Vega vegaflex 83 Operating Instructions Manual

Manual is about: TDR sensor for continuous level and interface measurement of liquids. Four-wire Modbus Converter version in second chamber Polished rod probe

Summary of vegaflex 83

  • Page 1

    Operating instructions tdr sensor for continuous level and interface measurement of liquids vegaflex 83 foundation fieldbus polished rod probe document id: 44224.

  • Page 2: Contents

    2 contents vegaflex 83 • foundation fieldbus 44224-en-160518 contents 1 about this document 1.1 function ........................................................................................................................... 4 1.2 target group .......................................................

  • Page 3

    3 contents vegaflex 83 • foundation fieldbus 44224-en-160518 9.2 diagnosis memory ......................................................................................................... 53 9.3 status messages ............................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegaflex 83 • foundation fieldbus 44224-en-160518 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tionsformaintenanceandfaultrectification.Pleasereadth...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegaflex 83 • foundation fieldbus 44224-en-160518 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the devic...

  • Page 6

    6 2 for your safety vegaflex 83 • foundation fieldbus 44224-en-160518 youcanfindthececertificateofconformityinthedownloadsection of our homepage. Electromagnetic compatibility instruments in four-wire or ex-d-ia version are designed for use in an industrial environment. Nevertheless, electromagnetic...

  • Page 7: 3  Product Description

    7 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 3 product description 3.1 configuration thetypelabelcontainsthemostimportantdataforidentificationand use of the instrument: 2 1 13 14 15 16 12 11 5 3 6 4 7 8 9 10 fig. 1: layout of the type label (example) 1 instrument type 2 ...

  • Page 8

    8 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 • scan the data matrix code on the type label of the instrument or • enter the serial number manually in the app this operating instructions manual applies to the following instrument versions: • hardware from 1.0.0 • software...

  • Page 9

    9 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 d h 1 fig. 2: level measurement 1 sensorreferenceplane(sealsurfaceoftheprocessfitting) d distance to the level h height - level probe end tracking to increase sensitivity, the probe is equipped with probe end tracking. In prod...

  • Page 10

    10 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 ts d1 h1 h2 d2 1 l2 l1 l3 fig. 3: interface measurement 1 sensorreferenceplane(sealsurfaceoftheprocessfitting) d1 distance to the interface d2 distance to the level tsthicknessoftheuppermedium(d1-d2) h1 height - interface h2 ...

  • Page 11

    11 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 the instrument is always preset to the application "level measure- ment". For the interface measurement, you can select the requested output signal with the setup. 3.3 packaging, transport and storage your instrument was prot...

  • Page 12

    12 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 the vegadis 81 is an external display and adjustment unit for vega plics ® sensors. For sensors with double chamber housing the interface adapter "disadapt" is also required for vegadis 81. Youcanfindfurtherinformationintheop...

  • Page 13

    13 3 product description vegaflex 83 • foundation fieldbus 44224-en-160518 youcanfindadditionalinformationintheoperatinginstructions manual "externalhousing" (document-id 46802). If you mount the vegaflex 83 in a bypass tube or standpipe, you have to avoid contact to the bypass tube by using a space...

  • Page 14: 4 Mounting

    14 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 4 mounting 4.1 general instructions protect your instrument against moisture ingress through the following measures: • use the recommended cable (see chapter "connectingtopower supply") • tighten the cable gland • whenmountinghorizontal...

  • Page 15

    15 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 vessels, the distance to the vessel wall should be at least 500 mm (19.7 in). During operation, the probe must not touch any installations or the vessel wall. If necessary, fasten the probe end. In vessels with conical bottom it can be ...

  • Page 16

    16 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 fig. 5: installation in non-metallic vessel 1 flange 2 metal sheet ifpossible,avoidsockets.Mountthesensorflushwiththevesseltop. If this is not possible, use short sockets with small diameter. Higher sockets or sockets with a bigger ...

  • Page 17

    17 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 fig.7:socketmustbeinstalledflush 1 unfavourable installation 2 socketflush-optimuminstallation before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics thro...

  • Page 18

    18 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 products.Theseblockingdistancesfordifferentmediumsarelisted in chapter "technicaldata". Keep in mind for the adjustment that the default setting for the measuring range refers to water. Theprocessfittingmustbesealedifthereisgaugeorlowpr...

  • Page 19

    19 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 incaseofdifficultinstallationconditions,forexampleinasocket,the probe can be suitably adapted with a rod extension. To compensate for the resulting changes in signal runtime, let the instrument determine the probe length automatically. ...

