ABB RED670 Relion 670 series Product Manual

Manual is about: Line differential protection

Summary of RED670 Relion 670 series

  • Page 1

    Relion ® 670 series bay control rec670 pre-configured product guide.

  • Page 2

    Contents 1. Application.....................................................................3 2. Available functions..........................................................4 3. Differential protection......................................................9 4. Current protection........................

  • Page 3

    1. Application rec670 is used for the control, protection and monitoring of different types of bays in power networks. The ied is especially suitable for applications in control systems with distributed control ieds in all bays with high demands on reliability. The ied can be used up to the highest ...

  • Page 4

    2. Available functions main protection functions 2 = number of basic instances 3-a03 = optional function included in packages a03 (refer to ordering details) iec 61850 ansi function description bay control rec670 (a30) rec670 (b30) rec670 (c30) differential protection hzpdif 87 1ph high impedance di...

  • Page 5

    Back-up protection functions iec 61850 ansi function description bay control rec670 (a30) rec670 (b30) rec670 (c30) current protection phpioc 50 instantaneous phase overcurrent protection 1-c31 2-c32 2-c33 oc4ptoc 51_67 four step phase overcurrent protection 1-c31 2-c32 2-c33 efpioc 50n instantaneou...

  • Page 6

    Control and monitoring functions iec 61850 ansi function description bay control rec670 (a30) rec670 (b30) rec670 (c30) control sesrsyn 25 synchrocheck, energizing check and synchronizing 1 2 3 smbrrec 79 autorecloser 1-h04 2-h05 3-h06 apc8 3 apparatus control for single bay, max 8 apparatuses (1cb)...

  • Page 7

    Iec 61850 ansi function description bay control rec670 (a30) rec670 (b30) rec670 (c30) extension logic package fixedsignals fixed signal function block 1 1 1 b16i boolean 16 to integer conversion 16 16 16 b16ifcvi boolean 16 to integer conversion with logic node representation 16 16 16 ib16 integer ...

  • Page 8

    Designed to communicate iec 61850 ansi function description bay control rec670 (a30) rec670 (b30) rec670 (c30) station communication spa communication protocol 1 1 1 lon communication protocol 1 1 1 iec60870-5-103 communication protocol 20/1 20/1 20/1 operation selection between spa and iec60870-5-1...

  • Page 9

    Basic ied functions iec 61850 function description basic functions included in all products interrorsig self supervision with internal event list 1 time time and synchronization error 1 timesynch time synchronization 1 activegroup parameter setting groups 1 test test mode functionality 1 changelock ...

  • Page 10

    Four step phase overcurrent protection oc4ptoc the four step phase overcurrent protection function oc4ptoc has an inverse or definite time delay independent for step 1 and 4 separately. Step 2 and 3 are always definite time delayed. All iec and ansi inverse time characteristics are available togethe...

  • Page 11

    The three-phase current measuring protection has an i 2 t characteristic with settable time constant and a thermal memory.. An alarm level gives early warning to allow operators to take action well before the line is tripped. Thermal overload protection, two time constant trpttr if a power transform...

  • Page 12

    Two step residual overvoltage protection rov2ptov residual voltages may occur in the power system during earth faults. Two step residual overvoltage protection rov2ptov function calculates the residual voltage from the three-phase voltage input transformers or measures it from a single voltage input...

  • Page 13

    With the neutral point current on a separate input taken from another set of cores on the current transformer. A detection of a difference indicates a fault in the circuit and is used as alarm or to block protection functions expected to give unwanted tripping. Fuse failure supervision sddrfuf the a...

  • Page 14

    In normal security, the command is processed and the resulting position is not supervised. However with enhanced security, the command is processed and the resulting position is supervised. Normal security means that only the command is evaluated and the resulting position is not supervised. Enhance...

  • Page 15

    Single command, 16 signals the ieds can receive commands either from a substation automation system or from the local hmi. The command function block has outputs that can be used, for example, to control high voltage apparatuses or for other user defined functionality. 10. Scheme communication schem...

