ABB rec670 Installation Manual

Manual is about: Relion 670 Series, Bay Control

Summary of rec670

  • Page 1

    Relion® 670 series — 670 series version 2.2 iec installation manual.

  • Page 3

    Document id: 1mrk 514 026-uen issued: october 2017 revision: b product version: 2.2.1 © copyright 2017 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and...

  • Page 5

    Disclaimer this document has been carefully checked by abb but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall abb be responsible or liable for ...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents section 1 introduction.......................................................................5 this manual........................................................................................ 5 intended audience.......................................................................

  • Page 8

    Wall mounting..............................................................................26 overview................................................................................ 26 mounting procedure for wall mounting................................... 27 how to reach the rear side of the ied.....

  • Page 9

    Rs485 serial communication module..........................................73 installing the serial communication cable for rs485 spa/iec....77 data on rs485 serial communication module cable...................79 installing the gps antenna................................................................

  • Page 10

    4.

  • Page 11

    Section 1 introduction 1.1 this manual guid-ab423a30-13c2-46af-b7fe-a73bb425eb5f v18 the installation manual contains instructions on how to install the ied. The manual provides procedures for mechanical and electrical installation. The chapters are organized in the chronological order in which the ...

  • Page 12

    1.3 product documentation 1.3.1 product documentation set guid-3aa69ea6-f1d8-47c6-a8e6-562f29c67172 v15 iec07000220-4-en.Vsd p la n n in g & p u rc h a se e n gi n e e rin g in st a lli n g c o m m is si o n in g o p e ra tio n m ai n te n a n ce d e co m m is si o n in g d e in st a lli n g & d is ...

  • Page 13

    Describes the process of testing an ied in a substation which is not in service. The chapters are organized in the chronological order in which the ied should be commissioned. The relevant procedures may be followed also during the service and maintenance activities. The operation manual contains in...

  • Page 14

    1.3.3 related documents guid-94e8a5ca-be1b-45af-81e7-5a41d34ee112 v5 documents related to reb670 document numbers application manual 1mrk 505 370-uen commissioning manual 1mrk 505 372-uen product guide 1mrk 505 373-ben technical manual 1mrk 505 371-uen type test certificate 1mrk 505 373-ten document...

  • Page 15

    Documents related to ret670 document numbers application manual 1mrk 504 163-uen commissioning manual 1mrk 504 165-uen product guide 1mrk 504 166-ben technical manual 1mrk 504 164-uen type test certificate 1mrk 504 166-ten documents related to res670 document numbers application manual 1mrk 511 407-...

  • Page 16

    1.4 document symbols and conventions 1.4.1 symbols guid-2945b229-dab0-4f15-8a0e-b9cf0c2c7b15 v12 the electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. The cauti...

  • Page 17

    For example, select main menu/settings. • lhmi messages are shown in courier font. For example, to save the changes in non-volatile memory, select yes and press . • parameter names are shown in italics. For example, the function can be enabled and disabled with the operation setting. • each function...

  • Page 18

    12.

  • Page 19

    Section 2 safety information 2.1 symbols on the product guid-e48f2ec3-6ab8-4ecf-a77e-f16ce45ca5fd v2 all warnings must be observed. Read the entire manual before doing installation or any maintenance work on the product. All warnings must be observed. Class 1 laser product. Take adequate measures to...

  • Page 20

    M2364-2 v1 always use suitable isolated test pins when measuring signals in open circuitry. Potentially lethal voltages and currents are present. M2370-2 v1 never connect or disconnect a wire and/or a connector to or from a ied during normal operation. Hazardous voltages and currents are present tha...

  • Page 21

    2.3 caution signs ip1503-1 v1 guid-5d1412b8-8f9d-4d39-b6d1-60fb35797fd0 v1 whenever changes are made in the ied, measures should be taken to avoid inadvertent tripping. Guid-f2a7bd77-80fb-48f0-aae5-be73de520cc2 v1 the ied contains components which are sensitive to electrostatic discharge. Esd precau...

  • Page 22

    2.4 note signs ip1497-1 v1 m19-2 v3 observe the maximum allowed continuous current for the different current transformer inputs of the ied. See technical data. Section 2 1mrk 514 026-uen b safety information 16 670 series 2.2 iec installation manual.

