ABB REC650 ANSI Product Manual

Manual is about: Relion 650 series Bay control

Summary of REC650 ANSI

  • Page 1

    Relion ® 650 series bay control rec650 product guide.

  • Page 2

    Contents 1. 650 series overview..............................................3 2. Application...........................................................3 3. Available functions...............................................6 4. Control................................................................1...

  • Page 3

    1. 650 series overview the 650 series ieds provide optimum 'off-the- shelf', ready-to-use solutions. It is configured with complete protection functionality and default parameters to meet the needs of a wide range of applications for generation transmission and sub-transmission grids. The 650 series...

  • Page 4

    Rec650-a01 – single busbar single breaker 10ai (4i+1i+5u) s cswi control s xcbr control s cswi control smb rrec 79 0->1 s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions s xswi control s...

  • Page 5

    Rec650-a02 – double busbar single breaker 10ai (4i+1i+5u) s cswi control s xcbr control s cswi control smb rrec 79 0->1 s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions s...

  • Page 6

    Rec650-a07 – bus coupler single breaker 10ai (6i+4u) s cswi control s xcbr control s cswi control s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions s xswi control s xswi c...

  • Page 7

    3. Available functions bay control rec650 1mrk 511 249-ben - product version: 1.1 issued: february 2011 abb 7.

  • Page 8

    Control and monitoring functions iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab control sesrsyn 25 synchrocheck, energizing check, and synchronizing 1 1 1 smbrrec 79 autorecloser 1 1 1 scilo 3 logical node for interlocking 8 8 8 bb...

  • Page 9

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab qcbay bay control 1 1 1 locrem handling of lr-switch positions 1 1 1 locremctrl lhmi control of permitted source to operate (psto) 1 1 1 slggio logic rotating switch for function selec...

  • Page 10

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab or configurable logic blocks, or gate 283 283 283 inverter configurable logic blocks, inverter gate 140 140 140 pulsetimer configurable logic blocks, pulse timer 40 40 40 gate configur...

  • Page 11

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab timersetqt configurable logic q/t, timer function block with quality and time 40 40 40 pulsetimerqt configurable logic q/t, pulse timer with quality and time 40 40 40 invalidqt configu...

  • Page 12

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab drprdre disturbance report 1 1 1 axradr analog input signals 4 4 4 bxrbdr binary input signals 6 6 6 spggio iec 61850 generic communication i/ o functions 64 64 64 sp16ggio iec 61850 g...

  • Page 13

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab metering pcggio pulse counter logic 16 16 16 etpmmtr function for energy calculation and demand handling 3 3 3 bay control rec650 1mrk 511 249-ben - product version: 1.1 issued: februa...

  • Page 14

    Back-up protection functions iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab current protection phpioc 50 instantaneous phase overcurrent protection 1 1 1 oc4ptoc 51/67 four step directional phase overcurrent protection 1 1 1 efpioc...

  • Page 15

    Iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab frequency protection saptuf 81 underfrequency function 2 2 2 saptof 81 overfrequency function 2 2 2 sapfrc 81 rate-of-change frequency protection 2 2 2 bay control rec650 1mrk 511 249-...

  • Page 16

    Designed to communicate iec 61850/ function block name ansi function description bay rec650 (a01) 1cba rec650 (a02) 1cbab rec650 (a07) bcab station communication iec 61850 communication protocol, lan1 1 1 1 dnp3.0 for tcp/ip communication protocol, lan1 1 1 1 iec61870-5-103 iec60870-5-103 serial com...

  • Page 17

    Basic ied functions iec 61850/ function block name function description basic functions included in all products interrsig self supervision with internal event list 1 selfsupevlst self supervision with internal event list 1 sntp time synchronization 1 timesynchgen time synchronization 1 dtsbegin, dt...

  • Page 18

    4. Control synchrocheck, energizing check, and synchronizing sesrsyn the synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability. Synchrocheck, energizing check, and synchronizing (sesrsyn) function...

  • Page 19

    Iec09000668-1-en.Vsd iec09000668 v1 en figure 4. Select before operation with confirmation of command iec09000669-2-en.Vsd cancel ok iec09000669 v2 en figure 5. Overriding of synchrocheck bay control qcbay the bay control qcbay function is used together with local remote and local remote control fun...