  • Page 16

    Trip matrix logic tmaggio trip matrix logic tmaggio function is used to route trip signals and other logical output signals to different output contacts on the ied. Tmaggio output signals and the physical outputs allows the user to adapt the signals to the physical tripping outputs according to the ...

  • Page 17

    A disturbance is defined as an activation of an input to the axradr or bxrbdr function blocks, which are set to trigger the disturbance recorder. All signals from start of pre-fault time to the end of post-fault time will be included in the recording. Every disturbance report recording is saved in t...

  • Page 18

    Signal to other systems or equipment in the substation. It can also be used inside the same ied, to attach a range aspect to an analog value and to permit measurement supervision on that value. Measured value expander block range_xp the current and voltage measurements functions (cvmmxn, cmmxu, vmmx...

  • Page 19

    16. Station communication overview each ied is provided with a communication interface, enabling it to connect to one or many substation level systems or equipment, either on the substation automation (sa) bus or substation monitoring (sm) bus. Following communication protocols are available: • iec ...

  • Page 20

    18. Hardware description hardware modules power supply module psm the power supply module is used to provide the correct internal voltages and full isolation between the terminal and the battery system. An internal fail alarm output is available. Binary input module bim the binary input module has 1...

  • Page 21

    Xx05000003.Vsd c b e f a d iec05000003 v1 en figure 2. 1/2 x 19” case with rear cover xx05000004.Vsd iec05000004 v1 en figure 3. Side-by-side mounting case size a b c d e f 6u, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7 6u, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0 6u, 1/1 x 19” 265.9 448.1 2...

  • Page 22

    19. Connection diagrams table 1. Designations for 1/2 x 19” casing with 1 trm slot 1mrk002801-ac-2-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x51 and x52 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs48...

  • Page 23

    Table 3. Designations for 3/4 x 19” casing with 2 trm slot 1mrk002801-ac-4-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x71 and x72 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, x32...

  • Page 24

    Table 5. Designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x131 and x132 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, ...

  • Page 25

    1mrk002801-ac-10-670-1.2-pg v1 en figure 4. Transformer input module (trm) ■ indicates high polarity ct/vt-input designation according to figure 4 current/voltage configuration (50/60 hz) ai01 ai02 ai03 ai04 ai05 ai06 ai07 ai08 ai09 ai10 ai11 ai12 12i, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 12i, 5a ...

  • Page 26

    1mrk002801-ac-11-670-1.2-pg v1 en figure 5. Binary input module (bim). Input contacts named xa corresponds to rear position x31, x41, and so on, and input contacts named xb to rear position x32, x42, and so on. 1mrk002801-ac-15-670-1.2-pg v1 en figure 6. Ma input module (mim) 1mrk002801-ac-8-670-1.2...

  • Page 27

    1mrk002801-ac-7-670-1.2-pg v1 en figure 8. Power supply module (psm) 1mrk002801-ac-12-670-1.2-pg v1 en figure 9. Binary output module (bom). Output contacts named xa corresponds to rear position x31, x41, and so on, and output contacts named xb to rear position x32, x42, and so on. Bay control rec67...

  • Page 28

    1mrk002801-ac-13-670-1.2-pg v1 en figure 10. Static output module (som) 1mrk002801-ac-14-670-1.2-pg v1 en figure 11. Binary in/out module (iom). Input contacts named xa corresponds to rear position x31, x41, and so on, and output contacts named xb to rear position x32, x42, and so on. Bay control re...

  • Page 29

    20. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 30

    Table 7. Trm - energizing quantities, rated values and limits for measuring transformer modules quantity rated value nominal range current i r = 1 or 5 a (0-1.8) × i r at i r = 1 a (0-1.6) × i r at i r = 5 a permissive overload 1.1 × i r cont. 1.8 × i r for 30 min at i r = 1 a 1.6 × i r for 30 min a...

  • Page 31

    Binary inputs and outputs table 11. Bim - binary input module quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50ma 48/60 v, 50ma 110/125 v, 50ma 220/250 v, 50ma 220/250 v, 110ma ma...

  • Page 32

    Table 13. Iom - binary input/output module quantity rated value nominal range binary inputs 8 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v, 50 ma 48/60 v, 50 ma 110/125 v, 50 ma 220/250 v, 50 ma 220/250 v, 110 ma max. 0.05 w/input...

