Vega VEGAFLEX 81 Operating Instructions Manual

Manual is about: TDR sensor for continuous level and interface measurement of liquids

Summary of VEGAFLEX 81

  • Page 1

    Operating instructions tdr sensor for continuous level and interface measurement of liquids vegaflex 81 profibus pa coax probe document id: 44214.

  • Page 2: Contents

    2 contents vegaflex 81 • profibus pa 44214-en-171002 contents 1 about this document ............................................................................................................... 4 1.1 function ............................................................................................

  • Page 3

    3 contents vegaflex 81 • profibus pa 44214-en-171002 9.2 diagnosis memory ......................................................................................................... 53 9.3 status messages ....................................................................................................

  • Page 4: 1  About This Document

    4 1 about this document vegaflex 81 • profibus pa 44214-en-171002 1 about this document 1.1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc- tions for maintenance, fault rectification, the exchange of p...

  • Page 5: 2  For Your Safety

    5 2 for your safety vegaflex 81 • profibus pa 44214-en-171002 2 for your safety 2.1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the re...

  • Page 6

    6 2 for your safety vegaflex 81 • profibus pa 44214-en-171002 2.5 eu conformity the device fulfils the legal requirements of the applicable eu direc- tives. By affixing the ce marking, we confirm the conformity of the instrument with these directives. You can find the eu conformity declaration on ou...

  • Page 7: 3  Product Description

    7 3 product description vegaflex 81 • profibus pa 44214-en-171002 3 product description 3.1 configuration the type label contains the most important data for identification and use of the instrument: 2 1 12 13 14 15 11 10 5 3 6 4 7 8 9 fig. 1: layout of the type label (example) 1 instrument type 2 p...

  • Page 8

    8 3 product description vegaflex 81 • profibus pa 44214-en-171002 • download the vega tools app from the "apple app store" or the "google play store" • scan the data matrix code on the type label of the instrument or • enter the serial number manually in the app this operating instructions manual ap...

  • Page 9

    9 3 product description vegaflex 81 • profibus pa 44214-en-171002 d h 1 fig. 2: level measurement 1 sensorreferenceplane(sealsurfaceoftheprocessfitting) d distance to the level h height - level high frequency microwave impulses are guided along a steel cable or rod. Upon reaching the product surface...

  • Page 10

    10 3 product description vegaflex 81 • profibus pa 44214-en-171002 upper medium (l2) • the upper medium must not be conductive • the dielectric constant of the upper medium or the actual distance to the interface must be known (input required). Min. Dielectric con- stant: 1.6. You can find a list of...

  • Page 11

    11 3 product description vegaflex 81 • profibus pa 44214-en-171002 unless otherwise indicated, the packages must be stored only under the following conditions: • not in the open • dry and dust free • not exposed to corrosive media • protected against solar radiation • avoiding mechanical shock and v...

  • Page 12

    12 3 product description vegaflex 81 • profibus pa 44214-en-171002 the protective cover protects the sensor housing against soiling and intense heat from solar radiation. You will find additional information in the supplementary instructions manual "protective cover" (document-id 34296). Screwed fla...

  • Page 13: 4 Mounting

    13 4 mounting vegaflex 81 • profibus pa 44214-en-171002 4 mounting 4.1 general instructions on instruments with threaded process fitting, the hexagon must be tightened with a suitable wrench. For the proper wrench size see chapter "dimensions". Warning: the housing must not be used to screw the inst...

  • Page 14

    14 4 mounting vegaflex 81 • profibus pa 44214-en-171002 • process pressure • process temperature • chemical properties of the medium • abrasion and mechanical influences you can find detailed information on the process conditions in chapter "technical data" as well as on the type label. The instrume...

  • Page 15

    15 4 mounting vegaflex 81 • profibus pa 44214-en-171002 fig.5:mountingofthesensorwithinflowingmedium the reference plane for the measuring range of the sensors is the sealing surface of the thread or flange. Keep in mind that a min. Distance must be maintained below the refer- ence plane and possibl...

  • Page 16

    16 4 mounting vegaflex 81 • profibus pa 44214-en-171002 1 2 1 2 fig. 6: fasten the probe 1 coaxprobe 2 retaining sleeve.

  • Page 17

    17 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 5 connecting to power supply 5.1 preparing the connection always keep in mind the following safety instructions: warning: connect only in the complete absence of line voltage. • the electrical connection must only be carried o...

  • Page 18

    18 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 max. Torque for all housings, see chapter "technical data". Make sure that the cable screen and grounding are carried out ac- cording to fieldbus specification. We recommend to connect the cable screen to ground potential on b...

