ABB RED670 Relion 670 series Product Manual

Manual is about: Line differential protection

Summary of RED670 Relion 670 series

  • Page 1

    Relion ® 670 series line differential protection red670 ansi customized product guide.

  • Page 2

    Contents 1. Application.........................................................................3 2. Available functions.............................................................4 3. Differential protection.........................................................9 4. Impedance protection............

  • Page 3

    1. Application red670 is used for the protection, control and monitoring of overhead lines and cables in all types of networks. The ied can be used from distribution up to the highest voltage levels. It is suitable for the protection of heavily loaded lines and multi- terminal lines where the requir...

  • Page 4

    2. Available functions main protection functions 2 = number of basic instances 0-3 = option quantities iec 61850 ansi function description line differential red670 differential protection hzpdif 87 1ph high impedance differential protection 0-3 l3cpdif 87l line differential protection, 3 ct sets, 2-...

  • Page 5

    Back-up protection functions iec 61850 ansi function description line differential red670 current protection phpioc 50 instantaneous phase overcurrent protection 0-3 oc4ptoc 51_67 four step phase overcurrent protection 0-1 efpioc 50n instantaneous residual overcurrent protection 0-1 ef4ptoc 51n_67 n...

  • Page 6

    Control and monitoring functions iec 61850 ansi function description line differential red670 control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-2 smbrrec 79 autorecloser 0-4 apc15 3 apparatus control for single bay, max 15 apparatuses (2cbs) incl. Interlocking 0-1 qcbay apparatus...

  • Page 7

    Iec 61850 ansi function description line differential red670 sp16ggio iec61850 generic communication i/o functions 16 inputs 16 mvggio iec61850 generic communication i/o functions 24 bsstatreport logical signal status report 3 range_xp measured value expander block 66 lmbrflo fault locator 1 meterin...

  • Page 8

    Designed to communicate iec 61850 ansi function description line differential red670 station communication spa communication protocol 1 lon communication protocol 1 iec60870-5-103 communication protocol 20/1 operation selection between spa and iec60870-5-103 for slm 1 dnp3.0 for tcp/ip and eia-485 c...

  • Page 9

    Basic ied functions iec 61850 function description basic functions included in all products interrorsig self supervision with internal event list 1 time time and synchronization error 1 timesynch time synchronization 1 activegroup parameter setting groups 1 test test mode functionality 1 changelock ...

  • Page 10

    Line differential protection, 3 or 6 ct sets l3cpdif, l6cpdif (87l) line differential protection applies the kirchhoff's law and compares the currents entering and leaving the protected multi- terminal circuit, consisting of overhead power lines, power transformers and cables. It offers phase-segreg...

  • Page 11

    Ied ied ied communication channel communication channel communication channel protected zone ansi05000040_2_en.Vsd ansi05000040 v2 en figure 2. Example of application on a three-terminal line with breaker-and-a-half breaker arrangements the current differential algorithm provides high sensitivity fo...

  • Page 12

    Line differential protection 3 or 6 ct sets, with in-zone transformers lt3cpdif, lt6cpdif (87lt) two two-winding power transformers, or one three-winding power transformer, can be included in the line differential protection zone. Both two- and three-winding transformers are correctly represented wi...

  • Page 13

    Protected zone communication channel ied ied ied ied ansi05000043_2_en.Vsd ied ansi05000043 v2 en figure 4. Five terminal lines with master-master system line differential protection red670 ansi 1mrk505226-bus d customized product version: 1.2 abb 13.

  • Page 14

    Protected zone communication channels red 670 red 670 red 670 red 670 red 670 en05000044_ansi.Vsd ansi05000044 v1 en figure 5. Five terminal line with master-slave system current samples from ieds located geographically apart from each other, must be time coordinated so that the current differential...

  • Page 15

    The differential function can be allowed to trip as no load is fed through the line and protection is not working correctly. Features: • startup element is sensitive enough to detect the abnormal status of the protected system • startup element does not influence the operation speed of main protecti...

