ABB REC650 ANSI Product Manual

Manual is about: Relion 650 series Bay control

Summary of REC650 ANSI

  • Page 1

    Relion ® 650 series bay control rec650 ansi product guide.

  • Page 2

    Contents 1. 650 series overview...........................................................3 2. Application.........................................................................3 3. Available functions.............................................................7 4. Control...........................

  • Page 3

    1. 650 series overview the 650 series ieds provide both customized and configured solutions. With the customized ieds you have the freedom to completely adapt the functionality according to your needs. The 650 series ieds provide optimum 'off-the- shelf', ready-to-use solutions. It is configured wit...

  • Page 4

    Rec650-a01a – single busbar single breaker 10ai (4i+1i+5u) s cswi control s xcbr control s cswi control smb rrec 79 0->1 s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions s xswi control ...

  • Page 5

    Rec650-a02a – double busbar single breaker 10ai (4i+1i+5u) s cswi control s xcbr control s cswi control smb rrec 79 0->1 s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions ...

  • Page 6

    Rec650-a07a – bus coupler single breaker 10ai (4i+6u) s cswi control s xcbr control s cswi control s cswi control s cswi control smp ptrc 94 1->0 s cswi control s cswi control s cswi control ses rsyn 25 sync tcs scbr cond tcs scbr cond spvn zbat cond other configured functions s xswi control s xswi ...

  • Page 7

    3. Available functions bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 7.

  • Page 8

    Control and monitoring functions iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab control sesrsyn 25 synchrocheck, energizing check, and synchronizing 0–1 1 1 1 smbrrec 79 autorecloser for 3–phase operation 0–1 1 1 1 apc8 ap...

  • Page 9

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab locremctrl lhmi control of permitted source to operate (psto) 1 1 1 1 slggio logic rotating switch for function selection and lhmi presentation 15 15 15 15 vsggio selector min...

  • Page 10

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab xor configurable logic blocks, exclusive or gate 40 40 40 40 loopdelay configurable logic blocks, loop delay 40 40 40 40 timerset configurable logic blocks, timer function blo...

  • Page 11

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab indextspqt configurable logic q/t, single point indication logic signal gate extracting value with quality and time 20 20 20 20 q/t configurable logic blocks q/t 0–1 20 20 20 ...

  • Page 12

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab cntggio event counter 5 5 5 5 drprdre disturbance report 1 1 1 1 axradr analog input signals 4 4 4 4 bxrbdr binary input signals 6 6 6 6 spggio iec 61850 generic communication...

  • Page 13

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab metering pcggio pulse counter logic 16 16 16 16 etpmmtr function for energy calculation and demand handling 3 3 3 3 bay control rec650 ansi 1mrk 511 265-bus b product version:...

  • Page 14

    Back-up protection functions iec 61850/ function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab current protection phpioc 50 instantaneous phase overcurrent protection, 3–phase output 0–1 1 1 1 oc4ptoc 51 four step phase overcurrent protecti...

  • Page 15

    Iec 61850/ function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab frequency protection saptuf 81 underfrequency function 0–2 2 2 2 saptof 81 overfrequency function 0–2 2 2 2 sapfrc 81 rate-of-change frequency protection 0–2 2 2 2 bay contro...

  • Page 16

    Communication iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab station communication iec61850-8-1 iec 61850 communication protocol 1 1 1 1 dnpgen dnp3.0 for tcp/ip communication protocol 1 1 1 1 rs485dnp dnp3.0 for eia-485 c...

  • Page 17

    Iec 61850/function block name ansi function description bay rec650 rec650 (a01a) 1cba rec650 (a02a) 1cbab rec650 (a07a) bcab optical103 iec60870-5-103 optical serial communication 1 1 1 1 rs485103 iec60870-5-103 serial communication for rs485 1 1 1 1 gooseintlkrcv horizontal communication via goose ...

  • Page 18

    Basic ied functions iec 61850/function block name function description basic functions included in all products interrsig self supervision with internal event list 1 selfsupevlst self supervision with internal event list 1 timesynchgen time synchronization 1 sntp time synchronization 1 dtsbegin, dts...

  • Page 19

    4. Control synchrocheck, energizing check, and synchronizing sesrsyn (25) the synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability. Synchrocheck, energizing check, and synchronizing (sesrsyn, 25)...

