Wacker Neuson AD Series Operator's Manual - Ad ...
wagtx5700000016en.fm
9
AD ...
Operation
4.
Operation
4.1
Installation
Caution
The mains for supplying power to the machine (230 V, single phase,
50 Hz) must be grounded and equipped with a fault current protective
switch.
Set up the air dehumidifier in the middle of the room to be dehumidi-
fied. The air suction side and the air discharge side must not be ob-
structed. The minimum distance from the walls should be 20 - 30 cm.
Do not set up the machine near heat sources (for example radiators,
ovens, heat outlets etc.) or near doors or openings. Doors and win-
dows in the room must remain closed while the air dehumidifier is in
operation.
Caution
Do not place any rags or cloths on the air dehumidifier.
If required, you can conduct the water formed by dehumidification di-
rectly to a drain. To do this, remove the water collecting pan (9) and
connect a rubber hose to the condensate outlet (7).
4.2
Using the machine
4.2.1
Turning the machine on and off
Caution
Always keep the air dehumidifier in the vertical position (during opera-
tion, storage and, with model AD 22, during transport).
To turn on the air dehumidifier, proceed as follows:
* Turn the rotary control (d) of the moisture meter in the clockwise di-
rection to the marking "20 %".
* Set the green main switch (a) to the "ON" position. The fan and com-
pressor are turned on. The control lamp in the switch is lit.