Wattstopper PW-100 Installation Instructions Manual

Other manuals for PW-100: Installation Instructions Manual

Summary of PW-100

  • Page 1

    Santa clara, ca 95050 800.879.8585 ins tallation ins tructions specifications voltages: pw-100 & pw-200 . . . . . . . . . . . . . .120/230/277vac, 50/60hz pw-100-347 . . . . . . . . . . . . . . . . . . . . . . . . . . .347vac, 50/60hz load limits for each relay: @120vac . . . . . . . . . . . .0-800w...

  • Page 2

    Unit description and operation the pw passive infrared wall switch sensors use advanced passive infrared (pir) technology. The pw sensor can turn a load on, and hold it on as long as the sensor detects occupancy. After no movement is detected for the selected time delay, the lights switch off. A “wa...

  • Page 3

    Fixed time delay (dip 1 on, 2 & 3 off) high (dip #5 off) walk-through mode (dip #4 on) the pw sensor turns the load off three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay applies...

  • Page 4

    Call 800.879.8585 for technical support coverage patterns coverage testing has been performed according to the nema wd 7 guideline. For best performance, use in spaces not larger than 15’ x 12’. Pir sensor the sensor has a two-tiered, multi- cell viewing fresnel lens with 180 degree field of view. T...

  • Page 5

    1. Make sure that the power has been turned off at the circuit breaker. 2. Connect wires to the pw flying leads as shown in the wiring diagram that is appropriate to the pw model and electrical supply. The ground wire (green) must be festened to ground for the sensor to work properly. 3. Attach the ...

  • Page 6

    Dela y pir 50% w alk aud. Alert rl y 1 man rl y 2 man vis. Alert on/off buttons relay 1 relay 2 dip switches detection led pir lens dip switch settings =on =off =factory setting 8 auto on manual on relay 1 mode 9 auto on manual on relay 2 mode 5 high low, 50% pir sensitivity 7 disabled enabled audib...

  • Page 7

    Troubleshooting lights do not turn on with motion (led does flash) 1. Press and release each button to make sure that the correct lights come on for each relay. If the lights do not turn on, check wire connections, especially the load connection. If the lights turn on, verify that the correct on mod...

  • Page 8

    Ordering information warranty information watt stopper/legrand warranties its products to be free of defects in materials and workmanship for a period of five years. There are no obligations or liabilities on the part of watt stopper/legrand for consequential damages arising out of or in connection ...