  • Page 20

    20 4 mounting vegaflex 83 • foundation fieldbus 44224-en-160518 112 mm (4.84") din dn25 dn32 dn40 / 1" 1 1/2" l ø 54 mm (2.13") ø w 183 mm (7.20") 65,3 mm (2.57") ø w ø 50,5 din dn50 / 2" ø 64 ø 91 din dn65 / 3" 2 1 3 fig. 10: autoclaved version 1 groovenut 2 processfitting 3 coverwithgroovenut.

  • Page 21

    21 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only be c...

  • Page 22

    22 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equalisation (low impedance). 5.2 connecting the voltage supply and signal output are connected vi...

  • Page 23

    23 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 fig.12:connectionsteps5and6-doublechamberhousing 6. Insert the wire ends into the terminals according to the wiring plan information: solidcoresaswellasflexiblecoreswithwireendsleevesareinsert- eddirectlyintothetermina...

  • Page 24

    24 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 ( ) (-) 1 5 0 1 0 1 + 6 7 8 bus 2 3 4 5 fig.13:electronicsandterminalcompartment,singlechamberhousing 1 voltage supply, signal output 2 contactpinsforthedisplayandadjustmentmoduleorinterfaceadapter 3 simulation swi...

  • Page 25

    25 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 bus 5 1 2 + ( ) (-) 6 7 8 2 3 4 1 fig.15:terminalcompartment,doublechamberhousing 1 voltage supply, signal output 2 for display and adjustment module or interface adapter 3 for external display and adjustment unit 4 gr...

  • Page 26

    26 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 5.5 double chamber housing with disadapt 3 1 2 fig.17:viewtotheelectronicscompartmentwithdisadaptforconnectionof the external display and adjustment unit 1 disadapt 2 internal plug connection 3 plug connector m12 x 1 3...

  • Page 27

    27 5 connecting to power supply vegaflex 83 • foundation fieldbus 44224-en-160518 5.6 wiring plan - version ip 66/ip 68, 1 bar 1 2 fig. 19: wire assignment in permanently connected connection cable 1 brown (+) and blue (-) to power supply or to the processing system 2 shielding 5.7 supplementary ele...

  • Page 28: Module

    28 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 6 set up with the display and adjustment module 6.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneo...

  • Page 29

    29 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 fig. 22: installing the display and adjustment module in the double chamber housing 1 in the electronics compartment 2 in the terminal compartment note: ifyouintendtoretrofittheinstrumentwithadis...

  • Page 30

    30 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 – move to the menu overview – confirmselectedmenu – edit parameter – save value • [->] key: – change measured value presentation – select list entry – select editing position • [+] key: – change valu...

  • Page 31

    31 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 6.3 parameter adjustment - quick setup to quickly and easily adapt the sensor to the application, select the menu item "quick setup" in the start graphic on the display and adjustment module. The fol...

  • Page 32

    32 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 info: instrument name, hardware and software version, date of manu- facture, device id, instrument features note: for optimum adjustment of the measuring point, the individual sub- menu items in the ...

  • Page 33

    33 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 note: theselectionoftheapplicationhasaconsiderableinfluenceonall other menu items. Keep in mind that as you continue with the param- eter adjustment, individual menu items are only optionally availab...

  • Page 34

    34 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 you can enter the dielectric constant of the upper medium directly or have the value determined by the instrument. To do this you have to enter the measured or known distance to the interface. In thi...

  • Page 35

    35 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 this menu item is only available if you have selected interface meas- urement under the menu item "application". You can accept the settings of the level measurement also for the interface measuremen...

  • Page 36

    36 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 be done with the lowest possible level so that all potential interfering reflectionscanbedetected. Proceed as follows: enter the actual distance from the sensor to the product surface. All interferin...

  • Page 37

    37 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 required.Correspondinglinearizationcurvesarepreprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. Thelinearizationappliestothemeasuredvaluein...

  • Page 38

    38 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 + h d - h fig. 24: vessel height and socket correction value d vessel height +h positive socket correction value -h negative socket correction value in the menu item "lock/unlockadjustment", you can ...

  • Page 39

    39 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 caution: with active pin, adjustment via pactware/dtm as well as other systems is also blocked. You can change the pin number under "additional settings - pin". In the main menu point "display", the ...

  • Page 40

    40 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 in delivery status, the lighting is switched on. In this menu item, the device status is displayed. The respective min. And max. Measured value is saved in the sen- sor. The two values are displayed ...

  • Page 41

    41 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 the respective min. And max. Measured values are saved in the sensor. The values are displayed in the menu item "peak values ad- ditional". This menu item displays the peak values of the electronics ...