  • Page 33

    Table 15. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 250 v r...

  • Page 34

    Table 17. Som - static output module data (reference standard: iec 61810-2): electromechanical relay outputs function of quantity trip and signal relays max system voltage 250v ac/dc number of outputs 6 test voltage across open contact, 1 min 1000v rms current carrying capacity: continuous 8a 1.0s 1...

  • Page 35

    Table 20. Auxiliary dc supply voltage influence on functionality during operation dependence on reference value within nominal range influence ripple, in dc auxiliary voltage operative range max. 2% full wave rectified 15% of el 0.01% /% auxiliary voltage dependence, operate value ± 20% of el 0.01% ...

  • Page 36

    Type tests according to standards table 22. Electromagnetic compatibility test type test values reference standards 1 mhz burst disturbance 2.5 kv iec 60255-22-1 100 khz slow damped oscillatory wave immunity test 2.5 kv iec 61000-4-18, class iii ring wave immunity test, 100 khz 2-4 kv iec 61000-4-12...

  • Page 37

    Table 24. Environmental tests test type test value reference standard cold test test ad for 16 h at -25°c iec 60068-2-1 storage test test ad for 16 h at -40°c iec 60068-2-1 dry heat test test bd for 16 h at +70°c iec 60068-2-2 damp heat test, steady state test ca for 4 days at +40 °c and humidity 93...

  • Page 38

    Differential protection table 27. 1ph high impedance differential protection hzpdif function range or value accuracy operate voltage (20-400) v i=u/r ± 1.0% of i r reset ratio >95% - maximum continuous power u>trip 2 /seriesresistor ≤200 w - operate time 10 ms typically at 0 to 10 x u d - reset time...

  • Page 39

    Current protection table 28. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 25 ms typically at 0 to 2 x i set - reset time 25 ms typically at 2 to 0...

  • Page 40

    Table 30. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - operate time 25 ms typically at 0 to 2 x i set - reset time 25 ms typically at 2 to 0 x i set - criti...

  • Page 41

    Table 32. Four step negative sequence overcurrent protection ns4ptoc function range or value accuracy operate value, negative sequence current, step 1-4 (1-2500)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio > 95% - timers (0.000-60.000) s ± 0.5% ± 10 ms inverse characteristi...

  • Page 42

    Table 33. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r at low setting: (0.25-1.00)% of i r : ±0.05% of i ...

  • Page 43

    Table 33. Sensitive directional residual overcurrent and power protection sdepsde, continued function range or value accuracy reset time, non-directional residual over current 60 ms typically at 2 to 0 x i set - operate time, start function 150 ms typically at 0 to 2 x i set - reset time, start func...

  • Page 44

    Table 36. Breaker failure protection ccrbrf function range or value accuracy operate phase current (5-200)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ± 1.0% of i r at i £ i r ± 1.0% of i at i > i r reset rat...

  • Page 45

    Table 40. Broken conductor check brcptoc function range or value accuracy minimum phase current for operation (5–100)% of ibase ± 0.1% of i r unbalance current operation (0–100)% of maximum current ± 0.1% of i r timer (0.00-6000.00) s ± 0.5% ± 10 ms bay control rec670 1mrk511232-ben e pre-configured...

  • Page 46

    Voltage protection table 41. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1–100)% of ubase ± 0.5% of u r absolute hysteresis (0–100)% of ubase ± 0.5% of u r internal blocking level, step 1 and step 2 (1–100)% of ubase ± 0.5% of u r inv...

  • Page 47

    Table 43. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 and step 2 (1-200)% of ubase ± 0.5% of u r at u r ± 1.0% of u at u > u r absolute hysteresis (0–100)% of ubase ± 0.5% of u r at u r ± 1.0% of u at u > u r inverse time characteristics...

  • Page 48

    Frequency protection table 46. Underfrequency protection saptuf function range or value accuracy operate value, start function (35.00-75.00) hz ± 2.0 mhz operate time, start function 100 ms typically - reset time, start function 100 ms typically - operate time, definite time function (0.000-60.000)s...

