Waldorf 800 Series RN8910GE Installation And Operation Manual - page 26
24
Gas Conversion and Specifications
Gas Regulator
NOTE:
Gas regulator supplied is
convertible between Natural Gas
and LP Gas, but it’s outlet
pressure is fixed ex-factory and is
NOT to be adjusted.
- Town Gas Only.
1.
Remove slotted cap from regulator.
2.
Turn ‘On’ gas supply and appliance.
3.
Adjust pressure adjusting screw to achieve correct burner
operating pressure.
NOTE: Measure operating pressure at manifold test point
with two burners operating at 'High Flame' setting.
4.
Verify operating pressure remains correct (Re-adjust regulator
if required).
5.
Screw cap nut back onto regulator.
Gas Type Identification Label
On completion of gas conversion, replace gas type identification label located at:-
- Rear of appliance, above gas connection point.
- Beside rating plate.
Commissioning
Before leaving the installation;
1.
Check all gas connections for leakage using soapy water or other gas detecting equipment.
2.
Carry out a ‘Commissioning’ check of appliance as shown in Installation Section of this manual.
3.
Ensure any paint sealed components are re-sealed on completion of adjustments.
NOTE, Pin rotated
for Natural Gas
NOTE, Pin rotated
for LPG