  • Page 42

    42 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 select the requested simulation variable and set the requested value. Caution: during simulation, the simulated value is outputted as 4 … 20 ma cur- rent value and digital hart signal. Push the [esc]...

  • Page 43

    43 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 with a reset, certain parameter adjustments carried out by the user are reset. The following reset functions are available: delivery status: restoring the parameter settings at the time of ship- ment...

  • Page 44

    44 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 menu item default value modifiedvalue max. Adjustment - interface 100 % max. Adjustment - interface distance: 0.000 m(d) - note block- ing distances min. Adjustment - interface 0 % min. Adjustment - ...

  • Page 45

    45 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 additional adjustments menu item default value modifiedvalue pin 0000 date actual date time actual time time - format 24 hours probe type device-specific the instrument settings are copied with this ...

  • Page 46

    46 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 change the settings of the special parameters only after having con- tactedourservicestaff. In this menu, you read out the instrument name and the instrument serial number. In this menu item, the har...

  • Page 47

    47 6 set up with the display and adjustment module vegaflex 83 • foundation fieldbus 44224-en-160518 the following data or settings for adjustment of the display and ad- justment module are saved: • all data of the menu "setup" and "display" • in the menu "additional settings" the items "sensor-spec...

  • Page 48: 7  Setup With Pactware

    48 7 setup with pactware vegaflex 83 • foundation fieldbus 44224-en-160518 7 setup with pactware 7.1 connect the pc 3 1 2 fig.25:connectionofthepcdirectlytothesensorviatheinterfaceadapter 1 usbcabletothepc 2 interfaceadaptervegaconnect 3 sensor 7.2 parameter adjustment with pactware for parameter ad...

  • Page 49

    49 7 setup with pactware vegaflex 83 • foundation fieldbus 44224-en-160518 fig.26:exampleofadtmview all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assi...

  • Page 50

    50 7 setup with pactware vegaflex 83 • foundation fieldbus 44224-en-160518 fig. 27: select quick setup 1 quick setup 2 extendedadjustment 3 maintenance quick setup with quick setup you can carry out the parameter adjustment of vegaflex 83 for your application in just a few simple steps. The assistan...

  • Page 51

    51 7 setup with pactware vegaflex 83 • foundation fieldbus 44224-en-160518 7.4 saving the parameter adjustment data we recommend documenting or saving the parameter adjustment data via pactware. That way the data are available for multiple use or service purposes..

  • Page 52

    52 8 set up with other systems vegaflex 83 • foundation fieldbus 44224-en-160518 8 set up with other systems 8.1 dd adjustment programs device descriptions as enhanced device description (edd) are available for dd adjustment programs such as, for example, ams™ and pdm. Thefilescanbedownloadedatwww.V...

  • Page 53

    53 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 9 diagnostics and servicing 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 9.2 diagnosis memory the instrument has several memories which are available for diagnosti...

  • Page 54

    54 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 • control system with edd • display and adjustment module further echo curves: up to 10 echo curves can be stored in a ring bufferinthismemorysection.Furtherechocurvesarestoredvia: • pc with pactware/dtm • control syste...

  • Page 55

    55 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.G. Due to buildup). This status message is inactive by default. It can be activated by the user via pactware/dtm or...

  • Page 56

    56 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 code text mes- sage cause rectification devspec diagnosis bits f105 measured value is de- termined – the instrument is still in the start phase, the measured value could not yet be determined – wait for the end of the s...

  • Page 57

    57 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 the following table shows the error codes and text messages in the status message "function check" and provides information on causes as well as corrective measures. Code text mes- sage cause rectification tb diagnose c...

  • Page 58

    58 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 code text mes- sage cause rectification tb diagnose m500 error in the delivery status – with the reset to deliv- ery status, the data could not be restored – repeat reset – loadxmlfilewith sensor data into the sensor bi...

  • Page 59

    59 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 • treatment of measurement errors further comprehensive diagnostics options are available with a pc with pactware and the suitable dtm. In many cases, the reasons can bedeterminedinthiswayandfaultsrectified. The below t...

  • Page 60

    60 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 measurementerrorduringfilling fault description error pattern cause rectification 3. Measured value re- mains in the area of the bottomduringfilling level time 0 – echo from the probe end larger than the product echo, f...

  • Page 61

    61 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 level time 0 1 real level 2 level displayed by the sensor notes: • whenever the sensor displays a constant value, the reason could also be that the fault setting of the current output is set to "hold value" • if the...

  • Page 62

    62 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 measurementerrorduringfilling fault description error pattern cause rectification 3. Measured value jumps towards 0 % duringfilling level time 0 – amplitude of a multiple echo (vessel top - product surface) is larger th...