  • Page 20

    Ansi09000668-1-en.Vsd ansi09000668 v1 en figure 4. Select before operation with confirmation of command cancel ok ansi09000669-1-en.Vsd ansi09000669 v1 en figure 5. Overriding of synchrocheck bay control qcbay the bay control qcbay function is used together with local remote and local remote control...

  • Page 21

    Vsggio can be controlled from the menu or from a symbol on the single line diagram (sld) on the local hmi. Iec 61850 generic communication i/o functions dpggio the iec 61850 generic communication i/o functions (dpggio) function block is used to send double indications to other systems or equipment i...

  • Page 22

    Second harmonic blocking restraint level can be set for the function and can be used to block each step individually. Ef4ptoc (51n/67n) can be used as main protection for phase-to-ground faults. Ef4ptoc (51n/67n) can also be used to provide a system back-up for example, in the case of the primary pr...

  • Page 23

    Overcurrent function is released from a normally open, 89b auxiliary contact on the line disconnector. Pole discordance protection ccrpld (52pd) circuit breakers and disconnectors can end up with their phases in different positions (close-open), due to electrical or mechanical failures. An open phas...

  • Page 24

    Voltage. When triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks. Ov2ptov (59) has two voltage steps, where step 1 can be set as inverse or definite time delayed. Step 2 is always definite time delayed. Ov2ptov (59) has an extremely high reset ratio to all...

  • Page 25

    A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection functions expected to give unwanted tripping. Fuse failure supervision sddrfuf the aim of the fuse failure supervision function (sddrfuf) is to block voltage measuring functions at failures in th...

  • Page 26

    • gate function block is used for whether or not a signal should be able to pass from the input to the output. • xor function block. • loopdelay function block used to delay the output signal one execution cycle. • timerset function has pick-up and drop-out delayed outputs related to the input signa...

  • Page 27

    State part is toggled. The function also propagates timestamp and quality of input signals. • indextspqt extracts individual signals from a group signal input. Value part of single position input is copied to si_out output. Time part of single position input is copied to time output. State bits in c...

  • Page 28

    The disturbance report function is characterized by great flexibility regarding configuration, initiating conditions, recording times, and large storage capacity. A disturbance is defined as an activation of an input to the axradr or bxrbdr function blocks, which are set to trigger the disturbance r...

  • Page 29

    To the disturbance report function (maximum 40 analog and 96 binary signals). The binary signals available are the same as for the event recorder function. The function is characterized by great flexibility and is not dependent on the operation of protection functions. It can record disturbances not...

  • Page 30

    Circuit breaker monitoring sscbr the circuit breaker condition monitoring function sscbr is used to monitor different parameters of the circuit breaker. The breaker requires maintenance when the number of operations has reached a predefined value. For proper functioning of the circuit breaker, it is...

  • Page 31

    13. Basic ied functions self supervision with internal event list the self supervision with internal event list (interrsig and selfsupevlst) function reacts to internal system events generated by the different built-in self-supervision elements. The internal events are saved in an internal event lis...

  • Page 32

    61850-8-1. Iec 61850-8-1 protocol allows intelligent electrical devices (ieds) from different vendors to exchange information and simplifies system engineering. Peer-to-peer communication according to goose is part of the standard. Disturbance files uploading is provided. Disturbance files are acces...

  • Page 33

    Terminology, a primary station is a master and a secondary station is a slave. The communication is based on a point-to-point principle. The master must have software that can interpret iec 60870-5-103 communication messages. Iec 60870-5-103 protocol can be configured to use either the optical seria...

  • Page 34

    Rack mounting a single 3u ied ansi11000248 v1 en figure 7. Rack mounted 3u ied a 8.82 inches (224 mm) + 0.47 inches (12 mm) with ring-lug connectors b 1 inches (22.5 mm) c 19 inches (482 mm) d 5.20 inches, 3u (132 mm) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 34 abb.

  • Page 35

    16. Connection diagrams customized connection diagrams for 650 series ansi12000601 v1 en figure 8. Designation for 3u, 1/1x19" casing with 1 trm ansi12000602 v1 en figure 9. Designation for 3u, 1/1x19" casing with 1 trm and 1 aim bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 35.

  • Page 36

    Ansi12000603 v1 en figure 10. Communication module (com) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 36 abb.

  • Page 37

    Ansi12000604 v1 en figure 11. Power supply module (psm) 48-125v dc ansi12000605 v1 en figure 12. Power supply module (psm) 110-250v dc, 100–240v ac bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 37.