  • Page 23

    Section 3 environmental aspects 3.1 sustainable development guid-573c2931-cbb2-4e7d-a067-d8246cc7a52f v7 sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of t...

  • Page 24

    18.

  • Page 25

    Section 4 unpacking, inspecting and storing 4.1 removing transport packaging amu0600514 v5 ieds require careful handling. 1. Examine the delivered products to ensure that they have not been damaged during the transport. 2. Remove the transport packing carefully without force. The cardboard packaging...

  • Page 26

    4.2.4 returning an ied damaged in transit guid-966a05ed-cd30-4f66-957e-00ff38943a73 v4 if damage has occurred during transport, appropriate actions must be taken against the latest carrier. Please inform the nearest abb office or representative. Notify abb immediately if there are any discrepancies ...

  • Page 27

    Section 5 mounting 5.1 required tools guid-b9478208-286b-4cff-9c47-074d641a6f71 v2 generally, all the screws included in delivered mounting kits are of torx type and a torque screwdriver of the same type is needed (tx10, tx15, tx20, tx25 and tx30). Use only the screws included in the mounting kit wh...

  • Page 28

    • flush mounting kit • 19” panel (rack) mounting kit • wall mounting kit • side-by-side mounting kit the same mounting kit is used for side-by-side rack mounting and side-by-side flush mounting. The mounting kits are ordered with the ied from the ordering sheet in the product guide. They are also av...

  • Page 29

    • 1/2 x 19” • 3/4 x 19” • 1/1 x 19” • 1/4 x 19” (rhgs6 6u) only a single case can be mounted in each cut-out on the cubicle panel, for class ip54 protection. The screws from the ied shall be used to fasten the fasteners to the ied. Flush mounting cannot be used for side-by-side mounted ieds when ip5...

  • Page 30

    Posno description quantity type 1 sealing strip, used to obtain ip54 class. The sealing strip is factory mounted between the case and front plate. - - 2 fastener 2 - 3 groove - - 4 screw 4 m3x8 mm 5 joining point of sealing strip - - 6 panel - - 5.3.2 19” panel rack mounting ip10313-1 v1 5.3.2.1 ove...

  • Page 31

    5.3.2.2 mounting procedure for 19” panel rack mounting m11948-2 v6 1a iec08000160-3-en.Vsdx 1a 2 3 iec08000160 v3 en-us figure 4: 19” panel rack mounting details the required torque for the screws is 3.5 nm. 1mrk 514 026-uen b section 5 mounting 670 series 2.2 iec 25 installation manual.

  • Page 32

    Posno description quantity type 1a, 1b mounting angles, can be mounted either to the left or the right side of the case 2 - 2 screw 8 m4x6 3 washer 8 m4x6 5.3.3 wall mounting ip10316-1 v1 5.3.3.1 overview m11973-3 v6 all case sizes, 1/2 x 19”, 3/4 x 19”,1/1 x 19”, can be wall mounted. It is also pos...

  • Page 33

    5.3.3.2 mounting procedure for wall mounting m11949-2 v2 iec130 00266-1-en.Vsd 1 2 3 4 5 6 iec13000266 v1 en-us figure 5: wall mounting details. Posno description quantity type 1 bushing 4 - 2 screw 8 m4x10 3 screw 4 m6x12 or corresponding 4 mounting bar 2 - 5 screw 6 m5x8 6 side plate 2 - 5.3.3.3 h...

  • Page 34

    80 mm 1 3 2 iec06000135-2-en.Vsd iec06000135 v3 en-us figure 6: how to reach the connectors on the rear side of the ied. Posno description type 1 screw m4x10 2 screw m5x8 3 rear protection cover (ordered separately) 5.3.4 side-by-side 19” rack mounting ip10323-1 v1 5.3.4.1 overview m11974-3 v3 ied c...

  • Page 35

    5.3.4.2 mounting procedure for side-by-side rack mounting m11955-2 v3 iec040004563enoriginal.Vsdx 1 2 3 4 3 iec04000456 v3 en-us figure 7: side-by-side rack mounting details. The required torque for the screws is 3.5 nm. Posno description quantity type 1 mounting plate 2 - 2, 3 screw 16 m4x6 4 mount...