  • Page 20

    Iec 61850 generic communication i/o functions dpggio the iec 61850 generic communication i/o functions (dpggio) function block is used to send double indications to other systems or equipment in the substation. It is especially used in the interlocking and reservation station-wide logics. Single poi...

  • Page 21

    Directional operation can be combined together with corresponding communication logic in permissive or blocking teleprotection scheme. Current reversal and weak-end infeed functionality are available as well. Sensitive directional residual overcurrent and power protection sdepsde in isolated network...

  • Page 22

    The pole discordance function operates based on information from the circuit breaker logic with additional criteria from unsymmetrical phase currents when required. Broken conductor check brcptoc conventional protection functions can not detect the broken conductor condition. Broken conductor check ...

  • Page 23

    Transformers or measures it from a single voltage input transformer fed from an open delta or neutral point voltage transformer. Rov2ptov has two voltage steps, where step 1 can be set as inverse or definite time delayed. Step 2 is always definite time delayed. Loss of voltage check lovptuv loss of ...

  • Page 24

    Transformer and the ied in order to avoid unwanted operations that otherwise might occur. The fuse failure supervision function basically has three different algorithms, negative sequence and zero sequence based algorithms and an additional delta voltage and delta current algorithm. The negative seq...

  • Page 25

    • loopdelay function block used to delay the output signal one execution cycle. • timerset function has pick-up and drop- out delayed outputs related to the input signal. The timer has a settable time delay. • and function block. • srmemory function block is a flip-flop that can set or reset an outp...

  • Page 26

    Output changes, the event bit in the state part is toggled. The function also propagates timestamp and quality of input signals. • indextspqt extracts individual signals from a group signal input. Value part of single position input is copied to si_out output. Time part of single position input is c...

  • Page 27

    Blocks, which are set to trigger the disturbance recorder. All signals from start of pre-fault time to the end of post-fault time will be included in the recording. Every disturbance report recording is saved in the ied in the standard comtrade format. The same applies to all events, which are conti...

  • Page 28

    The function is characterized by great flexibility and is not dependent on the operation of protection functions. It can record disturbances not detected by protection functions. The disturbance recorder information for the last 100 disturbances are saved in the ied and the local hmi is used to view...

  • Page 29

    Scaled service value is available over the station bus. Function for energy calculation and demand handling etpmmtr outputs from the measurements (cvmmxn) function can be used to calculate energy consumption. Active as well as reactive values are calculated in import and export direction. Values can...

  • Page 30

    Time-tagging of internal events and disturbances are an excellent help when evaluating faults. Without time synchronization, only the events within the ied can be compared to one another. With time synchronization, events and disturbances within the entire station, and even between line ends, can be...

  • Page 31

    According to goose is part of the standard. Disturbance files uploading is provided. Disturbance files are accessed using the iec 61850-8-1 protocol. Disturbance files are available to any ethernet based application via ftp in the standard comtrade format. Further, the ied can send and receive binar...

  • Page 32

    15. Hardware description layout and dimensions mounting alternatives the following mounting alternatives are available (ip40 protection from the front): • 19” rack mounting kit • wall mounting kit • flush mounting kit • 19" dual rack mounting kit see ordering for details about available mounting alt...

  • Page 33

    A b c e d iec09000677.Ai iec09000677 v1 en figure 10. Two rack mounted ieds side by side a 224 mm + 12 mm with ring-lug connector b 25.5 mm c 482.6 mm (19") d 13 mm e 265.9 mm (6u) wall mounting the ied c f g b a e d iec09000678.Ai iec09000678 v1 en figure 11. Wall mounting the ied a 270 mm e 190.5 ...

  • Page 34

    16. Connection diagrams 1mrk006501-bb 2 pg 1.1 iec v1 en figure 13. Designation for 6u, 1/2x19" casing with 1 trm module slot rear position com pcom x0, x1, x4, x9,x304 psm ppsm x307, x309, x410 trm p2 x101, x102 bio p3 x321, x324 bio p4 x326, x329 bio p5 x331, x334 bio p6 x336, x339 bay control rec...

