Vent-Axia 405215 Advance S Installation & Commissioning Manual

Other manuals for 405215 Advance S: Installation And User Manual
Manual is about: Mechanical Ventilation/Heat Recovery (MVHR)

Summary of 405215 Advance S

  • Page 1

    Copyright © 2009 vent-axia limited. All rights reserved. Sentinel kinetic advance mvhr installation & commissioning stock ref. N° 405215 advance s 405216 advance sx please retain these instructions with the product. 408651.

  • Page 2

    Warnings and safety information 2 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 warnings and safety information please read these instructions carefully before commencing installation. 1. Do not install this product in areas where the following may be present or o...

  • Page 3

    Warnings and safety information sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 3 installation guidance 1. The installer is responsible for the installation and electrical connection of the sentinel system on site. It is the responsibility of the installer to ensure...

  • Page 4

    About this document 4 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 about this document contents warnings and safety information installation guidance ..................................................................... 3 about this document contents ...............

  • Page 5

    Technical data sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 5 technical data product description the vent-axia sentinel kinetic advance models s & sx mechanical ventilation/heat recovery (mvhr) is a heat recovery unit designed for the energy efficient ventilation...

  • Page 6

    Technical data 6 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 accessories  472703 wifi controller accessory the wifi controller is a plug & play accessory that fits next to the control module. This offers the user instant access to various functions and features...

  • Page 7

    Technical data sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 7 technical specification performance sentinel kinetic advance s sentinel kinetic advance sx airflow maximum, fid, 115 l/s (414 m 3 /h) low default 20% normal default 30% boost default 50% purge default ...

  • Page 8

    Technical data 8 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 product dimensions figure 2: sentinel kinetic advance dimensions remove front cover (see page 17) to view rating label. (label is positioned to the right of the controller)..

  • Page 9

    Technical data sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 9 sentinel kinetic advance summer bypass the sentinel kinetic advance includes a unique summer bypass (sbp) feature to provide energy-free cooling when the house temperature and ambient temperature allow...

  • Page 10

    Technical data 10 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 performance data fig 3 sentinel kinetic advance performance graph static pressure (pa).

  • Page 11

    Installation sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 11 installation overview the following instructions are intended to help prevent potential hazards and installation should only be carried out by a qualified electrician and installer. This booklet covers ...

  • Page 12

    Installation 12 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 wall mounting the unit step 1: mark the wall bracket position using the dimensions shown. Note the position of the top of the unit in relation to the wall bracket. Ensure the bracket position is horizon...

  • Page 13

    Installation sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 13 floor mounting the unit step 1: the unit has 44 x 12mm deep fixing holes on the underside suitable for a no.6 screw. Pre drill a board using the dimensions shown, and cut 2 x 105mm minimum diameter hole...

  • Page 14

    Installation 14 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 floor mounting the unit (alternate method) step 1: the unit has 44 x 12mm deep fixing holes on the underside suitable for a no.6 screw. The holes are configured to allow fitment of most standard kitchen...

  • Page 15

    Installation sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 15 vertical discharge condensate installation note the kinetic advance condensate outlet is compatible with standard 22 mm plastic push-fit fittings and 32mm plastic waste pipe fittings. A water trap must ...

  • Page 16

    Installation 16 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 attach the ducting 1. Always use a short piece of insulated flexible duct 100-150 mm long, extended to its full length when connecting to ductwork. 2. Securely connect this ducting to the spigots using ...

  • Page 17

    Installation sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 17 electrical installation step 1: remove the outer cover by pressing the tabs either side of the control module and lifting the cover outwards from the bottom edge. Step 2: remove the control module by li...

  • Page 18

    Installation 18 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 connect switches and sensors the unit can be switched to boost by a variety of methods: applying 240 v to the ls input . Switching across 1 pair of switch terminals. N.B alternative switches and inputs ...

  • Page 19

    Installation sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 19 terminal no. Name description (control mode 01) remote remote terminals for connecting a remote externally from the unit. Swi switch 1 volt-free contact for sensor input between + and - terminals led re...

  • Page 20

    Installation 20 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 connect the power supply warnings 1. Mains supply voltages (220-240 v ac) are present in this equipment which may cause death or serious injury by electric shock. Only a qualified electrician or install...

  • Page 21

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 21 commissioning powering up the unit switching on to switch the unit on: 1. Switch on the power at the mains supply isolator feeding the unit. 2. Following switch-on, the fan motors will start and the co...

  • Page 22

    Commissioning 22 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 commissioning menu when powering up the unit for the first time, the controller will automatically scroll through the commissioning menu ‘modify settings’ screens (see page 24) allowing the installer t...

  • Page 23

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 23 commissioning screens summary when the unit is switched on (see powering up the unit on page 21, the following control unit screens are available for commissioning the unit..

  • Page 24

    Commissioning 24 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 commissioning modify settings the following pages show all available settings withing the commissioning menu. Please note that some settings may not apear, or may be in a different order, due to pre-co...