  • Page 36

    8 8 8 7 5 6 3 4 2 7 5 6 7 5 6 3 4 2 3 4 2 1 1 2 1 1 1 8 7 5 6 3 4 2 2 1 iec06000180-2-en.Vsd iec06000180 v2 en-us figure 8: ied (1/2 x 19”) mounted with a rhgs6 case containing a test switch module equipped with only a test switch and a rx2 terminal base 5.3.5 side-by-side flush mounting ip10329-1 v...

  • Page 37

    5.3.5.2 mounting procedure for side-by-side flush mounting m12730-6 v4 1 2 3 4 iec06000181-2-en.Vsd iec06000181 v2 en-us figure 9: side-by-side flush mounting details (rhgs6 side-by-side with 1/2 x 19” ied). The required torque for the screws is 3.5 nm. Posno description quantity type 1 mounting pla...

  • Page 38

    5.3.7 mounting the coupling capacitor unit rex061 and shunt resistor unit rex062 (reg670 only) 5.3.7.1 coupling capacitor unit rex061 guid-59726b2b-0888-4cc1-8dea-209f77ca5173 v5 x1 x2 iec11000019-2-en.Vsd iec11000019 v1 en-us figure 10: coupling capacitor unit rex061 217 [8,54] 25 5 [1 0] 23 5 [9 ,...

  • Page 39

    Rex061 shall be mounted close to the generator in order to limit the exposure of the field circuit. Alternatively it can be located in the excitation cubicle. The surface of rex061 unit may be temporarily very hot due to heat dissipation, up to about 50° c above the ambient temperature. It must be i...

  • Page 40

    217 [8,54] 25 5 [1 0 ] 2 35 [9 ,2 5] 84 [3,3] 84 [3,3] Ø 5,5 [0,22] 22 3 [8 ,7 8] 2 [0,079] 155 [6,1] 19 9 [7 ,8 3] 38 [1 ,5 ] iec11000039-2-en.Vsd iec11000039 v2 en-us figure 13: rex062 measures and drilling plan rex062 shall be mounted close to the ied. It is recommended that rex060 and rex062 are...

  • Page 41

    Section 6 connecting 6.1 making the electrical connection 6.1.1 ied connectors semod127536-1 v1 6.1.1.1 overview semod129364-5 v1 the quantity and designation of connectors depend upon the type and size of the ied. The rear cover plates are prepared with space for the maximum of hw options for each ...

  • Page 42

    Table 3: application specific modules module description binary input module (bim) module with 16 optically isolated binary inputs binary output module (bom) module with 24 single outputs or 12 double-pole command outputs including supervision function binary i/o module (iom) module with 8 optically...

  • Page 43

    6.1.1.2 front side connectors semod129384-5 v3 iec16000051 v1 en-us figure 15: rj-45 communication port 1 ied service port with rj-45 connector 2 green indicator led (lit when the cable is successfully connected) 1mrk 514 026-uen b section 6 connecting 670 series 2.2 iec 37 installation manual.

  • Page 44

    6.1.1.3 rear side connectors semod129387-1 v1 m16105-3 v8 table 4: designations for 1/2 x 19” casing with 1 trm slot 1mrk002801-ac-2-670-1.2-pg v.3 en 1mrk002801-ac-2-670-1.2-pg v4 en-us rear position module x11 psm x31 and x32 etc. To x51 and x52 bim, bom, som, iom or mim x301, x302, x303, x304 sfp...

  • Page 45

    Semod111882-4 v7 table 5: designations for 3/4 x 19” casing with 1 trm slot 1mrk002801-ac-3-670-1.2-pg v4 en-us rear position module x11 psm x31 and x32 etc. To x101 and x102 bim, bom, som, iom or mim x301, x302, x303, x304 sfp x305 ldcm x306 ldcm or oem x3061, x3062 sfp if oem is selected x311: a, ...