  • Page 63

    63 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 fault description error pattern cause rectification 7. Measured value jumps sporadically to- wards 100 % during emptying level time 0 – varying condensation or con- tamination on the antenna – carry out false signal sup...

  • Page 64

    64 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 if you have stored the data of the parameter adjustment during the firstsetupofthesensor,youcantransferthesetothereplacement electronics module. A new setup is no more necessary. 9.6 exchanging the rod the rod (meas. Pa...

  • Page 65

    65 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 6. Enter new probe length and if necessary the new probe type and then carry out a fresh adjustment (see "setupprocedure,carry- ingoutmin.Adjustment-carryingoutmax.Adjustment"). 9.7 exchanging the seal if necessary, the...

  • Page 66

    66 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 1 fig.48:exchangingthemeasuringrod 1 sealing ring (9.25 x 1.78) 4. Loosenprocessfittingwithasuitablewrench. 5. Unscrewtheprocessfittingmanuallyfromthesensor. 6. Removetheoldsealoutoftheprocessfitting. 7. Insert the atta...

  • Page 67

    67 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 1 2 3 fig.49:seal-processfitting 1 positionoftheseal-processfitting 2 hole for leakage detection 3 processfitting,e.G.Clamp 8. Screwtheprocessfittingbyhandontothethreadofthesensor. 9. Tightentheprocessfittingwithasuitab...

  • Page 68

    68 9 diagnostics and servicing vegaflex 83 • foundation fieldbus 44224-en-160518 youcanfindthecurrentinstrumentsoftwareaswellasdetailed information on the procedure in the download area of our homepage: www.Vega.Com. Caution: instruments with approvals can be bound to certain software versions. Ther...

  • Page 69: 10 Dismount

    69 10 dismount vegaflex 83 • foundation fieldbus 44224-en-160518 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters "moun...

  • Page 70: 11 Supplement

    70 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 11 supplement 11.1 technical data general data 316l corresponds to 1.4404 or 1.4435 materials, wetted parts Ʋ processfitting 316l and peek Ʋ process seal on the instrument side (rod leadthrough) ffkm(kalrez6221),epdm(freudenberg70ep-...

  • Page 71

    71 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 lateral load with rod: ø 8 mm (0.315 in) - polished 10 nm (7.38 lbf ft) torque for exchangeable rod probe (in theprocessfitting) max. 4.5 nm (3.32 lbf ft) torque for npt cable glands and conduit tubes Ʋ plastic housing max. 10 nm (7....

  • Page 72

    72 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 2 4 5 3 1 fig.50:measuringranges-vegaflex83 1 reference plane 2 probe length l 3 measuring range (default setting refers to the measuring range in water) 4 upper dead band (see following diagrams - grey section) 5 lower dead band (se...

  • Page 73

    73 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 l 0 -2mm (-0.079 ") 2mm (0.079 ") 15mm (0.591 " ) -15mm (-0.591 ") 0,2 m (7.874 " ) 0,08 m (3.15 " ) 0,04 m (1.575 ") 1 fig.51:deviationvegaflex83inrodversioninwater 1 dead band - no measurement possible in this area l probe length l...

  • Page 74

    74 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 influenceofthesuperimposedgasandpressuretotheaccuracy the propagation speed of the radar impulses in gas or vapour above the medium is reduced by highpressure.Thiseffectdependsonthesuperimposedgasorvapours. Thefollowingtableshowsther...

  • Page 75

    75 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 Ʋ epdm (freudenberg 70 epdm 291) -20 … +150 °c (-4 … +302 °f) Ʋ fepm (vi 602 extreme-etp, fa. Cog) -10 … +150 °c (+14 … +302 °f) 1 2 3 4 a b 0°c / 32°f -40°c / -40°f 80°c / 176°f 35°c / 95°f 30°c / 86°f 45°c / 113°f 60°c / 140°f 150°...

  • Page 76

    76 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 material ca- ble gland material seal insert cable diameter 4.5 … 8.5 mm 5 … 9 mm 6 … 12 mm 7 … 12 mm 10 … 14 mm pa nbr – ● ● – ● brass, nickel- plated nbr ● ● ● – – stainless steel nbr – ● ● – ● wire cross-section (spring-loaded term...

  • Page 77

    77 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 integrated clock date format day.Month.Year time format 12 h/24 h timezoneexfactory cet rate deviation max. 10.5 min/year additional output parameter - electronics temperature output of the temperature values Ʋ analogue via the curre...

  • Page 78

    78 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 housing material version ip-protection class nema protection stainless steel, electro- polished single chamber ip 66/ip 68 (0.2 bar) type 6p stainless steel, precision casting single chamber ip 66/ip 68 (0.2 bar) ip 68 (1 bar) type 6...

