MOUNTING THE SENSOR
Directly to Ceiling
1. Attach the plastic spring clips to
the edge of the sensor in the slots
provided.
2. Cut a 3.5” to 4” round hole in
the acoustic ceiling tile at the
mounting location. A 3.5” hole is
recommended for a secure fi t.
3. Pull the low voltage wire from the
power pack to the sensor through
the hole.
4. Connect the low voltage wires to
the appropriate terminals on the
sensor.
5. Push the sensor up through the hole until the Spring Clips hold the sensor
securely in place.
6. Snap the front cover onto the sensor.
Using an Octagonal J-Box
1. Pull the low voltage wires
from the power pack into the
J-Box through the conduit
knockout.
2. Connect the low voltage wires
to the appropriate terminals
on the sensor.
3. Loosen the appliance
mounting screws attached to
the J-Box
4. Align the sensor in the J-Box
so that the mounting screws
on the box match the key
holes on the sensor’s rear
housing.
5. Push the sensor up into the J -Box and twist it so that the mounting screws are
seated in the keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor.
Rear
housing
Depluggable terminal
Front
cover
Ceiling
Spring clips (2)
Ceiling Mount
Rear
housing
Depluggable
terminal
4" Octagonal J-Box
(at least 1.5" deep)
Front
cover
Ceiling
Screws
J-Box Mount
Call 800.879.8585 for Technical Support