  • Page 46

    Semod111884-4 v6 table 6: designations for 3/4 x 19” casing with 2 trm slot 1mrk002801-ac-4-670-1.2-pg v.3 en 1mrk002801-ac-4-670-1.2-pg v4 en-us rear position module x11 psm x31 and x32 etc. To x71 and x72 bim, bom, som, iom or mim x301. X302, x303, x304 sfp x305 ldcm x306 ldcm or oem x3061, x3062 ...

  • Page 47

    M16106-3 v8 table 7: designations for 1/1 x 19” casing with 1 trm slot 1mrk002801-ac-5-670-1.2-pg v.3 en 1mrk002801-ac-5-670-1.2-pg v4 en-us rear position module x11 psm x31 and x32 etc. To x161 and x162 bim, bom, som, iom or mim x301, x302, x303, x304 sfp x305 ldcm x306 ldcm or oem x3061, x3062 sfp...

  • Page 48

    M16108-3 v9 table 8: designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v.3 en 1mrk002801-ac-6-670-1.2-pg v4 en-us rear position module x11 psm x31 and x32 etc. To x131 and x132 bim, bom, som, iom or mim x301, x302, x303, x304 sfp x305 ldcm x306 ldcm or oem x3061, x3062 sf...

  • Page 49

    Semod53217-4 v13 iec08000479 v3 en-us figure 16: transformer input module (trm) ■ indicates high polarity ct/vt-input designation according to figure 16 current/voltage configuration (50/60/17.3 hz) ai01 ai02 ai03 ai04 ai05 ai06 ai07 ai08 ai09 ai10 ai11 ai12 12i, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a ...

  • Page 50

    3im, 1a+4ip, 1a+5u 1am *) 1am *) 1am *) 1a 1a 1a 1a 110-220v 110-220v 110-220v 110-220v 110-220v 3im, 5a+4ip, 5a+5u 5am *) 5am *) 5am *) 5a 5a 5a 5a 110-220v 110-220v 110-220v 110-220v 110-220v 6i+6u, 1a 1a 1a 1a 1a 1a 1a 110-220v 110-220v 110-220v 110-220v 110-220v 110-220v 6i+6u, 5a 5a 5a 5a 5a 5a...

  • Page 51

    1mrk002801-ac-11-670-1.2-pg v2 en-us figure 17: binary input module (bim) 1mrk 514 026-uen b section 6 connecting 670 series 2.2 iec 45 installation manual.

  • Page 52

    Xa 7 8 9 13 14 15 16 17 18 10 11 12 ma input module (mim) ch1 ch2 ch3 ch4 ch5 ch6 configuration location=pn 1mrk002801-ac-15-670-1.2-pg v2 en-us figure 18: ma input module (mim) 1mrk002801-ac-8-670-1.2-pg v2 en-us figure 19: ied with basic functionality and communication interfaces section 6 1mrk 51...

  • Page 53

    X11 1 3 x 11 2 x 11 4 5 power supply module (psm) internal fail p1 + - ready fail + protective earth must be connected el 1mrk002801-ac-7-670-1.2-pg v3 en-us figure 20: power supply module (psm) 1mrk002801-ac-12-670-1.2-pg v1 en-us figure 21: binary output module (bom) 1mrk 514 026-uen b section 6 c...

  • Page 54

    1mrk002801-ac-13-670-1.2-pg v2 en-us figure 22: static output module (som) 1mrk002801-ac-14-670-1.2-pg v2 en-us figure 23: binary in/out module (iom) section 6 1mrk 514 026-uen b connecting 48 670 series 2.2 iec installation manual.

  • Page 55

    6.1.1.4 connection examples for high impedance differential protection guid-8c58a73d-7c2e-4be5-ab87-b4c93fb7d62b v5 warning! Use extreme caution! Dangerously high voltages might be present on this equipment, especially on the plate with resistors. De-energize the primary object protected with this e...

  • Page 56

    3 necessary connection for three-phase metrosil set. 4 position of optional test switch for secondary injection into the high impedance differential ied. 5 necessary connection for setting resistors. 6 factory-made star point on a three-phase setting resistor set. The star point connector must be re...

