WIRING DIRECTIONS
CAUTION
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING POWER PACKS, SWITCHES OR SENSORS.
Each Watt Stopper B series
power pack can supply power
for up to 2 DT-300 sensors.
Each Watt Stopper BZ series
power pack can supply power
for 3 DT-300 sensors. When
using more sensors than this,
multiple power packs are
required.
Refer to the wiring diagram
on the next page for the
following procedures:
Connect the low voltage:
• RED wire (+24VDC)
from power pack to the
+24V terminal on the
sensor.
• BLACK wire (Return) from power pack to Common terminal on the sensor.
Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY–connect:
• BLUE wire from power pack to Control Out terminal on sensor.
To add a MANUAL SWITCH such as the LVS-1 Momentary Toggle Switch, or RS2-3
Low Voltage Momentary Switch to the above applications (see wiring diagram
“Manual-On wiring with low voltage momentary switch”) – connect:
• Wire from one side of switch to Common terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
Wiring the Isolated Relay: The Isolated Relay is rated for 1A@30VAC/VDC. Connect
the wires necessary to the application that requires this output:
• Relay Common (must be used for proper operation)
• N.O. (Normally Open)–Closed when occupancy is detected
• N.C. (Normally Closed)–Open when occupancy is detected
DT-300
360° Dual Technology
Occupancy Sensor
U.S.Patents:
5,124,566
5,640,113
Patent Pending
PIR & 40kHz Ultrasonic
+24VDC/VAC
Connect to Watt Stopper
Class 2 Power Packs
For Indoor Use Only
Model#:
02828r3
C US
LISTED
88T9
Appliance
Control
Santa Clara, CA
800.879.8585
Relay Com.
N.O.
N.C.
Light Level
Control Out.
Man. Switch
+24V
Common
Wiring
terminals