  • Page 25

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 25 filter check select the time interval for checking the filters using the / buttons on the screen, between 1 month and 18 months. Note: there is an automatic filter check after the first 3 months irresp...

  • Page 26

    Commissioning 26 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 port allocation if the installation has switch sensors, is wired to the lighting, has vent-wise sensors or vent-wise momentary switch, the mode parameters can be set for each port. The unit will automa...

  • Page 27

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 27 summer bypass adjust the summer bypass settings. Select each setting to adjust bypass mode, indoor and outdoor temperatures and go to modes. Select the required bypass mode. Details of each mode can be...

  • Page 28

    Commissioning 28 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 internal rh trip the integral humidity sensor increases airflow speed in proportion to relative humidity levels. The sensor also reacts to small but rapid increases in humidity, even if the normal trig...

  • Page 29

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 29 frost protection frost protection is required to prevent the heat exchanger freezing at low temperatures. The process is fully automatic. Airflow mode reduces the intake flow and increases the extract ...

  • Page 30

    Commissioning 30 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 mode scheduling use a schedule to set a mode (airflow setting) for a fixed, repeated period. For example, set boost mode every morning between 7:00am and 8:00am while cooking breakfast. Select the sche...

  • Page 31

    Commissioning sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 31 service phone the service phone screen enables the installer to enter the telephone number that should be called for service in the event of a unit fault or for routine maintenance. Enter the number us...

  • Page 32

    Operation and monitoring 32 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 operation and monitoring control unit screens summary the following control unit screens are available for daily operation and monitoring of the unit. Refer to installation and commissi oni ...

  • Page 33

    Operation and monitoring sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 33 control unit screens summary the following control unit screens are available in the settings / performance section..

  • Page 34

    Operation and monitoring 34 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 user controls user menu home screen the user menu home screen, consists of a user mode (boost) button, a machine status bar, and a settings / performance bar. The machine status scrolls thro...

  • Page 35

    Operation and monitoring sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 35 settings and performance settings scroll through the settings using the & buttons and select using where applicable to access language, date, time, reset filter, display settings, summer byp...

  • Page 36

    Operation and monitoring 36 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 time change the time using the / buttons on the screen. Note: the clock is 24 hour reset filter after maintenance or replacement of the filters, the filter timer can be reset by pressing . P...

  • Page 37

    Operation and monitoring sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 37 summer bypass adjust the summer bypass settings. Select each setting to adjust bypass mode, indoor and outdoor temperatures and go to modes. Select the required bypass mode. Details of each ...

  • Page 38

    Operation and monitoring 38 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 mode scheduling use a schedule to set a mode (airflow setting) for a fixed, repeated period. For example, set boost mode every morning between 7:00am and 8:00am while cooking breakfast. Sele...

  • Page 39

    Operation and monitoring sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 39 service phone the service phone number can be entered by the installer and should be used if the unit displays a fault code, or to arrange routine servicing for the unit. Commissioning menu ...

  • Page 40

    Operation and monitoring 40 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 default settings parameters settings commissioning screens country united kingdom language english. Date automatic - factory set time automatic gmt/bst - factory set unit configuration right...

  • Page 41

    Maintenance sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 41 maintenance filter maintenance heat recovery units require regular maintenance. The sentinel kinetic has been designed to facilitate access to enable maintenance to be carried out easily. When the unit d...

  • Page 42

    Maintenance 42 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 periodic maintenance warning the fan and ancillary control equipment must be isolated from the power supply during maintenance. Fan filters check fan filters as described on the previous page. Heat excha...

  • Page 43

    Maintenance sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 43 spares the following spare parts may be ordered from vent-axia: part no description 472663 main power board 472665 control module 472667 filters g3, 2 per pack 472669 filters m5, 1 per pack 472671 filter...

  • Page 44

    Troubleshooting 44 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 troubleshooting diagnosing a problem in the event of a problem, always troubleshoot the unit according to: fault code displayed on the control unit. Fault led if connected. If no indications are disp...

  • Page 45

    Notes sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 45 this page is intentionally blank and can be used for making notes regarding the unit..

  • Page 46

    Notes 46 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 this page is intentionally blank and can be used for making notes regarding the unit..

  • Page 47

    Product fiche sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 47 product fiche product fiche name: vent‐axia model id (stock ref.) : kinetic advance s ‐ 405215 sec class a+ sec value ('average') ‐43.70 sec value ('warm') ‐18.32 sec value ('cold') ‐88.78 label requir...

  • Page 48

    Notes 48 sentinel kinetic advance mvhr installation & commissioning instructions pn 408651 head office: fleming way, crawley, west sussex, rh10 9yx. Uk national call centre, newton road, crawley, west sussex, rh10 9ja sales enquiries: tel: 0344 8560590 fax: 01293 565169 technical support tel: 0344 8...