  • Page 35

    Connection diagrams for rec650 a01 1mrk006501-db 3 pg 1.1 iec v1 en figure 14. Communication module (com) 1mrk006501-db 4 pg 1.1 iec v1 en figure 15. Power supply module (psm) 48-125v dc 1mrk006501-db 5 pg 1.1 iec v1 en figure 16. Power supply module (psm), 110-250v dc 1mrk006501-db 6 pg 1.1 iec v1 ...

  • Page 36

    1mrk006501-db 7 pg 1.1 iec v1 en figure 18. Binary input/output (bio) option (terminal x321, x324) 1mrk006501-db 8 pg 1.1 iec v1 en figure 19. Binary input/output (bio) option (terminal x326, 329) 1mrk006501-db 9 pg 1.1 iec v1 en figure 20. Binary input/output (bio) option (terminal x331, 334) conne...

  • Page 37

    1mrk006501-cb 4 pg 1.1 iec v1 en figure 22. Power supply module (psm) 48-125v dc 1mrk006501-cb 5 pg 1.1 iec v1 en figure 23. Power supply module (psm), 110-250v dc 1mrk006501-cb 6 pg 1.1 iec v1 en figure 24. Transformer module (trm) 1mrk006501-cb 7 pg 1.1 iec v1 en figure 25. Binary input/output (bi...

  • Page 38

    1mrk006501-cb 8 pg 1.1 iec v1 en figure 26. Binary input/output (bio) option (terminal x326, x329) 1mrk006501-cb 9 pg 1.1 iec v1 en figure 27. Binary input/output (bio) option (terminal x331, x334) 1mrk006501-cb 10 pg 1.1 iec v1 en figure 28. Binary input/output (bio) option (x336, x339) connection ...

  • Page 39

    1mrk006501-bb 4 pg 1.1 iec v1 en figure 30. Power supply module (psm) 48-125v dc 1mrk006501-bb 5 pg 1.1 iec v1 en figure 31. Power supply module (psm), 110-250v dc 1mrk006501-bb 6 pg 1.1 iec v1 en figure 32. Transformer module (trm) 1mrk006501-bb 7 pg 1.1 iec v1 en figure 33. Binary input/output (bi...

  • Page 40

    1mrk006501-bb 8 pg 1.1 iec v1 en figure 34. Binary input/output (bio) option (terminal x326, x329) 1mrk006501-bb 9 pg 1.1 iec v1 en figure 35. Binary input/output (bio) option (terminal x331, x334) 1mrk006501-bb 10 pg 1.1 iec v1 en figure 36. Binary input/output (bio) option (terminal x336, x339) ba...

  • Page 41

    17. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 42

    Analog inputs table 2. Energizing inputs description value rated frequency 50/60 hz operating range rated frequency ± 5 hz current inputs rated current, i n 0.1/0.5 a 1) 1/5 a 2) thermal withstand capability: • continuously 4 a 20 a • for 1 s 100 a 500 a • for 10 s 20 a 100 a dynamic current withsta...

  • Page 43

    Auxiliary dc voltage table 3. Power supply description type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 48, 60, 110, 125 v dc 110, 125, 220, 250 v dc u aux variation 85...110% of u n (85...264 v ac) 80...120% of u n (38.4...150 v dc) 80...120% of u n (88...300 v dc) maximum loa...

  • Page 44

    Table 5. Signal output and irf output irf relay change over - type signal output relay description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 30 a breaking capacity when the control-circuit time constant l/r v dc ≤0.5 a/≤0.1 a/≤0.0...

  • Page 45

    Table 8. Ethernet interfaces ethernet interface protocol cable data transfer rate lan/hmi port (x0) 1) - cat 6 s/ftp or better 100 mbits/s lan1 (x1) tcp/ip protocol fibre-optic cable with lc connector 100 mbits/s 1) only available for the external hmi option. Table 9. Fibre-optic communication link ...

  • Page 46

    Table 14. Environmental conditions description value operating temperature range -25...+55ºc (continuous) short-time service temperature range -40...+70ºc ( note: degradation in mtbf and hmi performance outside the temperature range of -25...+55ºc relative humidity atmospheric pressure 86...106 kpa ...

  • Page 47

    Type tests according to standards table 16. Electromagnetic compatibility tests description type test value reference 100 khz and 1 mhz burst disturbance test iec 61000-4-18 iec 60255-22-1, level 3 • common mode 2.5 kv • differential mode 1.0 kv electrostatic discharge test iec 61000-4-2 iec 60255-2...

