fig. 10: connection steps 6 and 7 8 press down the opening levers of the terminals, you will hear the terminal spring closing 9 check the hold of the wires in the terminals by lightly pulling on them 10 connect the screen to...

  • Page 20

    I²c display 1 2 5 6 7 8 3 4 1 2 fig. 11: electronics and connection compartment with single chamber housing 1 plug connector for vegaconnect (i²c interface) 2 spring-loaded terminals for connection of the external indication vegadis 61 3 ground terminal for connection of the cable screen 4 spring-lo...

  • Page 21

    1 3 2 display 1 2 5 6 7 8 i²c fig. 13: electronics compartment, double chamber housing 1 plug connector for vegaconnect (i²c interface) 2 internal connection cable to the connection compartment 3 terminals for vegadis 61 3 1 2 display 1 2 i²c fig. 14: connection compartment, double chamber housing 1...

  • Page 22

    I2c 1 1 2 fig. 15: wiring plan with double chamber housing 1 voltage supply/signal output 5.5 wiring plan - version ip 66/ip 68, 1 bar + - 1 2 fig. 16: wire assignment connection cable 1 brown (+) and blue (-) to power supply or to the processing system 2 shielding wiring plan wire assignment con- n...

  • Page 23: Module Plicscom

    6 set up with the indicating and adjustment module plicscom 6.1 short description the indicating and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in the following housing versions and instruments: l all sensors of the plics ® instrument family, in...

  • Page 24

    Fig. 17: insert indicating and adjustment module note: if you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. 24 vegaflex 61 • profibus pa 6 set up with the indicating and adjustme...

  • Page 25

    6.3 adjustment system 1.1 2 3 1 fig. 18: indicating and adjustment elements 1 lc display 2 indication of the menu item number 3 adjustment keys l [ok] key: - move to the menu overview - confirm selected menu - edit parameter - save value l [->] key to select: - menu change - select list entry - selec...

  • Page 26

    6.4 setup steps after vegaflex 61 is connected to voltage supply or after voltage recurrence, the instrument carries out a self-check for approx. 30 seconds. The following steps are carried out: l internal check of the electronics l indication of the instrument type, the firmware as well as the senso...

  • Page 27

    Start your parameter adjustment with the following menu items of the basic adjustment: proceed as follows: 1 move from the measured value display to the main menu by pushing [ok]. ▶ basic adjustment display diagnostics service info 2 select the menu item "basic adjustment" with [->] and confirm with ...

  • Page 28

    Each product has different reflective properties. In addition, there are various interfering factors which have to be taken into account: agitated product surfaces and foam generation (with liquids); dust generation, material cones and echoes from the vessel wall (with solids). To adapt the sensor to ...

  • Page 29

    Linearisation curve linear enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [->] key. Caution: note the following, if vegaflex 61 is used as part of an overfill protection system according to whg: if a linearisation curve is selected,...

  • Page 30

    2 select the menu item "service" with [->] and confirm with [ok]. Now the menu item "false signal suppression" is displayed. 3 confirm "false signal suppression - change now" with [ok] and select in the below menu "create new". Enter the actual distance from the sensor to the product surface. All fals...

  • Page 31

    Basic adjustment if the function "reset" is carried out, the sensor resets the values of the following menu items to the reset values (see chart): 2) the following values will be reset: function reset value max. Adjustment distance, upper dead zone min. Adjustment distance, supplied sensor length mi...

  • Page 32

    6.5 menu schematic basic adjustment 1 ▶ basic adjustment display diagnostics service info 1.1 sensor address 000 1.2 min. Adjustment 0.00 % = 10.000 m(d) 8.000 m(d) 1.3 max. Adjustment 100.00 % = 1.000 m(d) 2.000 m(d) 1.4 linearisation curve linear 1.5 channel pv lin. Value 1.6 damping 0 s 1.7 senso...

  • Page 33

    Service 4 basic adjustment display diagnostics ▶ service info 4.1 sensor 5.00 m rod 4.2 application liquid standard (dk ≥ 2) 4.3 gating out of false signals change now? 4.4 additional pa value secondary value 1 4.5 out-scale-unit volume hl 4.6 pv-out-scale 0 % = 0.0 m³ 100 % = 100 m³ 4.7 simulation ...

  • Page 34

    6.6 saving the parameter adjustment data it is recommended noting the adjusted data, e.G. In this operating instructions manual and archive them afterwards. They are hence available for multiple use or service purposes. If vegaflex 61 is equipped with an indicating and adjustment module, the most im...

  • Page 35: Programs

    7 set up with pactware and other adjustment programs 7.1 connecting the pc 3 1 2 fig. 19: connection of the pc via vegaconnect directly to the sensor 1 usb cable to the pc 2 vegaconnect 3 sensor 1 2 3 4 open twist usb lock fig. 20: connection via vegaconnect externally 1 i²c bus (com.) interface on ...