  • Page 19

    19 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 fig.7:connectionsteps5and6-singlechamberhousing fig.8:connectionsteps5and6-doublechamberhousing 6. Insert the wire ends into the terminals according to the wiring plan information: solid cores as well as flexible cores with wi...

  • Page 20

    20 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Reinsert the display and adjustment module, if one was installed 11. Screw the housing lid back on the electrical co...

  • Page 21

    21 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 bus 5 1 2 + ( ) (-) 6 7 8 2 3 4 1 fig. 11: terminal compartment - double chamber housing 1 voltage supply, signal output 2 for display and adjustment module or interface adapter 3 for external display and adjustment unit 4 gro...

  • Page 22

    22 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 contact pin colour, connection ca- ble in the sensor terminal, electronics module pin 1 brown 5 pin 2 white 6 pin 3 blue 7 pin 4 black 8 5.6 wiring plan - version ip 66/ip 68, 1 bar 1 2 fig. 14: wire assignment in permanently ...

  • Page 23

    23 5 connecting to power supply vegaflex 81 • profibus pa 44214-en-171002 5 0 0 5 1 6 2 7 3 8 4 9 0 5 1 6 2 7 3 8 4 9 1 0 1 6 7 8 bus 2 1 3 1 2 + ( ) (-) fig. 15: address selection switch 1 addresses 100 (selection 1) 2 decade of the address (selection 0 to 9) 3 unit position of the address (selecti...

  • Page 24: Module

    24 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 6 set up with the display and adjustment module 6.1 insert display and adjustment module the display and adjustment module can be inserted into the sensor and removed again at any time. You can choose any on...

  • Page 25

    25 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 1 2 fig. 17: installing the display and adjustment module in the double chamber housing 1 in the electronics compartment 2 in the terminal compartment note: if you intend to retrofit the instrument with a di...

  • Page 26

    26 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 – move to the menu overview – confirm selected menu – edit parameter – save value • [->] key: – change measured value presentation – select list entry – select editing position • [+] key: – change value of t...

  • Page 27

    27 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 6.3 parameter adjustment - quick setup to quickly and easily adapt the sensor to the application, select the menu item "quick setup" in the start graphic on the display and adjustment module. The following s...

  • Page 28

    28 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 info: instrument name, hardware and software version, date of manu- facture, instrument features note: for optimum adjustment of the measuring point, the individual sub- menu items in the main menu item "set...

  • Page 29

    29 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 • numbers from 0 … 9 • special characters + - / _ blanks in this menu item you select the distance unit and the temperature unit. For the distance units you can choose between m, mm and ft and for the temper...

  • Page 30

    30 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 you have the option of choosing the demonstration mode. This mode is only suitable for test and demonstration purposes. In this mode, the sensor ignores the parameters of the application and reacts immedi- a...

  • Page 31

    31 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 in this menu item you can enter the max. Adjustment for the level. With interface measurement this is the maximum total level. Adjust the requested percentage value with [+] and store with [ok]. Enter the ap...

  • Page 32

    32 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 enter the requested percentage value for the max. Adjustment. As an alternative, you have the possibility taking over the adjustment of the level measurement also for the interface. Enter the respective dist...

  • Page 33

    33 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 if the probe is covered, enter the actual distance from the sensor to the product surface. All interfering signals in this section are detected by the sensor and stored. Keep in mind that with covered probe ...

  • Page 34

    34 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 user especially when setting the switching point on the limit signal transmitter. In the following, you have to enter the values for your vessel, for example the vessel height and the socket correction. For ...

  • Page 35

    35 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 in menu item"channel" you determine which measured value the output refers to. In menu item "scaling unit" you define the scaling variable and the scaling unit for the level value on the display, e.G. Volume...

  • Page 36

    36 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 with active pin, only the following adjustment functions are possible without entering a pin: • select menu items and show data • read data from sensor into the display and adjustment module. Caution: when t...

  • Page 37

    37 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 the default setting for the displayed value 2 is the electronics tem- perature. In this menu item, you define the display format of the measured value on the display. You can define different display formats...

  • Page 38

    38 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 the respective min. And max. Measured values are saved in the sensor. The two values are displayed in the menu item "peak values, measurement certainty". The measurement can be influenced by the process cond...

  • Page 39

    39 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 with the following functions you can zoom part sections of the echo curve. • "x-zoom": zoom function for the meas. Distance • "y-zoom": 1, 2, 5 and 10x signal magnification in "v" • "unzoom": reset the prese...

