Thermal disinfection
CS 200 – 6720830475 (2015/06)
Table 9
Settings in the Maintenance menu
Contact address
The contact address is automatically displayed to the end user
in case of a fault.
Entering company name and telephone number
The current cursor position will flash (marked by
| ).
Fig. 10
Entering a contact address
▶ Turn the control knob to move the cursor.
▶ Press the control knob to activate the input field.
▶ Turn the control knob to enter characters.
▶ Press the Back key when you have finished making entries.
▶ Press the Back key again to return to the next previous
menu.
7.2.6 Reset
You can delete different settings or lists or reset them to the
default setting in this menu.
Table 10 Resetting the settings
7.2.7 Calibration
Table 11 Settings in the Calibration menu
8
Thermal disinfection
CAUTION:
Risk of scalding.
During thermal disinfection, discharging unmixed hot water can
cause serious scalding.
▶ Only use the maximum adjustable hot water temperature
for thermal disinfection.
▶ Inform occupants of the premises of the risk of scalding.
▶ Perform thermal disinfection outside of the normal
operating times.
▶ Do not discharge DHW unmixed.
▶ Ensure a thermal mixing valve is fitted as stated in the UK
G3 building regulations.
Perform thermal disinfection/daily heat-up to kill off pathogens
(e.g. legionella) on a regular basis.
To guarantee thermal disinfection/daily heat-up:
▶ Set the heat source (e.g. boiler) in such a way that daily
heat-up can be carried out, for example temperature
settings or time programme for DHW heating.
▶ Install the pipework for system components, which are
necessary for thermal disinfection or daily heat-up, as
energy-efficiently as possible (short pipe lengths, good
thermal insulation, etc.).
In the case of larger DHW systems, there may be statutory
requirements (
regulations on drinking water) for thermal
disinfection. Observe the instructions in the technical
documentation of the heat source.
Menu item
Description
Contact address
"Contact address"
Menu item
Description
Fault history
The fault history is deleted. If currently a
fault is present, the fault history is
recorded again.
Default setting
All settings are reset to the corresponding
default setting.
The system must be recommissioned after
this reset!
0010003273.001
Menu item
Description
Time correction
This correction ( – 20 ...
0 ... + 20 s) is
automatically carried out once a week (0 is
default).
Example: Deviation of the time by
approximately –6 minutes per year
•
–6 minutes per year is equal to
–360 seconds per year
•
1 year = 52 weeks
•
–360 seconds: 52 weeks
•
–6.92 seconds per week
•
Correction factor = +7 s/week.