  • Page 57

    2 one-phase plate with stabilizing resistor and metrosil. Protective earth is a separate 4 mm screw terminal on the plate. 3 necessary connection for the metrosil. 4 position of optional test switch for secondary injection into the high impedance differential ied. 5 necessary connection for stabiliz...

  • Page 58

    6.1.3 connecting the power supply module semod128790-5 v6 the wiring from the cubicle terminal block to the ied terminals (see figure 20 for psm connection diagram) must be made in accordance with the established guidelines for this type of equipment. Do not insert anything else to the female connec...

  • Page 59

    6.1.5 connecting the binary input and output signals m11992-9 v8 auxiliary power and signals are connected using voltage connectors. Signal wires are connected to a female connector (see figure 27 ) which is then plugged into the corresponding male connector (see figure 28 ) located at the rear of t...

  • Page 60

    Iec02000742-2-en.Vsdx iec02000742 v2 en-us iec16000050-1-en.Vsdx iec16000050 v1 en-us figure 27: a female connector (top: screw compression type, bottom: ringlug type) iec04000167 v1 en-us figure 28: board with male connectors section 6 1mrk 514 026-uen b connecting 54 670 series 2.2 iec installatio...

  • Page 61

    1 2 iec06000168 v3 en-us figure 29: accessories posno description 1 ferrule 2 bridge connector, used to jump terminal points in a connector. M12583-1 v6 table 10: auxiliary power supply and binary i/o connectors connector type rated voltage maximum conductor area screw compression type 250 v ac 2.5 ...

  • Page 62

    Iec13000234-1-en.Vsd guid-682a59d0-950c-4d89-8318-984e0a8b2761 v1 en-us figure 30: shield connection clamp the cable shield shall be properly connected to the ied chassis by the cable clamp with the maximum open conductor length of 40 mm between clamp and terminals. If double shielded cable is used,...

  • Page 63

    6.2 making the electrical connection to the rotor and stator injection equipment (reg670 only) 6.2.1 connectors for injection unit rex060, coupling capacitor unit rex061 and shunt resistor unit rex062 6.2.1.1 injection unit rex060 guid-18b7451e-7f72-4c24-99e7-e72ed2f99b43 v3 x11 rear view x61 x81 x6...

  • Page 64

    1mrk002501-ba-4-pg v2 en-us figure 33: stator injection module section 6 1mrk 514 026-uen b connecting 58 670 series 2.2 iec installation manual.

  • Page 65

    1mrk002501-ba-5-pg v2 en-us figure 34: rotor injection module 1mrk 514 026-uen b section 6 connecting 670 series 2.2 iec 59 installation manual.

  • Page 66

    6.2.1.2 coupling capacitor unit rex061 guid-a35479a3-6be6-4c8a-be3c-ff03af68a197 v2 front view bottom view x1 x2 abb (235 mm) (217 mm) module slot terminal ccm p1 x1, x2 rex061 p1 1mrk002551-ba-1-pg v2 en-us figure 35: designation for capacitor unit casing protective conductor terminal. For connecti...

  • Page 67

    1mrk002551-ba-2-pg v2 en-us figure 36: coupling capacitor module 1mrk 514 026-uen b section 6 connecting 670 series 2.2 iec 61 installation manual.

  • Page 68

    6.2.1.3 shunt resistor unit rex062 guid-f16ba87e-7744-4236-bc98-4ebb3ff576a9 v2 front view bottom view x1 abb (235 mm) (217 mm) p1 module slot terminal srm p1 x1 rex062 1mrk002556-ba-1-pg v2 en-us figure 37: designation for shunt resistor unit casing protective conductor terminal. For connection of ...

  • Page 69

    1mrk002556-ba-2-pg v2 en-us figure 38: shunt resistor module 6.2.2 connecting injection unit rex060, coupling capacitor unit rex061 and shunt resistor unit rex062 guid-0b6a1cde-9cde-413c-9e85-9314175d901e v4 the injection unit rex060 should be installed close to the ied in the same cubicle, or at mi...

  • Page 70

    Guidelines for this type of equipment. The auxiliary power wiring should have a minimum cross-sectional area of 1.0 mm 2 and a voltage rating of 250 v. Branch circuit protection must be provided in the auxiliary power supply wiring to the ied and, if necessary, it must be possible to disconnect it m...

