Waterstage Air to Water Operation Manual - page 14
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Time program 5 / Cooling
If the installation is fitted with the cooling kit (Only with the cooling kit option).
600
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
601
1st phase On (start)
00:00... --:--
10 min
8:00
602
1st phase Off (end)
00:00... --:--
10 min
20:00
603
2nd phase On (start)
00:00... --:--
10 min
--:--
604
2nd phase Off (end)
00:00... --:--
10 min
--:--
605
3rd phase On (start)
00:00... --:--
10 min
--:--
606
3rd phase Off (end)
00:00... --:--
10 min
--:--
615
Copy
616
Default values
No, Yes
No
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs. Your
customised settings are therefore lost.
Holidays, heating circuit 1 (For the Holiday program is active, the heating mode should be on AUTO).
641
Preselection
Period 1 to 8
Period 1
642
Period Start (Day / Month)
01.01... 31.12
1
643
Period End (Day / Month)
01.01... 31.12
1
648
Operating level
Frost protection, Reduced
Frost
protection
Holidays, heating circuit 2 (For the Holiday program is active, the heating mode should be on AUTO).
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
651
Preselection
Period 1 to 8
Period 1
652
Period Start (Day / Month)
01.01... 31.12
1
653
Period End (Day / Month)
01.01... 31.12
1
658
Operating level
Frost protection, Reduced
Frost
protection
Heating, circuit 1
710
Comfort setpoint
Reduced setpoint… 28 °C
0,5 °C
20 °C
712
Reduced setpoint
Frost protection setpoint…
Comfort setpoint
0,5 °C
19 °C
714
Frost protection setpoint
4 °C… Reduced setpoint
0,5 °C
8 °C
Cooling circuit 1
If the installation is fitted with the cooling kit (Only with the cooling kit option).
901
Operating mode
Off, Automatic
Off
902
Comfort cooling setpoint
17... 40 °C
0,5 °C
24 °C
907
Release
24h/day, Time program HC,
Time program 5 / Cooling
Time
program 5
If the installation is fitted with a DHW tank, set the parameter 907 to "Time program 5 / Cooling"
(In order to activate cooling only during the day and leave the DHW system to operate during the night).
Heating, Circuit 2
Only with the 2nd circuit kit option (If the installation consists of 2 heating circuits).
1010
Comfort setpoint
Reduced setpoint… 28 °C
0,5 °C
20 °C
1012
Reduced setpoint
Frost protection setpoint…
Comfort setpoint
0,5 °C
19 °C
1014
Frost protection setpoint
4°C… Reduced setpoint
0,5 °C
8 °C