WAGNER SUNGO S Operating Instructions Manual - page 10
10
EN-SUNGO-S_BA-0804-1122P200
4.6 Service – System Messages
Display of system information
Display
Description
Correction
System Messages
All system messages are displayed with a blinking caution symbol.
In case of sensor errors the sensor in question is also marked with short circuit or interruption symbols.
Interruption
Displayed sensor or line connection interrupted
/ defunct.
●
Check the resistance value of the sensor and
compare to the resistance table.
●
Check all contact points up to the sensor.
Short circuit
There is a short circuit of the sensor on the
display, the line or the sensor input on the
controller.
dT too high
A fixed value of 20 K is added to the
temperature difference between collector (T1)
and tank sensor (T2). The message is displayed
if after 30 minutes the total temperature
difference has not been reduced.
●
Check pump/pump connections/wiring.
●
Check system for air, and vent if required.
●
Check sensors/sensor lines and change sensor if
required.
4.7 Service – Sensor Control
Resistance values for Pt1000-sensors in relation to the temperature
-10 °C
0 °C
10 °C
20 °C
30 °C
40 °C
50 °C
60 °C
70 °C
80 °C
90 °C
100 °C
110 °C
961
Ω
1000
Ω
1039
Ω
1078
Ω
1117
Ω
1155
Ω
1194
Ω
1232
Ω
1271
Ω
1309
Ω
1347
Ω
1385
Ω
1423
Ω
The working condition of the sensor can be checked with this table and an Ohm meter.
!