  • Page 48

    Table 16. Electromagnetic compatibility tests, continued description type test value reference power frequency immunity test • common mode • differential mode 300 v rms 150 v rms iec 60255-22-7, class a iec 61000-4-16 voltage dips and short interruptions dips: 40%/200 ms 70%/500 ms interruptions: 0-...

  • Page 49

    Table 17. Insulation tests description type test value reference dielectric tests: iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 1 kv, 50 hz, 1 min, communication impulse voltage test: iec 60255-5 • test voltage 5 kv, unipolar impulses, waveform 1.2/50 μs, source energy 0.5 j 1 kv, unipolar impulses...

  • Page 50

    Emc compliance table 20. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) current protection table 21. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i £ ...

  • Page 51

    Table 22. Four step phase overcurrent protection oc4ptoc function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% - min. Operating current (1-10000)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r independent time ...

  • Page 52

    Table 23. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typically at 2 to 0 x i set - criti...

  • Page 53

    Table 24. Four step residual overcurrent protection ef4ptoc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate current for directional comparison (1–100)% of lbase ± 1.0% of i r min. Operating current (1-100...

  • Page 54

    Table 25. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of lbase at low setting: (2.5-10) ma (10-50) ma ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r ± 0.5 ma ± ...

  • Page 55

    Table 25. Sensitive directional residual overcurrent and power protection sdepsde, continued function range or value accuracy operate time, non- directional residual over current 80 ms typically at 0.5 to 2 x i set - reset time, non- directional residual over current 90 ms typically at 1.2 to 0.5 x ...

  • Page 56

    Table 26. Thermal overload protection, one time constant lpttr function range or value accuracy reference current (0-400)% of ibase ± 1.0% of i r reference temperature (0-600)°c ± 1.0°c operate time: 2 2 2 2 ln p b i i t i i t æ ö - ç ÷ = × ç ÷ - è ø equation1356 v1 en (equation 1) i = actual measur...

  • Page 57

    Table 28. Stub protection stbptoc function range or value accuracy operating current (1-2500)% of ibase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operating time 20 ms typically at 0 to 2 x i set - resetting time 30 ms typically at 2 to 0 x i set - critical impulse time 10 m...

  • Page 58

    Table 31. Directional over/underpower protection goppdop, guppdup function range or value accuracy power level (0.0–500.0)% of sbase ± 1.0% of s r at s r ± 1.0% of s at s > s r 1) (1.0-2.0)% of sbase 2) (2.0-10)% of sbase 3) characteristic angle (-180.0–180.0) degrees 2 degrees timers (0.010 - 6000....

  • Page 59

    Voltage protection table 33. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1–100)% of ubase ± 0.5% of u r reset ratio - inverse time characteristics for low and high step, see table 69 - see table 69 definite time delay, step 1 (0.00 - ...

  • Page 60

    Table 35. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 (1-200)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r operate voltage, step 2 (1–100)% of ubase ± 0.5% of u r at u r ± 0.5% of u at u > u r reset ratio >95% - inverse time cha...

  • Page 61

    Frequency protection table 37. Under frequency protection saptuf function range or value accuracy operate value, start function (35.00-75.00) hz ± 2.0 mhz operate value, restore frequency (45 - 65) hz ± 2.0 mhz operate time, start function at 50 hz: 200 ms typically at f set +0.5 hz to f set -0.5 hz...

  • Page 62

    Table 39. Rate-of-change frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ± 10.0 mhz/s operate value, restore enable frequency (45.00 - 65.00) hz ± 2.0 mhz timers (0.000 - 60.000) s operate time, start function at 50 hz: 100 ms typically ...

  • Page 63

    Table 42. Breaker close/trip circuit monitoring tcsscbr function range or value accuracy operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms control table 43. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degree...

  • Page 64

    Table 44. Autorecloser smbrrec function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 3ph (0.000-60.000) s ± 0.5% ± 25 ms shot 2 - t2 3ph shot 3 - t3 3ph shot 4 - t4 3ph shot 5 - t5 3ph (0.00-6000.00) s autorecloser maximum wait time for sync (0.0...