  • Page 36

    Necessary components: l vegaflex 61 l pc with pactware and suitable vega dtm l vegaconnect l power supply unit or processing system 7.2 parameter adjustment with pactware further setup steps are described in the operating instructions manual "dtm c ollection/pactware" attached to each cd and which c...

  • Page 37

    8 maintenance and fault rectification 8.1 maintenance when used as directed in normal operation, vegaflex 61 is completely maintenance free. 8.2 rectify malfunctions the operator of the system is responsible for taking suitable measures to remove interferences. Vegaflex 61 offers maximum reliability. ...

  • Page 38

    Error cause removal in simatic s7 the measured value is always presented as 0 only four bytes are consistently loaded in the plc use function component sfc 14 to load 5 bytes consistently measured value on the indicating and adjustment module does not correspond to the value in the plc the menu item...

  • Page 39

    Status accor- ding to ne 107 error code text message cause/rectification e 017 adjustment span too small adjustment not within the specifica- tion. Carry out the adjustment again, increasing the distance between min. And max. Adjustment e 036 no operable software failed or interrupted software up- dat...

  • Page 40

    Fig. 21: exchanging the cable or rod information: please keep the stated torque so that the max. Tensile strength remains. The cable and rod of the probe can be shortened by any amount. 1 cable: loosen the three pins on the gravity weight (hexagon 3) 2 cable: remove the pins 3 cable: pull the cable ...

  • Page 41

    Fig. 22: shortening the cable probe 8.4 exchanging the electronics module if the electronics module is defective, it can be replaced by the user. In ex applications only one instrument and one electronics module with respective ex approval may be used. If there is no electronics module available on ...

  • Page 42

    8.5 software update the software version of vegaflex 61 can be determined as follows: l on the type label of the electronics l via the indicating and adjustment module l via pactware you can view all software histories on our website www.Vega.Com. Make use of this advantage and get registered for up...

  • Page 43

    L please ask the agency serving you for the address of your return shipment. You can find the respective agency on our website www.Vega.Com under: "company - vega worldwide" on instruments with exchangeable rod, the rod must be unscrewed for transport to avoid damages. Return the parts separately for...

  • Page 44: 9 Dismounting

    9 dismounting 9.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in rever...

  • Page 45: 10 Supplement

    10 supplement 10.1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting 316l and pctfe, hastelloy c22 (2.4602) and pctfe - process seal on the instrument side (cable/rod leadthrough) fkm (viton), ffkm (kalrez 6375), epdm, silicone fep coa...

  • Page 46

    - gravity weight 325 g (11.46 oz) probe length l (from seal surface) - rod: ø 6 mm (0.236 in) up to 4 m (13.12 ft) - trimming accuracy - rod 1 mm (0.039 in) - cable: ø 2 mm (0.079 in) up to 32 m (105 ft) - cable: ø 4 mm (0.157 in) up to 32 m (105 ft) - trimming accuracy - cable ± 0.05 % lateral load...

  • Page 47

    2 4 5 3 2 4 5 3 1 1 fig. 23: measuring ranges of vegaflex 61 1 reference plane 2 probe length l 3 measuring range (default setting refers to the measuring range in water) 4 upper dead band (see diagrams under accuracy - grey section) 5 lower dead band (see diagrams under accuracy - grey section) out...

  • Page 48

    Installation reference conditions - min. Distance to installations > 500 mm (19.69 in) - vessel metallic, ø 1 m (3.281 ft), centric installation, process fitting flush with the vessel ceiling - medium water/oil (dk value ~2.0) - installation probe end does not touch the vessel bottom sensor parameter ...

  • Page 49

    L 0 -3 mm (-0.118 ") 3 mm (0.118 ") 15 mm (0.591 " ) -10 mm (-0.394 ") 0,3 m (11.811 " ) 0,08 m (3.15 " ) 0,02 m (0.787 ") 1 fig. 24: deviation vegaflex 61 in rod version in water 1 dead zone - no measurement possible in this area l probe length l 5 mm (0.197 ") 0 -5 mm (-0.197 ") 15 mm (0.591 " ) -...

  • Page 50

    0 3 mm (0.118 ") -3 mm (-0.118 ") 15 mm (0.591 ") 15 mm (0.591 ") 0,08 m (3.15 ") 0,3 m (11.811 ") 0,3 m (11.811 ") l 1 fig. 26: deviation vegaflex 61 in cable version, probe length l 1 dead zone - no measurement possible in this area l probe length l 0 -15 mm (-0.591 " ) 5 mm (0.197 ") -5 mm (-0.19...

