Vega VEGAKON 66 Operating Instructions Manual

Manual is about: Conductive multiple rod level switch for liquids

Summary of VEGAKON 66

  • Page 1

    Operating instructions vegakon 66 with relay output conductive.

  • Page 2: Contents

    Contents 1 about this document 1.1 function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 target group . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 symbolism used . . . . . . . . . . . . . . . . . . . . . . . 4 2 for your safety 2.1 authorised personnel . . . . . . . ....

  • Page 3

    9 supplement 9.1 technical data. . . . . . . . . . . . . . . . . . . . . . . . . 23 9.2 dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 9.3 industrial property rights. . . . . . . . . . . . . . . . . . 27 9.4 trademark . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 vega...

  • Page 4: 1 A

    1 a bout this document 1 .1 function this operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and kee...

  • Page 5: 2 F

    2 f or your safety 2 .1 authorised personnel all operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. During work on and with the device the required personal protection equipment must always be worn. 2 .2 app...

  • Page 6

    L emc: - emission en 50081-1 - susceptibility en 50082-2 l lvd: en 61010 2 .6 environmental instructions protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pr...

  • Page 7: 3 P

    3 p roduct description 3 .1 configuration the scope of delivery encompasses: l vegakon 66 compact level switch l documentation - this operating instructions manual vegakon 66 consists of the following components: l housing cover l housing with electronics l process fitting with electrodes 1 2 3 fig. 1...

  • Page 8

    3 .2 principle of operation the conductive vegakon 66 compact level switches detect levels of conductive liquids. If at least two electrodes are covered with a conductive medium, small alternating currents ( measuring electrode to the ground electrode. 1 3 2 fig. 2: functional principle 1 ground pro...

  • Page 9

    3 .3 operation the vegakon 66 is a compact level switch with integrated oscillator. On the electronics module you will find the following indicating and adjustment elements: l control lamp for indication of the switching condition l mode changeover for selection of the output signal l dil switch for ...

  • Page 10: 4 M

    4 m ounting 4 .1 general instructions use the recommended cables (see chapter "connecting to power supply") and tighten the cable gland. You can give your vegakon 66 additional protection against moisture penetration by leading the connection cable down- ward in front of the cable entry. Rain and co...

  • Page 11

    1 2 1 2 fig. 4: fasten the probe 1 probe 2 plastic socket on the probe end 3 probe 4 plastic socket laterally mounted vegakon 66 - with relay output 11 mounting 32649 - en -070615.

  • Page 12: 5 C

    5 c onnecting to power supply 5 .1 preparing the connection always keep in mind the following safety instructions: l connect only in the complete absence of line voltage connect the power supply according to the following diagrams. Oscillator kone60r is designed in protection class 1. To maintain th...

  • Page 13

    1 2 - + l1 n 3 4 5 6 7 8 1 2 fig. 5: electronics with relay output 1 relay output 2 power supply vegakon 66 - with relay output 13 connecting to power supply 32649 - en -070615.

  • Page 14: 6 S

    6 s et up 6 .1 general on the electronics module you will find the following indicating and adjustment elements: l dil switch for mode adjustment l dil switch for adjustment of the integration time l rotary switch for adjustment of the conductivity value l control lamp for indication of the switching...

  • Page 15

    With the rotary switch you can set the sensitivity of the instrument. Position 0.1 kΩ is the less sensitive and switch position 300 kΩ the most sensitive one, see chart "switching point adjustment". There are three switches on the dil switch block by which you can adjust the switching on and off dela...

  • Page 16

    Examples of conductivity values medium conductivity value recommended rotary switch position tap water 0.2 ms 3 kΩ saltwater (3.5 %) 35 ms 0.1 kΩ beer 1.4 ms 1 kΩ fruit juice 2 ms 0.3 kΩ milk, yogurt 3 ms 0.3 kΩ ketchup 15 ms 0.1 kΩ in case of horizontally mounted instruments, the response height is...

  • Page 17

    If there is danger of strong buildup or condensation, you can set the instrument more insensitive by one rotary switch position. The "function chart" shows how to select the switching condition of the output. The following settings apply to products with low conductivity ( 1 fill the vessel until th...

  • Page 18

    The instrument is adapted to the medium, i.E, the relay deenergizes when the max. Level is reached. Only when the min. Probe is decreased, the relay energizes again. Example: a filling pump is switched on when the min. Signal is decreased, fills the vessels until max. Signal is reached and is then swi...

  • Page 19

    Level switching sta- tus, relay mod- ule e60r control lamp mode a overflow protec- tion 1 relay energized 5 3 4 (8) (6) (7) does not light mode a overflow protec- tion 2 relay deener- gized 5 3 4 (8) (6) (7) lights mode b dry run protection 3 relay energized 5 3 4 (8) (6) (7) does not light mode b dry...

  • Page 20: 7 M

    7 m aintenance and fault rectification 7 .1 maintenance when used as directed in normal operation, vegakon 66 is completely maintenance free. 7 .2 electronics exchange in general, all oscillators of series kone66 can be inter- changed. If you want to use an oscillator with a different signal output, y...

  • Page 21

    As soon as you insert the electronics module, vegakon 66 is ready for operation. 7 .3 simulation of switching functions with the rotary switch for conductivity adjustment, full covering or empty signal can be simulated. The filling height must not be changed. You can hence easily check the response o...

  • Page 22: 8 D

    8 d ismounting 8 .1 dismounting steps warning: before dismounting, be aware of dangerous process con- ditions such as e.G. Pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "mounting" and "connecting to power supply" and carry out the listed steps in r...

  • Page 23: 9 S

    9 s upplement 9 .1 technical data general data material 316l corresponds to 1.4404 or 1.4435 materials, wetted parts - process fitting - thread pp - electrode 316ti - process seal klingersil c-4400 materials, non-wetted parts - housing plastic pbt (polyester), alu die-casting pow- der-coated - temper...

  • Page 24

    Breaking capacity - min. 50 mw - max. 750 va ac, 54 w dc if inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be permanently damaged. The contact is then no longer suitable for switching low-level signal circuits. Contact material (relay co...

  • Page 25

    Electrical protective measures protection - plastic housing ip 66 - aluminium housing ip 66/ip 67 overvoltage category ii protection class i vegakon 66 - with relay output 25 supplement 32649 - en -070615.

  • Page 26

    9 .2 dimensions l2 l3 l1 ~75mm (2 61 / 64 ") ø 4mm ( 5 / 32 ") 85mm (3 11 / 32 ") 92,5 mm (3 41 / 64 ") 24mm ( 15 / 16 ") 11 2mm (4 13 / 32 ") g1½a sw 60mm (2 23 / 64 ") m20x1,5 fig. 21: vegakon 66 with three probes l1 length ground probe l2 length max. Probe l3 length min. Probe 26 vegakon 66 - wit...

  • Page 27

    9 .3 industrial property rights vega product lines are global protected by industrial property rights. Further information see http://www.Vega.Com. Only in u.S.A.: further information see patent label at the sensor housing. Vega produktfamilien sind weltweit geschützt durch gewerbliche schutzrechte....

  • Page 28

    Vega grieshaber kg am hohenstein 113 77761 schiltach germany phone +49 7836 50-0 fax +49 7836 50-201 e-mail: info@de.Vega.Com www.Vega.Com iso 9001 all statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the...