Wattstopper DT-200 Installation Instructions Manual - page 4
WIRING DIRECTIONS
Each WattStopper B series power pack can supply power for up to 2 DT-200
sensors. Each WattStopper BZ series power pack can supply power for 3 DT-200
sensors. When using more sensors than this, multiple power packs are required.
Refer to the wiring diagram on the next page for the following procedures:
Connect the LOW VOLTAGE:
• RED wire (+24VDC) from power pack to the violet wire on the sensor.
• BLACK wire (Return) from power pack to the gray wire on the sensor.
Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY– connect:
• BLUE wire from power pack to the yellow wire on the sensor.
To add a MOMENTARY MANUAL SWITCH such as the LVS-1 Momentary Toggle
Switch, to the above applications–connect:
• Wire from one side of switch to the green wire on sensor.
• Wire from other side of switch to the gray wire on sensor.
Wiring the ISOLATED RELAY: (The Isolated Relay is rated for 1A@30VAC/VDC)
Connect the wires necessary to the application that requires this output:
• Relay Common (must be used for proper operation) is the red wire
• N.O. (Normally Open)–Closed when occupancy is detected, is the orange wire
• N.C. (Normally Closed)–Open when occupancy is detected, is the brown wire
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS OR SENSORS.
Call 800.879.8585 for Technical Support