  • Page 51

    L 3 mm (0.118 ") 0 -3 mm (-0.118 ") 15 mm (0.591 ") 20 mm (0.787”) 0,08 m (3.15 ") 0,3 m (11.811 ") 20 m (787.4 ") 1 fig. 28: deviation vegaflex 61 in cable version, probe length l > 20 m in water 1 dead zone - no measurement possible in this area l probe length l 0 20 mm (0.787 ") 0,25 m (9.843 ") ...

  • Page 52

    Ambient conditions ambient, storage and transport temperature -40 … +80 °c (-40 … +176 °f) process conditions process pressure -1 … +40 bar/-100 … +4000 kpa (- -14.5 … +580 psig), depending on the process fitting process temperature (thread or flange temperature) - fkm (viton) -40 … +150 °c (-40 … +30...

  • Page 53

    - double chamber housing l 1 x cable entry m20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind stopper m20 x 1.5; 1 x blind stopper m 16 x 1.5 or optionally available with 1 x plug m 12 x 1 for vegadis 61 or: l 1 x closing cap ½ npt, 1 x blind stopper ½ npt , 1 x blind stopper m16 x 1.5 or optionally 1 x plug ...

  • Page 54

    - inspection window polyester foil voltage supply operating voltage - non-ex instrument 9 … 32 v dc - eex-ia instrument 9 … 24 v dc - eex-d instrument 16 … 32 v dc operating voltage with lighted indicating and adjustment module - non-ex instrument 12 … 32 v dc - eex-ia instrument 12 … 24 v dc - eex-...

  • Page 55

    10.2 profibus pa instrument master file the instrument master file (gsd) contains the characteristic data of the profibus pa instrument. These data are, e.G. The permissible transmission rates as well as information on diagnostics values and the format of the measured value outputted by the pa instrumen...

  • Page 56

    Module of the pa sensors for the cyclic data traffic, vegaflex 61 provides the following modules: l ai (pa-out) - pa-out value of the fb1 after scaling l additional cyclic value - additional cyclical value (depending on the source) l free place - this module must be used if a value should not be used ...

  • Page 57

    L free place byte-no. 1 2 3 4 5 status status (fb1) ieee-754- floating point value pa-out (fb1) format value data format of the output signal byte4 byte3 byte2 byte1 byte0 status value (ieee-754) fig. 34: data format of the output signal the status byte corresponds to profile 3.0 "profibus pa profile f...

  • Page 58

    Status code description according to pro- fibus standard possible cause 0x0c bad - sensor failure l hardware error l converter error l leakage pulse error l trigger error 0x10 bad - sensor failure l measured value generation error 0x1f bad - out of service constant "o ut of service" mode switched on ...

  • Page 59

    10.3 dimensions the following dimensional drawings represent only an extract of the possible versions. Detailed dimensional drawings can be downloaded on www.Vega.Com under "d ownloads" and "drawings". Plastic housing 1 2 ~ 69 mm (2.72") ø 77 mm (3.03") 1 1 2 mm (4 .4 1 ") m20x1,5/ ½ npt ~ 87 mm (3....

  • Page 60

    Aluminium housing in protection rating ip 66/ip 68, 1 bar 1 2 0 mm (4 .7 2 ") ~ 105 mm (4.13") 1 16 m m (4.57 ") ~ 150 mm (5.91") ø 84 mm (3.31") ø 84 mm (3.31") m20x1,5/ ½ npt m16x1,5 2 m20x1,5 m20x1,5 1 1 single chamber version 2 double chamber version stainless steel housing ~ 69 mm (2.72") ø 77 ...

  • Page 61

    Vegaflex 61 - threaded version l sw 36 (1.42") (g¾, ¾ npt) sw 41 (1.61") (g1, 1 npt) sw 46 (1.81") (g1½, 1½ npt) g¾, ¾ npt, g1, 1 npt, g1½, 1½ npt 2 2 mm (0 .8 7 ") 4 6 mm (1 .8 1 ") 1 5 0 mm (5 .9 1 ") 5 3 mm (2 .0 9 ") ø 6 mm (0.24") 12 mm (0.47") ø 54 mm (2.13") ø 20 mm (0.79") ø 2 mm / (0.08") ø...

  • Page 62

    Vegaflex 61 - flange version l b l b d d d d k k 6 8 mm (2 .6 8 ") 4 6 mm (1 .8 1 ") d b k d dn 25 pn 40 115 18 85 4x ø 14 dn 40 pn 40 150 18 110 4x ø 18 1" 150 lb 108 14,2 78,2 4x ø 15,7 1" 300 lb 124 17,5 88,9 4x ø 19,1 d b k d dn 50 pn 40 165 20 125 4x ø 18 dn 80 pn 40 200 24 160 8x ø 18 dn 100 pn...

  • Page 63

    10.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com . Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte...

  • Page 64

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com printing date: iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems co...