  • Page 38

    Ansi12000606 v1 en figure 13. Transformer module (trm) ansi12000607 v1 en figure 14. Analog input (aim) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 38 abb.

  • Page 39

    Ansi12000608 v1 en figure 15. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 39.

  • Page 40

    17. Connection diagrams configured 1mrk006502-cc-3-pg-ansi v1 en figure 16. Designation for 3u, 1/1x19" casing with 1 trm (a01a/a02a/a07a) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 40 abb.

  • Page 41

    Connection diagrams for rec650 a01a 1mrk006502-dc-pg-1.2-ansi v1 en figure 17. Communication module (com) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 41.

  • Page 42

    1mrk006502-dc-5-pg-1.2-ansi v1 en figure 18. Power supply module (psm) 48-125v dc bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 42 abb.

  • Page 43

    1mrk006502-dc-6-pg-1.2-ansi v1 en figure 19. Power supply module (psm), 110-250v dc, 100–240v ac bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 43.

  • Page 44

    1mrk006502-dc-7-pg-1.2-ansi v1 en figure 20. Transformer module (trm) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 44 abb.

  • Page 45

    1mrk006502-dc-8-pg-1.2-ansi v1 en figure 21. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 45.

  • Page 46

    1mrk006502-dc-9-pg-1.2-ansi v1 en figure 22. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 46 abb.

  • Page 47

    1mrk006502-dc-10-pg-1.2-ansi v1 en figure 23. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 47.

  • Page 48

    Connection diagrams for rec650 a02a 1mrk006502-cc-pg-1.2-ansi v1 en figure 24. Communication module (com) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 48 abb.

  • Page 49

    1mrk006502-cc-5-pg-1.2-ansi v1 en figure 25. Power supply module (psm) 48-125v dc bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 49.

  • Page 50

    1mrk006502-cc-6-pg-1.2-ansi v1 en figure 26. Power supply module (psm), 110-250v dc, 100–240v ac bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 50 abb.

  • Page 51

    1mrk006502-cc-7-pg-1.2-ansi v1 en figure 27. Transformer module (trm) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 51.

  • Page 52

    1mrk006502-cc-8-pg-1.2-ansi v1 en figure 28. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 52 abb.

  • Page 53

    1mrk006502-cc-9-pg-1.2-ansi v1 en figure 29. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 53.

  • Page 54

    1mrk006502-cc-10-pg-1.2-ansi v1 en figure 30. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 54 abb.

  • Page 55

    1mrk006502-cc-11-pg-1.2-ansi v1 en figure 31. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 55.

  • Page 56

    Connection diagrams for rec650 a07a 1mrk006502-bc-4-pg-1.2-ansi v1 en figure 32. Communication module (com) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 56 abb.

  • Page 57

    1mrk006502-bc-5-pg-1.2-ansi v1 en figure 33. Power supply module (psm) 48-125v dc bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 57.

  • Page 58

    1mrk006502-bc-6-pg-1.2-ansi v1 en figure 34. Power supply module (psm), 110-250v dc, 100–240v ac bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 58 abb.

  • Page 59

    1mrk006502-bc-7-pg-1.2-ansi v1 en figure 35. Transformer module (trm) bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 59.

  • Page 60

    1mrk006502-bc-8-pg-1.2-ansi v1 en figure 36. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 60 abb.

  • Page 61

    1mrk006502-bc-9-pg-1.2-ansi v1 en figure 37. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 61.

  • Page 62

    1mrk006502-bc-10-pg-1.2-ansi v1 en figure 38. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 62 abb.

  • Page 63

    1mrk006502-bc-11-pg-1.2-ansi v1 en figure 39. Binary input/output (bio) option bay control rec650 ansi 1mrk 511 265-bus b product version: 1.2 abb 63.

  • Page 64

    18. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 65

    Auxiliary ac and dc voltage table 3. Power supply description 600psm02 600psm03 v n 48, 60, 110, 125 v dc 100, 110, 120, 220, 240 v ac, 50 and 60 hz 110, 125, 220, 250 v dc v n variation 80...120% of v n (38.4...150 v dc) 85...110% of v n (85...264 v ac) 80...120% of v n (88...300 v dc) maximum load...

