VOKERA Eclipse 216 ESS Installation & Servicing Instructions Manual - page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
4
2.12
PUMP DUTY
Fig. 3 shows the flow rate available – after allowing
for pressure loss through the appliance – for
system requirements. When using this graph
apply only the pressure loss of the system. The
graph is based on 20
°
C temperature differential.
Fig. 4
This appliance must be installed by a competent
person in accordance with the Gas Safety (Instal-
lation & Use) Regulations.
3.1
RELATED DOCUMENTS
The installation of this boiler must be in accord-
ance with the relevant requirements of the Gas
Safety (Installation & Use) Regulations, the local
building regulations, the current I.E.E. wiring
regulations, the bylaws of the local water
undertaking, the Building Standards (Scotland)
Regulation and Building Standards (Northern
Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard
Codes of Practice.
Terminal position for fan assisted boiler
(minimum distance)
mm
A
-
Directly above or below an open window
300
or other opening (e.g. air brick)
B
-
Below gutters, soil pipes or drain pipes
25
C
-
Below eaves
25
D
-
Below balconies or car port roof
25
E
-
From vertical drain pipes and soil pipes
75
F
-
From internal or external corners
25
G
-
Above ground or below balcony level
300
H
-
From a surface facing a terminal
600
I
-
From a terminal facing a terminal
1200
J
-
From an opening in the car port (e.g. door
window) into dwelling.
1200
K
-
Vertically from a terminal on the same wall
1500
L
-
Horizontally from a terminal on the same wall
300
M
-
Horizontally from a vertical terminal to a wall
300
N –
Horizontally from an opening, airbrick, openable
window, etc.
300
NOTE:The flue must be terminated in a place not likely to cause a
nuisance.
SECTION 3
GENERAL REQUIREMENTS
3.2
LOCATION OF APPLIANCE
The appliance may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
wiring regulations, and in Scotland, the electrical
provisions of the Building Regulations, with
respect to the installation of the appliance in a
room or internal space containing a bath or shower.
When an appliance is installed in a room or
internal space containing a bath or shower, the
appliance or any control pertaining to it must not
be within reach of a person using the bath or
shower.
The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and
termination. The location must also permit an
adequate air supply for combustion purposes
Fig. 3
Water pressure (mbar)
Litres Per Hour (x100)
0 100 200 300 400 500 600 700 800
600
500
400
300
200
100
900 1000 1100 1200 1300 1400