  • Page 71

    Iec11000225-2-en.Vsd iec11000225 v3 en-us figure 40: stator connection example, with rex062 iec11000236-2-en.Vsd iec11000236 v3 en-us figure 41: stator connection example, without rex062 for connection details regarding rex060, rex061 and rex062, refer to section connection diagrams in the reg670 te...

  • Page 72

    Rex060 connections table 11: power x11 no signal 1 ready, power off no binary out 2 power off common binary out 3 fail, power off nc binary out 4 power input positive 5 power input negative table 12: stator ied and sense connection x61 no signals 1 block injection, 220 v binary in 2 block injection,...

  • Page 73

    Table 14: rotor injection and ied connection x81 no signal 1 block injection, 220 v binary in 2 block injection, 110 v binary in 3 block injection, 48 v binary in 4 block injection, common binary in 5 injection blocked nc binary out 6 voltage/current saturation no binary out 7 common binary out 8 vo...

  • Page 74

    Rex061 capacitor unit connections table 16: injection and rotor connection x1 no signal 1 rotor positive pole 2 - 3 positive pole 4 - 5 negative pole 6 - 7 rotor negative pole 8 - 9 rotor injection 10 injection earth. Internally connected to chassis and pe table 17: measurment connector x2 no signal...

  • Page 75

    Rex062 shunt resistor unit connections table 18: injection via shunt resistors connection x1 no signal 1 - 2 injection 3 - 4 injection return 5 - 6 current sense output 7 - 8 current sense output 9 injection input, external shunt 10 injection input return, external shunt x1 connector. Connect each s...

  • Page 76

    Rex060 x61 9 8 8 9 11 10 11 10 x81 stator module sim rotor module rim ied voltage measure (u) voltage measure (u) current measure (u) current measure (u) iec11000209-1-en.Vsd iec11000209 v1 en-us figure 42: separate analog inputs for stator sttiphiz and rotor rotiphiz protection 2. It is possible to...

  • Page 77

    Some settings are required for the analog voltage inputs. Set the voltage ratio for the inputs to 1/1, for example, vtsecx = 100 v vtprimx = 0.1 kv the analog inputs are linked to a pre-processor block in the signal matrix tool. This pre-processor block must have the same cycle time, 8 ms, as the fu...

  • Page 78

    Optical fibers have transmission (tx) and reception (rx) connectors, and they should be attached to the tx and rx connectors on the slm module (tx cable to rx connector, rx cable to tx connector). Connectors are usually color coded: connect blue or dark grey cable connectors to blue or dark grey (re...

  • Page 79

    Schemes on the ieee/ansi c37.94 protocol. The optical ports on the rear side of the ied are x305, x306, x312, x313, x322 and x323. When ldcm is used for binary signal exchange between ieds in the same station or even within the same panel, the fiber optic cables can be quite short (1-2 meters). With...

  • Page 80

    Pin name 2-wire name 4-wire description 2–wire: connect pin x1:1 to pin x1:6 and pin x1:2 to pin x1:5. Termination (2-wire): connect pin x1:1 to pin x1:3 termination (4-wire): connect pin x1:1 to pin x1:3 and pin x1:4 to pin x1:6 the distance between connection points should be 45 and 46 . Only the ...

  • Page 81

    Cc cc 1) external equipment (pc) pe 1) 3) 2) 4) ied x1 1 6 5 4 3 2 ied 1 6 5 4 3 2 x1 4) iec13000229-1-en.Vsd 3) iec07000141 v2 en-us figure 45: communication cable installation, 2-wire where: 1 the inner shields shall be connected together (with an isolated terminal block) and only have one connect...

  • Page 82

    External equipment (pc) pe 1) 3) 2) ied 1 6 5 4 3 2 x1 4) cc 4) ied x1 1 6 5 4 3 2 1) 1) cc iec13000230-1-en.Vsd 3) iec07000142 v2 en-us figure 46: communication cable installation, 4-wire where: 1 the inner shields shall be connected together (with an isolated terminal block) and only have one conn...

