A&D CC-Link Interface AD-4402-OP-20 Instruction Manual - page 10
Page 8
AD-4402-20
4.1.2.
4.1.2.
4.1.2.
4.1.2.
Address Map of the Remote Input / Output
Address Map of the Remote Input / Output
Address Map of the Remote Input / Output
Address Map of the Remote Input / Output
Flags (bits) and CC-link handshake in the remote input,
AD-4402 to Master Unit
Assumed that station No. is "1".
Station No.
Flags (bits)
and CC-link
Handshake of
Remote Input
Buffer
Description
RX0000
Reply flag to store setpoints
RX0001
Not used
RX0002
Command replay flag
RX0003
Read / Write replay flag
RX0004
RX0005
Not used
RX0006
CPU normal operation
RX0007
Not used
RX0008
Decimal point 2
0
RX0009
Decimal point 2
1
RX000A
Decimal point 2
2
Three bits binary
RX000B to
RX000F
0E0
Not used
RX0010
Zero band
RX0011
Full flow
RX0012
Medium flow
RX0013
Dribble flow
RX0014
Over
RX0015
OK
RX0016
Under
RX0017
Stable
RX0018
Batch finish
RX0019
Capacity exceeded
RX001A
Hold
RX001B
Full
RX001C
Not used
RX001D
Discharge
RX001E
Weighing sequence error
1
RX001F
0E1
Abnormal weighing without weighing
sequence error.(Zero error, Alarm 1, Alarm 2)
RX0020
Stable
RX0021
Zero band
RX0022
Full
RX0023
Full flow
RX0024
Medium flow
RX0025
Dribble flow
RX0026
Over
RX0027
OK
RX0028
Under weight
RX0029
2
RX002A
0E2
Internal reservation