  • Page 66

    Table 6. Power output relays without tcm function description value rated voltage 250 v ac/dc continuous contact carry 8 a make and carry for 3.0 s 15 a make and carry for 0.5 s 30 a breaking capacity when the control-circuit time constant l/ r ≤1 a/≤0.3 a/≤0.1 a table 7. Power output relays with tc...

  • Page 67

    Table 10. X8/irig-b and eia-485 interface type protocol cable screw terminal, pin row header irig-b shielded twisted pair cable recommended: cat 5, belden rs-485 (9841- 9844) or alpha wire (alpha 6222-6230) screw terminal, pin row header shielded twisted pair cable recommended: descaflex rd-h(st)h-2...

  • Page 68

    Table 14. Optical serial port (x9) wave length fibre type connector permitted path attenuation 1) 820 nm mm 62,5/125 µm glass fibre core st 6.8 db (approx. 1700m length with 4 db / km fibre attenuation) 820 nm mm 50/125 µm glass fibre core st 2.4 db (approx. 600m length with 4 db / km fibre attenuat...

  • Page 69

    Table 18. Environmental tests description type test value reference cold tests operation storage 96 h at -25ºc 16 h at -40ºc 96 h at -40ºc iec 60068-2-1/ansi c37.90-2005 (chapter 4) dry heat tests operation storage 16 h at +70ºc 96 h at +85ºc iec 60068-2-2/ansi c37.90-2005 (chapter 4) damp heat test...

  • Page 70

    Type tests according to standards table 19. Electromagnetic compatibility tests description type test value reference 100 khz and 1 mhz burst disturbance test iec 61000-4-18, level 3 iec 60255-22-1 ansi c37.90.1-2002 • common mode 2.5 kv • differential mode 2.5 kv electrostatic discharge test iec 61...

  • Page 71

    Table 19. Electromagnetic compatibility tests, continued description type test value reference voltage dips and short interruptionsc on dc power supply dips: 40%/200 ms 70%/500 ms interruptions: 0-50 ms: no restart 0...∞ s : correct behaviour at power down iec 60255-11 iec 61000-4-11 voltage dips an...

  • Page 72

    Table 20. Insulation tests description type test value reference dielectric tests: iec 60255-5 ansi c37.90-2005 • test voltage 2 kv, 50 hz, 1 min 1 kv, 50 hz, 1 min, communication impulse voltage test: iec 60255-5 ansi c37.90-2005 • test voltage 5 kv, unipolar impulses, waveform 1.2/50 μs, source en...

  • Page 73

    Emc compliance table 23. Emc compliance description reference emc directive 2004/108/ec standard en 50263 (2000) en 60255-26 (2007) current protection table 24. Instantaneous phase overcurrent protection, 3-phase output phpioc (50) function range or value accuracy operate current (5-2500)% of lbase ...

  • Page 74

    Table 25. Four step phase overcurrent protection, 3-phase output oc4ptoc (51/67) function setting range accuracy operate current (5-2500)% of lbase ± 1.0% of i n at i ≤ i n ± 1.0% of i at i > i n reset ratio > 95% - min. Operating current (1-10000)% of lbase ± 1.0% of i n at i ≤ i n ± 1.0% of i at i...

  • Page 75

    Table 26. Instantaneous residual overcurrent protection efpioc (50n) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - operate time 20 ms typically at 0 to 2 x i set - reset time 30 ms typically at 2 to 0 x i set -...

  • Page 76

    Table 27. Four step residual overcurrent protection ef4ptoc (51n/67n) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i n ± 1.0% of i at i > i n reset ratio > 95% - operate current for directional comparison, zero sequence (1–100)% of lbase ± 2.0% of i n operate ...

  • Page 77

    Table 28. Sensitive directional residual overcurrent and power protection sdepsde (67n) function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of lbase at low setting: (2.5-10) ma (10-50) ma ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n ± 0.5 ...

  • Page 78

    Table 28. Sensitive directional residual overcurrent and power protection sdepsde (67n) , continued function range or value accuracy reset time, non-directional residual over current 90 ms typically at 1.2 to 0.5 x i set - operate time, non-directional residual overvoltage 70 ms typically at 0.8 to ...

  • Page 79

    Table 30. Breaker failure protection, 3-phase activation and output ccrbrf (50bf) function range or value accuracy operate phase current (5-200)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ± 1.0% of i n at i ...

