Vents Micra 60 User manual - page 8
8
Micra 60
Micra 60
MOUNTING AND SET-UP
The unit mounting is carried out with the master plate from the delivery set and two air ducts of required length or any of the mounting
kits, MK1 Micra 60 or MK2 Micra 60 (special accessories).
The mounting set MK1 Micra 60 is specially designed for mounting of the unit at general construction stage. It includes two plastic air
ducts, 500 mm (19 11/16”) long and two master plates for marking holes on inner and outer wall sides.
The mounting set MK2 Micra 60 is specially designed for mounting of the unit in a ready-built premise. It includes two plastic air ducts,
500 mm (19 11/16”) long, a master plate for marking holes and an outer ventilation hood NB Micra 60 that prevents ingress of foreign objects
inside the unit. If the building’s wall thickness is above 500 mm (19 11/16”) prepare two extra Ø 125 mm (Ø 5”) air ducts of required length.
drill 2 holes in the wall, 60 mm (2 3/8”)
deep, with a Ø 8 mm (Ø 5/16”) tool.
2 holes for the round Ø 125 mm (Ø 5”)
duct. Fill the gaps between the wall and
the air duct with a mounting foam.
239 (9 7/16")
160 (6 5/16")
503 (19 13/16")
89,5 (3 1/2")
160 (6 5/16")
2 holes for the round Ø 125 mm (Ø 5”) duct. Fill
the gaps between the wall and the air duct
with a mounting foam.
drill 2 holes in the wall, 60 mm (2 3/8”)
deep, with a Ø 8 mm (Ø 5/16”) tool.
PAPER MASTER PLATE FOR HOLE MARKING [MM] (INCHES)
UNIT MOUNTING
The unit is mounted as follows:
1. Fix the master plate from the delivery set on the wall with a sealing
tape on a required level.