  • Page 40

    40 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 under the sub-menu item "echocurvememory" you can store the current echo curve. Parameter settings for recording the echo curve and the settings of the echo curve itself can be carried out in the adjustment ...

  • Page 41

    41 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 menu - setup menu menu item default value setup lock adjustment released measurement loop name sensor units distance unit: order-specific temperature unit: order-specific probe length länge der messsonde fac...

  • Page 42

    42 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 menu menu item default value setup ai fb1 tag descriptor ai fb1 channel primary value (lin. Percent level) ai fb1 scaling pv scale (min.) 0 % ai fb1 scaling pv scale (max.) 100 % ai fb1 lin. Type linear ai f...

  • Page 43

    43 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 menu menu item default value diagnostics device memory - echo curve memory stopped device memory - measured value memory started device memory - measured value memory - measured values distance level, percen...

  • Page 44

    44 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 menu menu item default value additional settings ai fb2 tag descriptor ai fb 2 channel primary value (lin. Percent level) ai fb2 scaling pv scale (min.) 0 % ai fb2 scaling pv scale (max.) 100 % ai fb2 lin. T...

  • Page 45

    45 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 the instrument settings are copied with this function. The following functions are available: • read from sensor: read data from sensor and save in the display and adjustment module • write to sensor: save d...

  • Page 46

    46 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 in this menu, you read out the instrument name and the instrument serial number. In this menu item, the hardware and software version of the sensor is displayed. In this menu item, the date of factory calibr...

  • Page 47

    47 6 set up with the display and adjustment module vegaflex 81 • profibus pa 44214-en-171002 • the values of the user-programmable linearisation curve the function can also be used to transfer settings from one instru- ment to another instrument of the same type. If it is necessary to exchange a sen...

  • Page 48: 7  Setup With Pactware

    48 7 setup with pactware vegaflex 81 • profibus pa 44214-en-171002 7 setup with pactware 7.1 connect the pc 3 1 2 fig.20:connectionofthepcdirectlytothesensorviatheinterfaceadapter 1 usbcabletothepc 2 interfaceadaptervegaconnect 3 sensor 7.2 parameter adjustment with pactware for parameter adjustment...

  • Page 49

    49 7 setup with pactware vegaflex 81 • profibus pa 44214-en-171002 fig.21:exampleofadtmview all device dtms are available as a free-of-charge standard version and as a full version that must be purchased. In the standard version, all functions for complete setup are already included. An assistant fo...

  • Page 50

    50 7 setup with pactware vegaflex 81 • profibus pa 44214-en-171002 fig. 22: select quick setup 1 quick setup 2 extendedadjustment 3 maintenance quick setup with quick setup you can carry out the parameter adjustment of vegaflex 81 for your application in just a few simple steps. The assistant-driven...

  • Page 51

    51 7 setup with pactware vegaflex 81 • profibus pa 44214-en-171002 7.4 saving the parameterisation data we recommend documenting or saving the parameterisation data via pactware. That way the data are available for multiple use or service purposes..

  • Page 52

    52 8 set up with other systems vegaflex 81 • profibus pa 44214-en-171002 8 set up with other systems 8.1 dd adjustment programs device descriptions as enhanced device description (edd) are available for dd adjustment programs such as, for example, ams™ and pdm. The files can be downloaded at www.Veg...

  • Page 53

    53 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 9 diagnostics and servicing 9.1 maintenance if the instrument is used correctly, no maintenance is required in normal operation. 9.2 diagnosis memory the instrument has several memories available for diagnostic pur- poses. The ...

  • Page 54

    54 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 • display and adjustment module further echo curves: up to 10 echo curves can be stored in a ring buffer in this memory section. Additional echo curves are stored via: • pc with pactware/dtm • control system with edd • display ...

  • Page 55

    55 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 this status message is inactive by default. It can be activated by the user via pactware/dtm or edd. The following table shows the codes and text messages of the status message "failure" and provides information on causes as we...

  • Page 56

    56 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 code text message cause rectification devspec diagnosis bits f264 installation/set- up error • adjustment not within the vessel height/measuring range • max. Measuring range of the instrument not sufficient • check for correct ...

  • Page 57

    57 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 code text message cause rectification tb diagnostics s603 impermissible operating voltage • operating voltage below specified range • check electrical connection • if necessary, increase operating voltage bit 26 the following t...

  • Page 58

    58 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 • constant level • filling • emptying the images in column "errorpattern" show the real level as a broken line and the level displayed by the sensor as a continuous line. 1 2 level time 0 fig. 24: the broken line 1 shows the re...