  • Page 79

    79 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 advanced function blocks discret input (di) yes pid control yes output splitter (os) yes signalcharacterizer(sc) yes integrator yes input selector (is) yes arithmetic (ar) yes diagnostics standard yes advanced yes performance no func...

  • Page 80

    80 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 fig. 55: schematic presentation function block analog input (ai) function block discret input (di) the function block "discret input (di)" takes the original measured value selected by a channel number and makes it available to addit...

  • Page 81

    81 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 function block output splitter the function block "output splitter" generates two control outputs out of one input. Each output is a linear image of a part of the input. A retrograde calculation function is realised by using the line...

  • Page 82

    82 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 fig. 60: schematic presentation function block integrator function block input selector the function block "input selector"offersselectionpossibilitiesforuptofourinputsandgenerates an output signal according to the selection criteria...

  • Page 83

    83 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 • flow compensation, approximate • btuflow • traditional multiply divide • average • traditional summer • fourth order polynomial • simple htg compensated level • fourth order polynomial based on pv fig. 62: schematic presentation fu...

  • Page 84

    84 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 ff desciptor description unit secondary_value_2_ type secondary value 2 type fill_height_value_type filling height value type diagnosis aitb diagnosis diag_mask_1 diag_out_1 diag_mask_2 diag_out_2 device_identification manufacturer i...

  • Page 85

    85 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 ff desciptor description unit ecp_curve_avaraging_ config averaging factor on increasing and decreasing amplitude level_echo_measure- ment functionmeasuredvaluefilter echo_curve_status packet_count gu_id_end echo_curve_read echo curv...

  • Page 86

    86 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 ff desciptor description unit device_state_config functioncheck,maintenancerequired,outofspecification electronic_tempera- ture electronics temperature reset_peak_electron- ic_temp focus_range_config width focusing range, time for op...

  • Page 87

    87 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 aluminium housing 2 1 ø 86 mm (3.39") ~ 116 mm (4.57") 116 mm (4.57") m20x1,5 m20x1,5/ ½ npt ~ 87 mm (3.43") m16x1,5 ø 86 mm (3.39") 120 mm (4.72") m20x1,5/ ½ npt fig.64:housingversionswithprotectionratingip66/ip68(0.2bar)-withintegr...

  • Page 88

    88 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 stainless steel housing ~ 69 mm (2.72") ø 79 mm (3.11") 117 mm (4.61") m20x1,5/ ½ npt ~ 59 mm (2.32") ø 80 mm (3.15") 112 mm (4.41") m20x1,5/ ½ npt ~ 87 mm (3.43") ø 86 mm (3.39") 120 mm (4.72") m20x1,5/ ½ npt m16x1,5 3 2 1 fig.66:ho...

  • Page 89

    89 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 vegaflex 83, rod version ø 8 mm (0.315 in), polished l 56 mm (2.20") ø 8 mm (0.32") fig.68:vegaflex83,rodversionø8mm(0.315in),polished l sensorlength,seechapter"technicaldata".

  • Page 90

    90 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 vegaflex 83, rod version ø 8 mm (0.315 in), polished - autoclaved version 112 mm (4.84") din dn25 dn32 dn40 / 1" 1 1/2" l ø 54 mm (2.13") ø w 183 mm (7.20") 65,3 mm (2.57") ø w ø 50,5 din dn50 / 2" ø 64 ø 91 din dn65 / 3" 2 1 3 fig.6...

  • Page 91

    91 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 extension components - rod extension ø 8 mm (0.315 in), polished a 1 b c l l ø8 mm (0.31") sw 10 fig.70:extensionrodswithø8mm(0.315in) 1 versionwiththreadedfitting 2 versionwithflangeconnection a basicextensionrodwithø8mm(0.315in) b ...

  • Page 92

    92 11 supplement vegaflex 83 • foundation fieldbus 44224-en-160518 11.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informat...

  • Page 93: Index

    93 index vegaflex 83 • foundation fieldbus 44224-en-160518 index a adjustment – max. Adjustment 34, 35 – min. Adjustment 34, 35 adjustment system 30 application 32, 33 application area 8 b backlight 39 c connection 22 copy sensor settings 45 curve indication – echo curve 41 d damping 36 date of manu...

  • Page 94

    94 index vegaflex 83 • foundation fieldbus 44224-en-160518 simulation 41 special parameters 45 t type label 7 type of medium 32 u units 32.

  • Page 95

    95 notes vegaflex 83 • foundation fieldbus 44224-en-160518.

  • Page 96

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 44224-en-160518 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...