ABB REB670 Product Manual

Manual is about: Relion 670 Series Busbar protection

Summary of REB670

  • Page 1

    Relion ® 670 series busbar protection reb670 pre-configured product guide.

  • Page 2

    Contents 1. Application.....................................................................3 2. Available functions..........................................................9 3. Differential protection....................................................12 4. Zone selection.............................

  • Page 3

    1. Application reb670 is designed for the selective, reliable and fast differential protection of busbars, t-connections and meshed corners. Reb670 can be used for protection of single and double busbar with or without transfer bus, double circuit breaker or one-and-half circuit breaker stations. Th...

  • Page 4

    Flexible, software based dynamic zone selection enables easy and fast adaptation to the most common substation arrangements such as single busbar with or without transfer bus, double busbar with or without transfer bus, one-and-a- half breaker stations, double busbar-double breaker stations, ring bu...

  • Page 5

    • fully configured for the total available number of bays in each reb670 variant • facility to take any bay out of service via the local hmi or externally via binary input • facility to block any of the two zones via the local hmi or externally via binary input • facility to block all bay trips via ...

  • Page 6

    Bi1 qa1 qb1 qb7 bi1 qb7 qb1 qa1 bi1 qb7 qb1 qa1 bi1 qb7 qb1 qa1 bi1 qb7 qb1 qa1 za zb bi1 qb7 qb1 qa1 xx06000013.Vsd iec06000013 v1 en figure 4. Example of single bus station with transfer bus bi1 qa1 qb1 qb2 bi1 qa1 qb1 qb2 bi1 qa1 qb1 qb2 bi1 qa1 qb1 qb2 bi1 qa1 qb1 qb2 bi1 qa1 bi1 qb1 qb2 qa1 za ...

  • Page 7

    Bi3 bi1 qa1 bi2 qa2 qa3 bi3 bi1 qa1 bi2 qa2 qa3 bi3 bi1 qa1 bi2 qa2 qa3 bi3 bi1 qa1 bi2 qa2 qa3 bi3 bi1 qa1 bi2 qa2 qa3 za zb xx06000017.Vsd iec06000017 v1 en figure 8. Example of one-and-a-half breaker station qa1 bi1 bi2 qa2 qa1 bi1 bi2 qa2 qa1 bi1 bi2 qa2 qa1 bi1 bi2 qa2 qa1 bi1 bi2 qa2 za zb xx0...

  • Page 8

    Note that customized reb670 is delivered without any configuration. Thus the complete ied engineering shall be done by the customer or its system integrator. In order to secure proper operation of the busbar protection it is strictly recommended to always start engineering work from the pcm600 proje...

  • Page 9

    2. Available functions main protection functions 2 = number of basic instances 3-a03 = optional function included in packages a03 (refer to ordering details) iec 61850 ansi function description busbar reb670 (a20) reb670 (a31) reb670 (b20) reb670 (b21) reb670 (b31) differential protection butptrc, b...

  • Page 10

    Control and monitoring functions iec 61850 ansi function description busbar reb670 (a20) reb670 (a31) reb670 (b20) reb670 (b21) reb670 (b31) control smbrrec 79 autorecloser 2-h05 2-h05 2-h05 2-h05 2-h05 qcbay apparatus control 1 1 1 1 1 locrem handling of lrswitch positions 1 1 1 1 1 locremctr l lhm...

  • Page 11

    Designed to communicate iec 61850 ansi function description busbar reb670 (a20) reb670 (a31) reb670 (b20) reb670 (b21) reb670 (b31) station communication spa communication protocol 1 1 1 1 1 lon communication protocol 1 1 1 1 1 iec60870-5-103 communication protocol 20/1 20/1 20/1 20/1 20/1 operation...

  • Page 12

    Basic ied functions iec 61850 function description basic functions included in all products interrorsig self supervision with internal event list 1 time time and synchronization error 1 timesynch time synchronization 1 activegroup parameter setting groups 1 test test mode functionality 1 changelock ...

  • Page 13

    Saturated for at least two milliseconds during each power system cycle. It is also possible to add external tripping criteria by binary signal. The trip command from the differential protection including sensitive differential protection and circuit breaker failure backup-trip commands can be set ei...

  • Page 14

    These disconnectors then actually determine which ct input (that is, bay) is connected to which differential protection zone. For some more advanced features like end-fault or blind-spot protection the actual status of the circuit breaker in some or even all bays can be vital information for busbar ...

  • Page 15

    • permanently connect this bay current to zone a (that is, za) • permanently connect this bay current to zone b (that is, zb) • permanently connect this bay current to zone a and inverted bay current to zb (that is, za and zb) • connect this bay current to za or zb depending on the logical status of...

  • Page 16

    5. Current protection four step phase overcurrent protection oc4ptoc the four step phase overcurrent protection function oc4ptoc has an inverse or definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always definite time delayed. All iec and ansi inverse time characteristics...