  • Page 59

    59 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 fault description error pattern cause rectification 4. Measured value re- mains momentarily unchanged during fill- ing and then jumps to the correct level level time 0 • turbulence on the product surface, quick filling • check ...

  • Page 60

    60 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 in ex applications, only instruments and electronics modules with ap- propriate ex approval may be used. If there is no electronics module available on site, the electronics module can be ordered through the agency serving you....

  • Page 61

    61 9 diagnostics and servicing vegaflex 81 • profibus pa 44214-en-171002 if a repair is necessary, please proceed as follows: • print and fill out one form per instrument • clean the instrument and pack it damage-proof • attach the completed form and, if need be, also a safety data sheet outside on ...

  • Page 62: 10 Dismount

    62 10 dismount vegaflex 81 • profibus pa 44214-en-171002 10 dismount 10.1 dismounting steps warning: before dismounting, be aware of dangerous process conditions such as e.G. Pressure in the vessel or pipeline, high temperatures, cor- rosive or toxic products etc. Take note of chapters "mounting" an...

  • Page 63: 11 Supplement

    63 11 supplement vegaflex 81 • profibus pa 44214-en-171002 11 supplement 11.1 technical data general data 316l corresponds to 1.4404 or 1.4435 materials, wetted parts Ʋ process fitting 316l and peek, alloy c22 (2.4602) and peek Ʋ process seal on the instrument side (rod leadthrough) fkm (shs fpm 70c...

  • Page 64

    64 11 supplement vegaflex 81 • profibus pa 44214-en-171002 second line of defense (optional) Ʋ the second line of defense (slod) is a second level of the process separation in the form of a gas-tight feedthrough in the lower part of the housing, preventing product from penetrating into the housing. ...

  • Page 65

    65 11 supplement vegaflex 81 • profibus pa 44214-en-171002 sensor address 126 (default setting) damping (63 % of the input variable) 0 … 999 s, adjustable profibus pa profile 3.02 number of fbs with ai (function blocks with analogue input) 3 default values Ʋ 1. Fb primary value (filling height linea...

  • Page 66

    66 11 supplement vegaflex 81 • profibus pa 44214-en-171002 2 4 5 3 1 2 4 5 3 1 fig.33:measuringranges-vegaflex81 1 reference plane 2 probe length l 3 measuring range (default setting refers to the measuring range in water) 4 upper dead band (see following diagrams - grey section) 5 lower dead band (...

  • Page 67

    67 11 supplement vegaflex 81 • profibus pa 44214-en-171002 l 0 -2 mm (-0.079 ") 2 mm (0.079 ") -10 mm (0.394 ") 5 mm (0.197 ") 0,15 m (5.906 " ) 0,03 m (1.181 " ) 0,05 m (1.969 ") 1 fig.34:deviationvegaflex81incoaxialversioninwater 1 dead band (no measurement possible in this area) l probe length l ...

  • Page 68

    68 11 supplement vegaflex 81 • profibus pa 44214-en-171002 gas phase temperature pressure 1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig) air 20 °c (68 °f) 0 % 0.22 % 1.2 % 200 °c (392 °f) -0.01 % 0.13 % 0.74 % 400 °c (752 °f) -0.02 % 0.08 % 0.52 % hydrogen 20 °c (68 °f) -0.01 % 0.1 % 0.61 % 2...

  • Page 69

    69 11 supplement vegaflex 81 • profibus pa 44214-en-171002 Ʋ with borosilicate glass leadthrough -60 … +150 °c (-76 … +302 °f) 1 2 3 4 a b 0°c / 32°f -40°c / -40°f 80°c / 176°f 45°c / 113°f 33°c / 91,4°f 50°c / 122°f 60°c / 140°f 150°c 302°f 100°c 212°f 50°c 122°f 80°c 176°f -40°c -40°f fig. 36: amb...

  • Page 70

    70 11 supplement vegaflex 81 • profibus pa 44214-en-171002 viscosity - dynamic 0.1 … 500 mpa s (requirement: with density 1) vibration resistance Ʋ coax probe 1 g with 5 … 200 hz according en 60068-2-6 (vibration at resonance) with tube length 50 cm (19.69 in) shock resistance Ʋ coax probe 25 g, 6 m...

  • Page 71

    71 11 supplement vegaflex 81 • profibus pa 44214-en-171002 display and adjustment module display element display with backlight measured value indication Ʋ number of digits 5 Ʋ size of digits w x h = 7 x 13 mm adjustment elements Ʋ 4 keys [ok], [->], [+], [esc] Ʋ switch bluetooth on/off bluetooth in...

