Wattstopper FS-705 Installation instructions - page 3
Figure 4: BZ‑150 Power Pack connected to FS‑705
using an FS‑C2 adaptor
FS-705 Sensor
Blue
Red
Black
FS-C2 shielded 6” (152mm) cable with 3 flying leads at one end and a shielded RJ45
male connector at the other. Use FS-C5 coupler with FS-C1 or FS-C3 to extend cable.
Line
Neutral
Load
Local OFF Switch
Feed-through
Br
own
Gr
ey
Yellow
Ye
llow
UL 2043 Plenum Rated
Santa Clara, CA
800.879.8585
APPLIANCE
CONTROL
88T9
Auto
ON
Manual
ON
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Model #:
BZ-150 Power Pack
08405r1
+24VDC
Common
Red
White
Neut.
Power Pack
Blue
Blac
k
Red
Dr
y
Contact
Lighting
Load
277VAC
Black
120VAC
+12-24VDC In
Hold OFF
+12-24VDC In
Hold ON
Any 3-Wire
24VDC
Sensor
Hot
Red
Brown
Orange
Gr
ey
Control
Momentary Switch (optional)
Low Voltage Wires
Set BZ-150
to
Auto-ON
FS-705 Sensor
Blue
Red
Black
FS-C2 shielded 6” (152mm) cable with 3 flying leads at one end and a shielded RJ45 male
connector at the other. Add an FS-C5 coupler and FS-C1 or FS-C3 to extend cable.
Line
Neutral
Load
Local OFF Switch
Feed-through
Yellow
08618r1
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Model #:
BZ-50 Power Pack
UL 2043 Plenum Rated
APPLIANCE
CONTROL
88T9
Santa Clara, CA • 800.879.8585
Red
White
Neut.
Power Pack
Switch
Lighting
Load
Black
Hot
Red
RJ45 connection
24VDC
Sensor
Figure 3: BZ‑50 Power Pack connected to FS‑705
using an FS‑C2 adaptor
ADJUSTMENTS
The Time Delay and PIR
Sensitivity adjustments are
located on the back of the
FS‑705 under a removable cover.
The sensors are factory preset
for maximum sensitivity and a
30 second time delay.
TEST OCCUPANCY SENSOR
Important, there is an initial warm‑up period:
It may take up to a minute for the sensor to warm‑up during
the initial power‑up. The sensor has an “instant on” feature.
This occurs during installation or after a lengthy power failure
only. As soon as power is supplied to the power pack, the
lights will come on and stay on for approximately 1 minute. If
no movement is detected within that time the lights will turn
off until detection occurs. If movement is detected during the
initial 1 minute then the lights will stay on for whatever time
has been set on the time delay.
1. Turn the time delay to minimum.
2. Move out of the sensor’s view. Lights should turn off after
30 seconds.
3. Walk down the aisle. When the first sensor detects motion
thegreenLEDinthesensorwillflashandthefirstcooler’s
lights should turn on.
4. Proceed down the aisle, the second cooler’s sensor should
detectyou,thegreenLEDinthesensorwillflashandthe
second cooler’s lights should turn on.
5. This process should continue down the rest of the aisle.
As you walk down the aisle, the cooler lights should
progressively turn on prior to you walking in front of that
cooler, turning on one at a time as you proceed down the
aisle.
6. Repeat this process from the opposite end of the aisle. No
matter which direction you approach the system should
function in this way.
Call 800.879.8585 for Technical Support
www.wattstopper.com
=ON
=OFF
2 3 4
Time Delay
30 second
1 minute
2 minutes
8 minutes
1
Sensitivity
Minimum
Maximum
Switch Settings