  • Page 65

    Table 46. Configurable logic blocks logic block quantity with cycle time range or value accuracy 5 ms 20 ms 100 ms and 60 60 160 - - or 60 60 160 - - xor 10 10 20 - - inverter 30 30 80 - - srmemory 10 10 20 - - rsmemory 10 10 20 - - gate 10 10 20 - - pulsetimer 10 10 20 (0.000–90000.000) s ± 0.5% ± ...

  • Page 66

    Monitoring table 48. Measurements cvmmxn function range or value accuracy voltage (0.1-1.5) ×u r ± 0.5% of u r at u £ u r ± 0.5% of u at u > u r connected current (0.2-4.0) × i r ± 0.5% of i r at i £ i r ± 0.5% of i at i > i r active power, p 0.1 x u r r 0.2 x i r r ± 1.0% of s r at s ≤ s r ± 1.0% o...

  • Page 67

    Table 50. Disturbance report drprdre function range or value accuracy current recording - ± 1,0% of i r at i ≤ i r ± 1,0% of i at i > ir voltage recording - ± 1,0% of u r at u ≤ u r ± 1,0% of u at u > u r pre-fault time (0.05–3.00) s - post-fault time (0.1–10.0) s - limit time (0.5–8.0) s - maximum ...

  • Page 68

    Table 51. Event list drprdre function value buffer capacity maximum number of events in the list 1000 resolution 1 ms accuracy depending on time synchronizing table 52. Indications drprdre function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number...

  • Page 69

    Table 55. Disturbance recorder drprdre function value buffer capacity maximum number of analog inputs 40 maximum number of binary inputs 96 maximum number of disturbance reports 100 maximum total recording time (3.4 s recording time and maximum number of channels, typical value) 340 seconds (100 rec...

  • Page 70

    Table 59. Circuit breaker condition monitoring sscbr function range or value accuracy alarm levels for open and close travel time (0-200) ms ± 0.5% ± 25 ms alarm levels for number of operations (0 - 9999) - setting of alarm for spring charging time (0.00-60.00) s ± 0.5% ± 25 ms time delay for gas pr...

  • Page 71

    Dimensions table 64. Dimensions description value width 220 mm height 265.9 mm (6u) depth 249.5 mm weight box weight lhmi 1.3 kg (6u) inverse time characteristics table 65. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = + × - æ ö ç ÷ ç ÷ è ø p a ...

  • Page 72

    Table 66. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 - iec normal inverse a=0.14, p=0.02 iec 60255-151, class 5 + 40 ms iec very inver...

  • Page 73

    Table 68. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: 2.0 480 32 0.5 0.035...

  • Page 74

    Table 69. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = uv measured k = (0.05-1.10) in steps of 0.01 unless otherwise stated class 5 +40 ms type b curve: 2.0 480 0.055 32 0.5 × = + × ...

  • Page 75

    Table 70. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 class 5 +40 ms type b curve: 2.0 480 32 0.5 0.035 = × - > × - - ...

  • Page 76

    18. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the example below. Exem...

  • Page 77

    Casing #5 notes and rules rack casing, 6 u 1/2 x 19" b selection for position #5. B mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x rack mounting kit for 6 u 1/2 x 19" a wall mounting kit for 6u 1/2 x 19" d flush mounting kit for 6u 1/2 x 19" e w...

  • Page 78

    Connection type for analog modules #9 notes and rules compression terminals s ringlug terminals r analog system slot position: p2 transformer module, 6i + 4u 1/5a, 100/220v a1 only for a07 transformer module, 4i, 1/5a+1i, 0.1/0.5a+5u, 100/220v a3 a01 and a02 selection for position #9. Binary input/o...

  • Page 79

    Manuals note: one (1) ied connect cd containing user documentation (operation manual, technical manual, installation manual, commissioning manual, application manual, communication protocol manual, dnp, communication protocol manual, iec61850, communication protocol manual, iec60870-5-103, type test...

  • Page 80

    Related documents documents related to rec650 identity number application manual 1mrk 511 246-uen technical manual 1mrk 511 247-uen commissioning manual 1mrk 511 248-uen product guide 1mrk 511 249-ben type test certificate 1mrk 511 249-ten 650 series manuals identity number communication protocol ma...

  • Page 81

    81.

  • Page 82

    Contact us abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 fax +46 (0) 21 14 69 18 www.Abb.Com/substationautomation 1mrk 511 249-ben - © copyright 2011 abb. All rights reserved..