  • Page 72

    72 11 supplement vegaflex 81 • profibus pa 44214-en-171002 Ʋ ex-ia instrument - power supply fisco model 9 … 17.5 v dc Ʋ ex-ia instrument - power supply entity model 9 … 24 v dc Ʋ ex-d-ia instrument 16 … 32 v dc operating voltage u b - illuminated display and adjustment module Ʋ non-ex instrument 13...

  • Page 73

    73 11 supplement vegaflex 81 • profibus pa 44214-en-171002 Ʋ with connected overvoltage protection up to 5000 m (16404 ft) pollution degree 7) 4 protection rating (iec 61010-1) iii approvals instruments with approvals can have different technical specifications depending on the version. For that rea...

  • Page 74

    74 11 supplement vegaflex 81 • profibus pa 44214-en-171002 fig.38:vegaflex81:blockdiagramwithaifb1…aifb3outvalues tb transducer block fb1…fb3 functionblock module of the pa sensors for the cyclic data traffic, vegaflex 81 provides the following modules: • ai fb1 (out) – out value of the ai fb1 after...

  • Page 75

    75 11 supplement vegaflex 81 • profibus pa 44214-en-171002 • long for profibus master only supporting the "identifier format" byte, e.G. Siemens s7-300/400 examplesoftelegramconfiguration in the following you will see how the modules can be combined and how the appendant data tel- egram is structure...

  • Page 76

    76 11 supplement vegaflex 81 • profibus pa 44214-en-171002 coding of the status byte associated with the pa output value you can find further information for the coding of the status byte in the device description 3.02 on www.Profibus.Com. Status code description according to profibusstandard possib...

  • Page 77

    77 11 supplement vegaflex 81 • profibus pa 44214-en-171002 11.3 dimensions the following dimensional drawings represent only an extract of all possible versions. Detailed dimensional drawings can be downloaded at www.Vega.Com/downloads under "drawings". Plastic housing ~ 69 mm (2.72") ø 79 mm (3.11"...

  • Page 78

    78 11 supplement vegaflex 81 • profibus pa 44214-en-171002 aluminium housing with protection rating ip 66/ip 68 (1 bar) 120 mm (4.72" ) ~ 105 mm (4.13") 116 mm (4.57" ) ~ 150 mm (5.91") ø 86 mm (3.39") ø 86 mm (3.39") m20x1,5/ ½ npt m16x1,5 2 m20x1,5 m20x1,5 1 fig. 43: housing version with protectio...

  • Page 79

    79 11 supplement vegaflex 81 • profibus pa 44214-en-171002 stainless steel housing with protection rating ip 66/ip 68, 1 bar 117 mm (4.61") ~ 103 mm (4.06") ø 79 mm (3.11") 120 mm (4.72") ~ 105 mm (4.13") ø 86 mm (3.39") m20x1,5 m20x1,5/ ½ npt m16x1,5 ~ 93 mm (3.66") ø 80 mm (3.15") 112 mm (4.41" ) ...

  • Page 80

    80 11 supplement vegaflex 81 • profibus pa 44214-en-171002 vegaflex 81, coax version l sw 36 (1.42") (g¾, ¾ npt) sw 41 (1.61") (g1, 1 npt) sw 46 (1.81") (g1½, 1½ npt) g¾, ¾ npt, g1, 1 npt, g1½, 1½ npt 46 mm (1.81" ) ø 21,3 mm (0.84") l 22mm (0.86" ) ø 42,2 mm (1.66") sw 55 (2.17") 51 mm (2.01" ) g1½...

  • Page 81

    81 11 supplement vegaflex 81 • profibus pa 44214-en-171002 11.4 industrial property rights vega product lines are global protected by industrial property rights. Further information see www.Vega.Com. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte. Nähere informationen un...

  • Page 82: Index

    82 index vegaflex 81 • profibus pa 44214-en-171002 index a adjustment – max. Adjustment 31 – min. Adjustment 31, 32 adjustment system 26 ai fb1 function block 34 application 29, 30 application area 8 b backlight 37 c channel 35 copy sensor settings 45 curve display – echo curve 38 cyclical data traf...

  • Page 83

    83 index vegaflex 81 • profibus pa 44214-en-171002 sensor status 37 service hotline 59 simulation 39 software addressing 23, 28 special parameters 45 status bytes pa output value 76 t telegram configuration 75 type label 7 type of medium 29 u units 29.

  • Page 84

    Printing date: vega grieshaber kg am hohenstein 113 77761 schiltach germany 44214-en-171002 all statements concerning scope of delivery, application, practical use and operat- ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subjec...