  • Page 17

    Those parts of the logic configuration that do not need extensive command receiving functionality (for example, scswi). In this way, simple commands can be sent directly to the ied outputs, without confirmation. Confirmation (status) of the result of the commands is supposed to be achieved by other ...

  • Page 18

    A disturbance is defined as an activation of an input to the axradr or bxrbdr function blocks, which are set to trigger the disturbance recorder. All signals from start of pre-fault time to the end of post-fault time will be included in the recording. Every disturbance report recording is saved in t...

  • Page 19

    Measured value expander block range_xp the current and voltage measurements functions (cvmmxn, cmmxu, vmmxu and vnmmxu), current and voltage sequence measurement functions (cmsqi and vmsqi) and iec 61850 generic communication i/o functions (mvggio) are provided with measurement supervision functiona...

  • Page 20

    Iec06000191 v1 en figure 12. Bay to zone connection example 1 user settable bay name 2 internally used bay fb 3 connections to internal zones iec06000192 v1 en figure 13. Example of status of primary switchgear objects 1 user settable switchgear names 2 switchgear object status 11. Station communica...

  • Page 21

    To goose is part of the standard. Disturbance files uploading is provided. Serial communication, lon existing stations with abb station bus lon can be extended with use of the optical lon interface. This allows full sa functionality including peer-to-peer messaging and cooperation between existing a...

  • Page 22

    The two high speed signal output channels are used for applications where short operating time is essential. Eight optically isolated binary inputs cater for required binary input information. Optical ethernet module oem the optical fast-ethernet module is used to connect an ied to the communication...

  • Page 23

    Xx05000004.Vsd iec05000004 v1 en figure 15. Side-by-side mounting case size a b c d e f 6u, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7 6u, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0 6u, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3 (mm) mounting alternatives • 19” rack mounting kit • flush mou...

  • Page 24

    14. Connection diagrams table 2. Designations for 1/2 x 19” casing with 1 trm slot 1mrk002801-ac-2-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x51 and x52 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs48...

  • Page 25

    Table 4. Designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x131 and x132 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, ...

  • Page 26

    1mrk002801-ac-10-670-1.2-pg v1 en figure 16. Transformer input module (trm) ■ indicates high polarity ct/vt-input designation according to figure 16 current/voltage configuration (50/60 hz) ai01 ai02 ai03 ai04 ai05 ai06 ai07 ai08 ai09 ai10 ai11 ai12 12i, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 12i, 5...

  • Page 27

    1mrk002801-ac-11-670-1.2-pg v1 en figure 17. Binary input module (bim). Input contacts named xa corresponds to rear position x31, x41, and so on, and input contacts named xb to rear position x32, x42, and so on. 1mrk002801-ac-15-670-1.2-pg v1 en figure 18. Ma input module (mim) 1mrk002801-ac-8-670-1...

  • Page 28

    1mrk002801-ac-7-670-1.2-pg v1 en figure 20. Power supply module (psm) 1mrk002801-ac-12-670-1.2-pg v1 en figure 21. Binary output module (bom). Output contacts named xa corresponds to rear position x31, x41, and so on, and output contacts named xb to rear position x32, x42, and so on. Busbar protecti...

  • Page 29

    1mrk002801-ac-13-670-1.2-pg v1 en figure 22. Static output module (som) 1mrk002801-ac-14-670-1.2-pg v1 en figure 23. Binary in/out module (iom). Input contacts named xa corresponds to rear position x31, x41, and so on, and output contacts named xb to rear position x32, x42, and so on. Busbar protect...

  • Page 30

    15. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 31

    Binary inputs and outputs table 8. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50ma 48/60 v, 50ma 110/125 v, 50ma 220/250 v, 50ma 220/250 v, 110ma max...

  • Page 32

    Table 10. Iom - binary input/output module quantity rated value nominal range binary inputs 8 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma max. 0.05 w/input...

  • Page 33

    Table 12. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 250 v r...

  • Page 34

    Table 14. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000v rms current carrying capacity: continuous 8a 1.0s 1...

  • Page 35

    Table 17. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01% /% auxiliary voltage dependence, operate value ± 20% of el 0.01% ...

  • Page 36

    Type tests according to standards table 19. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-22-1 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12...

  • Page 37

    Table 21. Environmental tests test type test value reference standard cold test test ad for 16 h at -25°c iec 60068-2-1 storage test test ad for 16 h at -40°c iec 60068-2-1 dry heat test test bd for 16 h at +70°c iec 60068-2-2 damp heat test, steady state test ca for 4 days at +40 °c and humidity 93...

  • Page 38

    Differential protection table 24. Busbar differential protection function range or value accuracy operating characteristic s=0.53 fixed ± 2.0% of i r for i i r ± 2.0% of i for i > i r reset ratio > 95% - differential current operating level (1-100000) a ± 2.0% of i r for i i r ± 2.0% of i for i > i ...