  • Page 49

    Multipurpose protection table 49. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, negseq, 3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2- phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph-ph - ba...

  • Page 50

    Table 49. General current and voltage protection cvgapc , continued function range or value accuracy relay characteristic angle (-180 to +180) degrees ± 2.0 degrees relay operate angle (1 to 90) degrees ± 2.0 degrees reset ratio, overcurrent > 95% - reset ratio, undercurrent - reset ratio, overvolta...

  • Page 51

    Secondary system supervision table 50. Current circuit supervision ccsrdif function range or value accuracy operate current (5-200)% of i r ± 10.0% of i r at i £ i r ± 10.0% of i at i > i r block current (5-500)% of i r ± 5.0% of i r at i £ i r ± 5.0% of i at i > i r table 51. Fuse failure supervisi...

  • Page 52

    Control table 52. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage ratio, u bus /u line 0.500 - 2.000 - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubasebus and ubaseline ±...

  • Page 53

    Table 53. Autorecloser smbrrec function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 1ph shot 1 - t1 2ph shot 1 - t1 3phhs shot 1 - t1 3phdld (0.000-60.000) s ± 0.5% ± 10 ms shot 2 - t2 shot 3 - t3 shot 4 - t4 shot 5 - t5 (0.00-6000.00) s extende...

  • Page 54

    Table 54. Voltage control tr1atcc, tr8atcc, tcmyltc and tlcyltc function range or value accuracy transformer reactance (0.1–200.0)Ω, primary - time delay for lower command when fast step down mode is activated (1.0–100.0) s - voltage control set voltage (85.0–120.0)% of ub ±0.25% of u r outer voltag...

  • Page 55

    Scheme communication table 55. Scheme communication logic for distance or overcurrent protection zcpsch function range or value accuracy scheme type intertrip permissive underreach permissive overreach blocking - co-ordination time for blocking communication scheme (0.000-60.000) s ± 0.5% ± 10 ms mi...

  • Page 56

    Table 58. Current reversal and weak-end infeed logic for residual overcurrent protection ecrwpsch function range or value accuracy operating mode of wei logic off echo echo & trip - operate voltage 3u o for wei trip (5-70)% of ubase ± 0.5% of u r reset ratio >95% - operate time for current reversal ...

  • Page 57

    Logic table 59. Tripping logic smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms timers (0.000-60.000) s ± 0.5% ± 10 ms table 60. Configurable logic blocks logic block quantity with cycle time range or value accura...

  • Page 58

    Table 61. Extension logic package logic block quantity with cycle time range or value accuracy fast medium normal logicand 40 40 100 - - logicxor - - 49 - - logicsrmemory - - 110 - - logictimer 5 5 49 (0.000–90000.000) s ± 0.5% ± 10 ms logicpulsetimer 5 5 49 (0.000–90000.000) s ± 0.5% ± 10 ms trip m...

  • Page 59

    Monitoring table 62. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) × f r ± 2.0 mhz voltage (0.1-1.5) ×u r ± 0.5% of u r at u £ u r ± 0.5% of u at u > u r connected current (0.2-4.0) × i r ± 0.5% of i r at i £ i r ± 0.5% of i at i > i r active power, p 0.1 x u r r 0.2 x i...

  • Page 60

    Table 66. Current sequence component measurement cmsqi function range or value accuracy current positive sequence, i1 three phase settings (0.1–4.0) × i r ± 0.2% of i r at i ≤ 0.5 × i r ± 0.2% of i at i > 0.5 × i r current zero sequence, 3i0 three phase settings (0.1–1.0) × i r ± 0.2% of i r at i ≤ ...

  • Page 61

    Table 70. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 94 maximum number of analog inputs 30 + 10 (ex...

  • Page 62

    Table 74. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance reports 100 resolution 1 ms accuracy depending on time synchronizing table 75. Trip value recorder function value buffer capacity maximum number of analog inputs 3...

  • Page 63

    Metering table 77. Pulse counter pcggio function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 78. Energy metering etpmmtr function range or value accuracy energy metering kwh export/import, kvarh export/ import input...