  • Page 80

    Table 33. Broken conductor check brcptoc (46) function range or value accuracy minimum phase current for operation (5–100)% of ibase ± 1.0% of i n unbalance current operation (50-90)% of maximum current ± 2.0% of i n timer (0.00-60.000) s ± 0.5% ± 25 ms trip time for pickup function 35 ms typically ...

  • Page 81

    Table 35. Negative sequence based overcurrent function dnsptoc (46) function range or value accuracy operate current (2.0 - 5000.0) % of ibase ± 1.0% of i r at i n ± 1.0% of i at i > i n reset ratio > 95 % - low voltage level for memory (0.0 - 5.0) % of vbase n relay characteristic angle (-180 - 180...

  • Page 82

    Voltage protection table 36. Two step undervoltage protection uv2ptuv (27) function range or value accuracy operate voltage, low and high step (1–100)% of vbase ± 0.5% of v n reset ratio - inverse time characteristics for low and high step, see table 74 - see table 74 definite time delay, step 1 (0....

  • Page 83

    Table 38. Two step residual overvoltage protection rov2ptov (59n) function range or value accuracy operate voltage, step 1 (1-200)% of vbase ± 0.5% of v n at v n ± 0.5% of v at v > v n operate voltage, step 2 (1–100)% of vbase ± 0.5% of v n at v n ± 0.5% of v at v > v n reset ratio >95% - inverse ti...

  • Page 84

    Frequency protection table 40. Under frequency protection saptuf (81) function range or value accuracy operate value, pickup function (35.00-75.00) hz ± 2.0 mhz operate value, restore frequency (45 - 65) hz ± 2.0 mhz reset ratio - operate time, pickup function at 50 hz: 200 ms typically at f set +0....

  • Page 85

    Secondary system supervision table 43. Current circuit supervision ccsrdif (87) function range or value accuracy operate current (5-200)% of i n ± 10.0% of i n at i £ i n ± 10.0% of i at i > i n block current (5-500)% of i n ± 5.0% of i n at i £ i n ± 5.0% of i at i > i n table 44. Fuse failure supe...

  • Page 86

    Control table 46. Synchronizing, synchronism check and energizing check sesrsyn (25) function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage ratio, v bus /v line 0.500 - 2.000 - reset ratio, synchronism check > 95% - frequency difference limit between bus and lin...

  • Page 87

    Table 47. Autorecloser for 3-phase operation smbrrec (79) function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 3ph (0.000-60.000) s ± 0.5% ± 25 ms shot 2 - t2 3ph shot 3 - t3 3ph shot 4 - t4 3ph shot 5 - t5 3ph (0.00-6000.00) s autorecloser maxi...

  • Page 88

    Table 49. Configurable logic blocks logic block quantity with cycle time range or value accuracy 5 ms 20 ms 100 ms and 60 60 160 - - or 60 60 160 - - xor 10 10 20 - - inverter 30 30 80 - - srmemory 10 10 20 - - rsmemory 10 10 20 - - gate 10 10 20 - - pulsetimer 10 10 20 (0.000–90000.000) s ± 0.5% ± ...

  • Page 89

    Monitoring table 51. Technical datacovering measurement functions:cvmmxn, cmmxu, vmmxu, cmsqi, vmsqi, vnmmxu function range or value accuracy voltage (0.1-1.5) ×v n ± 0.5% of v n at v£v n ± 0.5% of v at v > v n connected current (0.2-4.0) × i n ± 0.5% of i n at i £ i n ± 0.5% of i at i > i n active ...

  • Page 90

    Table 53. Disturbance report drprdre function range or value accuracy current recording - ± 1,0% of i r at i ≤ i r ± 1,0% of i at i > ir voltage recording - ± 1,0% of v n at v≤ v n ± 1,0% of vat v> v n pre-fault time (0.05–3.00) s - post-fault time (0.1–10.0) s - limit time (0.5–8.0) s - maximum num...

  • Page 91

    Table 55. Event list drprdre function value buffer capacity maximum number of events in the list 1000 resolution 1 ms accuracy depending on time synchronizing table 56. Indications drprdre function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number...

  • Page 92

    Table 60. Station battery supervision spvnzbat function range or value accuracy lower limit for the battery terminal voltage (60-140) % of vbat ± 1.0% of set battery voltage reset ratio, lower limit - upper limit for the battery terminal voltage (60-140) % of vbat ± 1.0% of set battery voltage reset...

