WarmFlow B-Series B120 Owner's Manual - page 7
Page 5
1.0 GeneralInformation
1.1 Introduction
Note: All our domestic appliances have been independently tested and
accreditedasexceedingtheminimumSEDBUKefficiencylevelsrequiredfor
theirtype,incompliancewiththeBuildingRegulationsApprovedDocument
L1A, L1B for England and Wales, the Building Standards (Scotland)
Regulations Section 6, Part F Northern Ireland and Part L Republic of
Ireland.
Warmflow standard efficiency boilers are designed for use only on fully pumped
(sealed or open-vented) heating systems and to burn Class C2 kerosene and
Class D gas oil. Note that with class D gas oil the flue MUST exhaust at more than
2m above the surrounding ground level. The low-level flue supplied as standard with
all Kabin Pak models is NOT suitable for Class D gas oil. Alternative options are
available – please contact Warmflow.
As standard the Combi and System boilers are fitted with a system expansion
vessel, circulating pumps, filling loop, pressure gauge and safety valve. An optional
7-day electronic programmer kit is also available for all Utility boiler models.
The Combi can provide at mains pressure domestic hot water without the need for
a storage cylinder.
Themanufacturer’sguaranteesarevoidiftheapplianceisnotinstalledand
commissionedinaccordancewiththerecommendationsmadeherein.
1.2 GeneralRequirements
The installation of the boiler must be in accordance with the following regulations.
BS540 : PART Code of practice for oil firing.
BS5449 : PART Forced circulation hot water systems.
BS7593 : Treatment of water in domestic hot water central heating systems.
Current Building Regulations Part J England and Wales
Section 3 Scotland
Part L Northern Ireland
Part J Republic of Ireland
Current IEE Regulations
BS7074 : PART Application Selection & Installation of Expansion Vessels
The heating system should be installed by a competent installer in accordance with
the recommendations laid down by HVCA, OFTEC and sound engineering practice.
In order to comply with the building regulations OFTEC forms CD10 for
installationsandCD11forcommissioningshouldbeleftwiththecustomer.
Alternatively the installation can be inspected and approved by a building
control officer. CD10 and CD11 forms are available from OFTEC on
Tel:08456585080,Fax:08456585181.