  • Page 64

    Station communication table 79. Iec 61850-8-1 communication protocol function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 608–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/i...

  • Page 65

    Table 84. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fibre: type st plastic fibre: type hfbr snap-in fibre, optical budget glass fibre: 11 db (3000ft/1000 m typically *) plastic fibre: 7 db (80ft/25 m typically *) fibre diameter glass fibre: 62.5/125 m m plas...

  • Page 66

    Remote communication table 87. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fibre graded-index multimode 62.5/125 µm or 50/125 µm singlemode 9/125 µm singlemode 9/125 µm wave length 850 nm 1310 nm 1550 nm optical...

  • Page 67

    Hardware ied table 88. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 89. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom ip2...

  • Page 68

    Basic ied functions table 93. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 94. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms tim...

  • Page 69

    Table 97. Irig-b quantity rated value number of channels irig-b 1 number of channels pps 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x accuracy...

  • Page 70

    Inverse characteristic table 98. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = + × - æ ö ç ÷ ç ÷ è ø p a t b k i equation1249-small v1 en reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en i = i measured /i set k = (0.05-999) ...

  • Page 71

    Table 99. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set k = (0.05-999) in steps of 0.01 - time delay to reset, iec inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ...

  • Page 72

    Table 101. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: 2.0 480 32 0.5 0.035 = × - > × - - > æ ö ç ÷ è ø...

  • Page 73

    Table 102. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = uv measured k = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: 2.0 480 0.055 32 0.5 × = + × - æ ö ç ÷ è ø k t u u u equa...

  • Page 74

    Table 103. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: 2.0 480 32 0.5 0.035 = × - > × - - > æ ...

  • Page 75

    21. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configur...

  • Page 76

    Software options #3 notes and rules no option x 00 all fields in the ordering form do not need to be filled in high impedance differential protections a 02 note: a02 only in a30/b30, a07 only in c30 high impedance differential protections - 2 zones a 07 sensitive directional residual overcurrent and...

  • Page 77

    Casing #5 notes and rules 1/2 x 19" case a 3/4 x 19" case 1 trm slot b 3/4 x 19" case 2 trm slots c 1/1 x 19" case 1trm slots d 1/1 x 19" case 2 trm slots e selection for position #5. Mounting details with ip40 of protection from the front #6 notes and rules no mounting kit included x 19" rack mount...

  • Page 78

    Binary input/output module, ma and time synchronizating boards. Note: 1bim and 1 bom included. #10 notes and rules make bim with 50 ma inrush current the primary choice. Bim with 50 ma inrush current fulfill additional standards. As a consequence the emc withstand capability is further increased. Bi...

  • Page 79

    Remote end communication, dnp serial comm. And time synchronization modules #11 notes and rules slot position (rear view) x312 x313 x302 x303 x322 x323 available slots in 1/2 case with 1 trm █ █ █ █ note: max 1 ldcm in 1/2 case available slots in 3/4 & 1/1 case with 1 trm █ █ █ █ note: max 2 ldcm in...

  • Page 80

    Test switch the test system combitest intended for use with the ied 670 products is described in 1mrk 512 001-ben and 1mrk 001024-ca. Please refer to the website: www.Abb.Com/substationautomation for detailed information. Due to the high flexibility of our product and the wide variety of application...

  • Page 81

    Configuration and monitoring tools front connection cable between lcd-hmi and pc quantity: 1mrk 001 665-ca led label special paper a4, 1 pc quantity: 1mrk 002 038-ca led label special paper letter, 1 pc quantity: 1mrk 002 038-da manuals note: one (1) ied connect cd containing user documentation (ope...

  • Page 82

    Reference information for our reference and statistics we would be pleased to be provided with the following application data: country: end user: station name: voltage level: kv related documents documents related to rec670 identity number operator’s manual 1mrk 511 228-uen installation and commissi...

  • Page 83

    83.

  • Page 84

    Contact us abb ab substation automation products se-721 59 västerås, sweden phone +46 (0) 21 32 50 00 fax +46 (0) 21 14 69 18 www.Abb.Com/substationautomation 1mrk511232-ben e © copyright 2012 abb. All rights reserved..