Woodsman Blaze Installation And Operating Instructions Manual - page 4
4
Installation Instructions
This appliance should only be installed by a trained and qualified installer.
Warning: the appliance and flue system shall be installed in accordance with AS/NZS 2918
and the appropriate requirements of relevant building code/codes.
Warning: appliances installed in accordance with this standard shall comply with the
requirements of AS/NZS 4013 where required by the regulatory authority, i.e. the appliance
shall be identifiable by a compliance plate with the marking “Tested to AS/NZS 4013”.
Any modification of the appliance that has not been approved in writing by the testing
authority is considered to be in breach of the approval granted for compliance with
AS/NZS 4013.
Caution: mixing of appliance or flue system components from different sources or modifying
the dimensional specification of components may result in hazardous conditions. Where such
action is considered, the manufacturer should be consulted in the first instance.
Caution: cracked and broken components e.g. glass panels or ceramic tiles, may render the
installation unsafe.
Warning: do not connect to an unvented hot water system.
Install in accordance with AS 3500.4.1 or NZS 4603 and the appropriate requirements of the
relevant building code/codes.
•
Maintain a clearance of at least 1 metre between front of the appliance and building
structure or any other substantial immovable object.
•
If the appliance is installed on a heat sensitive floor, the floor should be protected with
an insulation floor protector, which shall extend entirely beneath the heater. For the
correct floor protector extension, refer to dimension C in FIG 1 & 2.
•
Your appliance shall be seismically restrained, including the floor protector, using the
two metal seismic restraint brackets supplied.
Minimum Material Specifications
For Floor Protectors
MODEL
SPECIFICATION
BLAZE
8mm of ceramic tiles
ECR MkII
8mm of ceramic tiles
MANHATTEN & BOSTON
8mm of ceramic tiles
MILFORD
12mm HardiFlex
RMF (2006+)
8mm of ceramic tiles
RMF - RV
12mm Hardiflex
STRONGMAN
24mm Eterpan
TARRAS & TARRAS-WB
24mm Eterpan