  • Page 83

    En03000110.Vsd 1 2 iec03000110 v1 en-us figure 47: cable contact, phoenix: mstb2.5/6-st-5.08 1757051 where: 1 is cable 2 is screw conductor pair shield pair separator jacket separator overall shield drain wire en07000139.Vsd iec07000139 v1 en-us figure 48: cross section of communication cable the ei...

  • Page 84

    1 normative references eia standard rs-485 - electrical characteristics of generators and receivers for balanced digital multipoint systems 2 transmission method rs-485 differential bipolar signaling 2.1 differential signal levels two differential signal levels are defined: a+ =line a positive with ...

  • Page 85

    Exv is supplied by the node at end of the bus segment the specifications of the components are: a) ru + 5 v to signal b = 390 w, 0.25 w ±2.5% b) rt signal b to signal a = 220 w, 0.25 w ±2.5% c) rd signal a to gnd = 390 w, 0.25 w ±2.5% 2.3.3 bus power distribution the end node in each ph-segment appl...

  • Page 86

    1 2 4 3 5 6 7 xx05000510.Vsd iec05000510 v1 en-us posno description 1 gps antenna 2 tnc connector 3 console, 78x150 mm 4 mounting holes 5.5 mm 5 tab for securing of antenna cable 6 vertical mounting position (on antenna mast etc.) 7 horizontal mounting position mount the antenna and console clear of...

  • Page 87

    A 99001046.Vsd iec99001046 v1 en-us figure 50: antenna line-of-sight 6.5.2 electrical installation m12267-34 v4 use a 50 ohm coaxial cable with a male tnc connector on the antenna end and a male sma connector on the receiver end to connect the antenna to the ied. Choose cable type and length so that...

  • Page 88

    82.

  • Page 89

    Section 7 checking installation 7.1 identifying hardware and software version guid-7527a986-f827-4104-b0e9-c62b1b0ef706 v1 the information of hardware and software versions of the ied are available on the label attached on the case of the ied. There are also module labels that can be used to identif...

  • Page 90

    If the self supervision of the ied detects a diagnostic error during the start-up process, the green ready led flashes. Further information on the error may be visible on the local hmi under main menu/diagnostics/ied status/general. Note down the displayed information as reference when contacting ab...

  • Page 91

    Section 8 removing, repairing and exchanging 8.1 product lifecycle guid-d1a48469-e2db-4e39-8431-1686f13ffc4d v8 at some point of the product lifecycle, the ied will be upgraded to a next generation unit. When selecting the original product, already consider the upgrading and extension possibilities ...

  • Page 92

    8.4 sending the ied for repair amu0600445 v4 in case of product problems, contact the nearest abb office or representative for consultation and instructions. 8.5 exchanging the ied guid-1eb39784-696c-4b2e-b560-4115f721dcab v9 to exchange the ied with another identical unit, remove the ied and instal...

  • Page 93

    Section 9 technical data 9.1 dimensions ip11490-1 v3 9.1.1 case without rear cover semod53195-1 v1 m2152-3 v5 c b d e a iec08000164-3-en.Vsdx iec08000164 v3 en-us figure 51: case without rear cover 1mrk 514 026-uen b section 9 technical data 670 series 2.2 iec 87 installation manual.

  • Page 94

    Iec08000166-2-en.Vsdx j g f k h iec08000166 v2 en-us figure 52: case without rear cover with 19” rack mounting kit m2152-11 v4 case size (mm) a b c d e f g h j k 6u, 1/2 x 19” 266.7 224.0 204.1 249.9 205.8 190.5 204.0 242.3 188.9 259.1 6u, 3/4 x 19” 266.7 336.2 204.1 249.9 318.0 190.5 316.2 354.4 18...

  • Page 95

    9.1.2 case with rear cover semod53199-1 v1 m11985-110 v4 c b d e a iec08000163-2-en.Vsd iec08000163 v2 en-us figure 53: case with rear cover 1mrk 514 026-uen b section 9 technical data 670 series 2.2 iec 89 installation manual.

  • Page 96

    Iec08000165-2-en.Vsdx j g f k h iec08000165 v2 en-us figure 54: case with rear cover and 19” rack mounting kit iec05000503-2-en.Vsd iec05000503 v2 en-us figure 55: rear cover case with details m11985-120 v4 case size (mm) a b c d e f g h j k 6u, 1/2 x 19” 265.9 223.7 242.1 255.8 205.7 190.5 203.7 46...