  • Page 39

    Current protection table 25. Four step phase overcurrent protection oc4ptoc function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - min. Operating current (1-10000)% of lbase ± 1.0% of i r at i ≤ i ...

  • Page 40

    Table 27. Breaker failure protection ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset rat...

  • Page 41

    Control table 29. Autorecloser smbrrec function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 1ph shot 1 - t1 2ph shot 1 - t1 3phhs shot 1 - t1 3phdld (0.000-60.000) s ± 0.5% ± 10 ms shot 2 - t2 shot 3 - t3 shot 4 - t4 shot 5 - t5 (0.00-6000.00) s...

  • Page 42

    Logic table 30. Configurable logic blocks logic block quantity with update rate range or value accuracy fast medium normal logicand 90 90 100 - - logicor 90 90 100 - - logicxor 15 15 10 - - logicinverter 45 45 50 - - logicsrmemory 15 15 10 - - logicrsmemory 15 15 10 - - logicgate 15 15 10 - - logict...

  • Page 43

    Monitoring table 31. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) × f r ± 2.0 mhz connected current (0.2-4.0) × i r ± 0.5% of i r at i £ i r ± 0.5% of i at i > i r table 32. Phase current measurement cmmxu function range or value accuracy current (0.1-4.0) × i r ± 0.2% ...

  • Page 44

    Table 36. Voltage sequence measurement vmsqi function range or value accuracy voltage positive sequence, u1 (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v voltage zero sequence, 3u0 (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v voltage negative sequence, u2 (10 to 300)...

  • Page 45

    Table 40. Indications function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number of recorded disturbances 100 table 41. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance ...

  • Page 46

    Station communication table 44. Iec 61850-8-1 communication protocol function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 608–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/i...

  • Page 47

    Table 49. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fibre: type st plastic fibre: type hfbr snap-in fibre, optical budget glass fibre: 11 db (3000ft/1000 m typically *) plastic fibre: 7 db (80ft/25 m typically *) fibre diameter glass fibre: 62.5/125 m m plas...

  • Page 48

    Remote communication table 52. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fibre graded-index multimode 62.5/125 µm or 50/125 µm singlemode 9/125 µm singlemode 9/125 µm wave length 850 nm 1310 nm 1550 nm optical...

  • Page 49

    Hardware ied table 53. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 54. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom ip2...

  • Page 50

    Basic ied functions table 58. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 59. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms tim...

  • Page 51

    Table 62. Irig-b quantity rated value number of channels irig-b 1 number of channels pps 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x accuracy...

  • Page 52

    Inverse characteristic table 63. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = + × - æ ö ç ÷ ç ÷ è ø p a t b k i equation1249-small v1 en reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en i = i measured /i set k = (0.05-999) ...

  • Page 53

    Table 64. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 - time delay to reset, iec inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ...

  • Page 54

    16. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configur...

  • Page 55

    First local hmi user dialogue language #4 notes and rules hmi language, english iec b1 hmi language, english us b2 additional local hmi user dialogue language hmi language, german a1 hmi language, russian a2 hmi language, french a3 hmi language, spanish a4 hmi language, polish a6 hmi language, hunga...

  • Page 56

    Binary input/output module, ma and time synchronization boards. Note: 1bim and 1 bom included. #10 notes and rules make bim with 50 ma inrush current the primary choice. Bim with 50 ma inrush current fulfill additional standards. As a consequence the emc withstand capability is further increased. Bi...

  • Page 57

    Remote end communication, dnp serial comm. And time synchronization modules #11 notes and rules slot position (rear view) x312 x313 x302 x303 x322 x323 available slots in 1/2 case with 1 trm █ █ █ █ note: max 1 ldcm available slots in 3/4 case with 1 trm █ █ █ █ note: max 2 ldcm available slots in 1...

  • Page 58

    Interface converter (for remote end data communication) external interface converter from c37.94 to g703 quantity: 1 2 1mrk 002 245-aa external interface converter from c37.94 to g703.E1 quantity: 1 2 1mrk 002 245-ba test switch the test system combitest intended for use with the ied 670 products is...

  • Page 59

    Led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect cd containing user documentation (operator’s manual, technical reference manual, installation and commissioning manual, application manual and g...

  • Page 60

    Related documents documents related to reb670 identity number operator’s manual 1mrk 505 209-uen installation and commissioning manual 1mrk 505 210-uen technical reference manual 1mrk 505 208-uen application manual 1mrk 505 211-uen product guide pre-configured 1mrk 505 212-ben connection and install...

  • Page 61

    61.

  • Page 62

    Contact us abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 fax +46 (0) 21 14 69 18 www.Abb.Com/substationautomation 1mrk505212-ben e © copyright 2012 abb. All rights reserved..