  • Page 93

    Metering table 64. Pulse counter pcggio function setting range accuracy cycle time for report of counter value (1–3600) s - table 65. Function for energy calculation and demand handling etpmmtr function range or value accuracy energy metering mwh export/import, mvarh export/import input from mmxu. N...

  • Page 94

    Station communication table 66. Communication protocol function value protocol tcp/ip ethernet communication speed for the ieds 100 mbit/s protocol iec 61850–8–1 communication speed for the ieds 100base-fx protocol dnp3.0/tcp communication speed for the ieds 100base-fx protocol, serial iec 60870–5–1...

  • Page 95

    Inverse time characteristics table 70. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) = + × - æ ö ç ÷ ç ÷ è ø 1 p a t b td i equation1651 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 - ansi extremely inverse a=28.2, b=0.1217, p=2.0 an...

  • Page 96

    Table 72. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic = × - 1 0.236 0.339 t td i equation1656 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 rd type logarithmic inverse characteristic = - × æ ö ç ÷ è ø 5.8 1.35 t i in td e...

  • Page 97

    Table 74. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø td t vpickup v vpickup equation1658 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 ±5% +60 ms type b curve: × = + - × - æ ö ç ÷ è ø 2.0 480 0.055 32 0.5 td t vpic...

  • Page 98

    19. Ordering for customized ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Product specification b...

  • Page 99

    Current protection instantaneous phase overcurrent protection, 3–phase output (phpioc, 50) qty: 1mrk 004 908-aa four step phase overcurrent protection, 3–phase output (oc4ptoc, 51/67) qty: 1mrk 004 908-bb instantaneous residual overcurrent protection (efpioc, 50n) qty: 1mrk 004 908-ca four step resi...

  • Page 100

    Secondary system supervision current circuit supervision (ccsrdif, 87) qty: 1mrk 004 914-aa fuse failure supervision (sddrfuf) qty: 1mrk 004 914-ba control synchrocheck, energizing check and synchronizing (sesrsyn, 25) qty: 1mrk 004 917-ac autorecloser for 3–phase operation (smbrrec, 79) qty: 1mrk 0...

  • Page 101

    Analog system rule: one transformer input module must be ordered transformer module (trm) 6i+4u, 1/5a,100/220v qty: 1khl178083r0001 transformer module (trm) 8i+2u, 1/5a, 100/220v qty: 1khl178083r0013 transformer module (trm) 4i, 1/5a+1i, 0.1/0.5a+5u, 100/220v qty: 1khl178083r0016 transformer module ...

  • Page 102

    20. Ordering for configured ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the ...

  • Page 103

    Casing #5 notes and rules rack casing, 3u 1/1 x 19" d selection for position #5. D mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x rack mounting kit for 3u 1/1 x 19" h selection for position #6. Connection type for power supply, input/output and ...

  • Page 104

    Binary input/output module #10 notes and rules slot position (rear view) p3 p4 p5 p6 available slots in 1/1 case no board in slot x binary input/output module 9 bi, 3 no trip, 5 no signal, 1 co signal a a a a p6 optional for a01a p6 = a for a02a/a07a selection for position #10. A a a communication a...

  • Page 105

    21. Ordering for accessories configuration and monitoring tools front connection cable between lcd-hmi and pc quantity: 1mrk 001 665-ca led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect dvd cont...

  • Page 106

    Rule: specify the number of printed manuals requested operation manual ansi quantity: 1mrk 500 095-uus technical manual ansi quantity: 1mrk 511 263-uus commissioning manual ansi quantity: 1mrk 511 264-uus application manual ansi quantity: 1mrk 511 262-uus communication protocol manual, dnp3 ansi qua...

  • Page 107

    Related documents documents related to rec650 identity number application manual 1mrk 511 262-uus technical manual 1mrk 511 263-uus commissioning manual 1mrk 511 264-uus product guide 1mrk 511 265-bus type test certificate 1mrk 511 265-tus 650 series manuals identity number communication protocol ma...

  • Page 108

    108.

  • Page 109

    Contact us abb inc. 1021 main campus drive raleigh, nc 27606, usa phone toll free: 1-800-help-365, menu option #8 abb inc. 3450 harvester road burlington, on l7n 3w5, canada phone toll free: 1-800-help-365, menu option #8 abb mexico s.A. De c.V. Paseo de las americas no. 31 lomas verdes 3a secc. 531...