Controller Functions
8.1
MS2 manual 2-speed switch
Refer to section 7.1 for the relevant wiring diagram. This switch option is for manual control only and therefore
none of the automatic control accessories listed below are compatible with this switch.
Minimum size of 3-core cable to be used:
Power supply – 1.5mm…
Switch – 0.5mm…
Note – use a spanner to tighten all cable glands
Settings:
Speed 1: Normal operation
Speed 2: Boost setting for increased air exchange
8.2
Q3SP automatic 3-speed switch
Refer to sections 7.2, 7.3, 7.4 and 7.5 for the relevant wiring diagrams and additional controllers that are com-
patible with the 3-speed switch. With jumper 8 selected on the PCB, the 3-speed switch is active.
Minimum size of 3-core cable to be used:
Power supply – 1.5mm…
Switch – 0.5mm…
Note – use a spanner to tighten all cable glands
Key features:
-
Plus and minus keys to manually change speed
-
3 LEDs for speed indication / white housing
-
Up to 10 off 3-speed switches can be connected in parallel to each MVHR.
Indicators:
-
Moisture Protection
LED 1 flashes briefly every second
Important: an interval time is programmed into the Moisture Protection setting.
Interval time: 17 mins. ON
13 mins. OFF, etc.
-
Speed 1
LED 1 on
-
Speed 2
LED 2 on
-
Speed 3
LED 3 on
-
MVHR OFF*
LEDs 1+2+3 off
-
Filter service
LED 1 flashes quickly continuously (until reset as described below)
-
Timer reset
LEDs 1+2+3 flash 5 times in quick succession (to acknowledge reset is complete)
-
Fault alarm
LEDs 1+2+3 flash every second
-
Fault alarm reset
Mains voltage briefly interrupted
Settings:
-
MVHR On*
Press plus key
-
MVHR Off*
Press minus key until speed 0 is reached, i.e. 3>2>1>Moisture Protection>0,
MVHR OFF
-
Reset timer
Press plus and minus keys together and hold for 2 seconds
-
Speed 3
Speed 3 time-limited (only when no other controllers are used alongside the 3-speed
switch): after 1 hour, the MVHR automatically switches back to fan speed 2
On/off function (only possible when no other controllers are used alongside the 3-speed switch) can be
disabled with jumper 9 on the PCB. This means the speed switches from Ventilation to Moisture Protec-
tion – the lowest fan speed.
Filter service indicator:
The period for the filter service timer (3 months) is set and stored and cannot be changed.
Once the period of 3 months has expired, the switch will indicate that a filter serice is necessary whereby the
LED for fan speed 1 flashes every second.
Once the filter has been successfully serviced i.e. cleaned or changed, the filter service timer on the switch can
be reset by pressing both OPERATING KEYS (and holding for 2 seconds) and the filter service indicator on the
switch will go out. Resetting is acknowledged by LED 1 flashing quickly 5 times.
In the event of a full MVHR service outside the above 3 month period, the timer can also be reset, without the
filter service timer having completed its runtime, by pressing both operating keys together and holding for 10
seconds. Resetting is acknowledged by LED 1 flashing quickly 5 times.