  • Page 97

    9.1.3 flush mounting dimensions m11571-3 v6 c a iec04000465-3-en.Vsd b e d iec04000465 v3 en-us figure 56: flush mounting case size tolerance cut-out dimensions (mm) a +/-1 b +/-1 c d 6u, 1/2 x 19" 210.1 254.3 4.0-10.0 13.5 6u, 3/4 x 19" 322.4 254.3 4.0-10.0 13.5 6u, 1/1 x 19" 434.7 254.3 4.0-10.0 1...

  • Page 98

    9.1.4 side-by-side flush mounting dimensions m11984-3 v6 iec06000182-2-en.Vsd iec06000182 v2 en-us figure 57: a 1/2 x 19” size ied side-by-side with rhgs6 xx05000505.Vsd b a c g d e f iec05000505 v1 en-us figure 58: panel-cut out dimensions for side-by-side flush mounting case size (mm) tolerance a ...

  • Page 99

    9.1.5 wall mounting dimensions m11569-3 v4 iec04000471-2-en.Vsd iec04000471 v2 en-us figure 59: wall mounting case size (mm) a b c d e 6u, 1/2 x 19” 292.0 267.1 272.8 390.0 243.0 6u, 3/4 x 19” 404.3 379.4 272.8 390.0 243.0 6u, 1/1 x 19” 516.0 491.1 272.8 390.0 243.0 1mrk 514 026-uen b section 9 tech...

  • Page 100

    94.

  • Page 101

    Section 10 glossary m14893-1 v17 ac alternating current acc actual channel act application configuration tool within pcm600 a/d converter analog-to-digital converter adbs amplitude deadband supervision adm analog digital conversion module, with time synchronization ai analog input ansi american nati...

  • Page 102

    Ccitt consultative committee for international telegraph and telephony. A united nations-sponsored standards body within the international telecommunications union. Ccm can carrier module ccvt capacitive coupled voltage transformer class c protection current transformer class as per ieee/ ansi cmpps...

  • Page 103

    Dhcp dynamic host configuration protocol dip-switch small switch mounted on a printed circuit board di digital input dllb dead line live bus dnp distributed network protocol as per ieee std 1815-2012 dr disturbance recorder dram dynamic random access memory drh disturbance report handler dsp digital...

  • Page 104

    Gde graphical display editor within pcm600 gi general interrogation command gis gas-insulated switchgear goose generic object-oriented substation event gps global positioning system gsal generic security application gse generic substation event hdlc protocol high-level data link control, protocol ba...

  • Page 105

    Ieee 1686 standard for substation intelligent electronic devices (ieds) cyber security capabilities ied intelligent electronic device iet600 integrated engineering tool i-gis intelligent gas-insulated switchgear iom binary input/output module instance when several occurrences of the same function ar...

  • Page 106

    Mpm main processing module mval value of measurement mvb multifunction vehicle bus. Standardized serial bus originally developed for use in trains. Ncc national control centre nof number of grid faults num numerical module oco cycle open-close-open cycle ocp overcurrent protection oem optical ethern...

  • Page 107

    Rasc synchrocheck relay, combiflex rca relay characteristic angle risc reduced instruction set computer rms value root mean square value rs422 a balanced serial interface for the transmission of digital data in point-to-point connections rs485 serial link according to eia standard rs485 rtc real-tim...

  • Page 108

    St switch or push button to trip starpoint neutral point of transformer or generator svc static var compensation tc trip coil tcs trip circuit supervision tcp transmission control protocol. The most common transport layer protocol used on ethernet and the internet. Tcp/ip transmission control protoc...

  • Page 109

    Allowing for the eccentricity of the earth's orbit, the rotational axis tilt (23.5 degrees), but still showing the earth's irregular rotation, on which ut1 is based. The coordinated universal time is expressed using a 24-hour clock, and uses the gregorian calendar. It is used for aeroplane and ship ...

  • Page 110

    104.

  • Page 111

    105.

  • Page 112