  • Page 16

    En05000034.Vsd r x forward operation reverse operation iec05000034 v1 en figure 7. Typical quadrilateral distance protection zone with load encroachment function activated the independent measurement of impedance for each fault loop together with a sensitive and reliable built in phase selection mak...

  • Page 17

    En07000117.Vsd jx operation area operation area r operation area no operation area no operation area iec07000117 v1 en figure 8. Load encroachment influence on the offset mho characteristic the distance protection zones can operate, independent of each other, in directional (forward or reverse) or n...

  • Page 18

    En05000034.Vsd r x forward operation reverse operation iec05000034 v1 en figure 9. Typical quadrilateral distance protection zone with phase selection, quadrilateral characteristic with settable angle function frpspdis (21) activated the independent measurement of impedance for each fault loop toget...

  • Page 19

    5. Current protection instantaneous phase overcurrent protection phpioc (50) the instantaneous three phase overcurrent function has a low transient overreach and short tripping time to allow use as a high set short-circuit protection function. Four step phase overcurrent protection oc4ptoc (51/67) t...

  • Page 20

    Thermal overload protection, one time constant lpttr the increasing utilizing of the power system closer to the thermal limits has generated a need of a thermal overload protection also for power lines. A thermal overload will often not be detected by other protection functions and the introduction ...

  • Page 21

    Two step overvoltage protection (ov2ptov, 59) function can be used to detect open line ends, normally then combined with a directional reactive over-power function to supervise the system voltage. When triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks. Ov...

  • Page 22

    Cvgapc can also be used to improve phase selection for high resistive ground faults, outside the distance protection reach, for the transmission line. Three functions are used, which measures the neutral current and each of the three phase voltages. This will give an independence from load currents ...

  • Page 23

    Close first and the second will only close if the fault proved to be transient. Each autoreclosing function is configured to co-operate with the synchronism check function. Apparatus control apc the apparatus control functions are used for control and supervision of circuit breakers, disconnectors a...

  • Page 24

    Automationbits, command function for dnp3.0 autobits automationbits function for dnp3 (autobits) is used within pcm600 to get into the configuration of the commands coming through the dnp3 protocol. The autobits function plays the same role as functions goosebinrcv (for iec 61850) and multicmdrcv (f...

  • Page 25

    The logic can be controlled either by the autorecloser (zone extension) or by the loss-of-load current (loss-of-load acceleration). Scheme communication logic for residual overcurrent protection ecpsch (85) to achieve fast fault clearance of ground faults on the part of the line not covered by the i...

  • Page 26

    Features: • carrier redundancy to ensure security in dtt scheme • blocking function output on cr channel error • phase wise trip outputs negative sequence overvoltage protection lcnsptov (47) negative sequence components are present in all types of fault condition. Negative sequence voltage and curr...

  • Page 27

    An ied, either for forcing the unused inputs in other function blocks to a certain level/value, or for creating certain logic. 13. Monitoring measurements cvmmxn, cmmxu, vnmmxu, vmmxu, cmsqi, vmsqi the measurement functions are used to get on-line information from the ied. These service values make ...

  • Page 28

    The event recorder logs all selected binary input signals connected to the disturbance report function. Each recording can contain up to 150 time-tagged events. The event recorder information is available for the disturbances locally in the ied. The event recording information is an integrated part ...

  • Page 29

    35-40 degrees apart the accuracy can be still maintained with the advanced compensation included in fault locator. 14. Metering pulse counter logic pcggio pulse counter (pcggio) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculat...

  • Page 30

    Serial communication, lon existing stations with abb station bus lon can be extended with use of the optical lon interface. This allows full sa functionality including peer-to-peer messaging and cooperation between existing abb ied's and the new ied 670. Spa communication protocol a single glass or ...

  • Page 31

    Enables extensive monitoring and evaluation of operation of the ied and for all associated electrical circuits. Binary output module bom the binary output module has 24 independent output relays and is used for trip output or any signaling purpose. Static binary output module som the static binary o...

  • Page 32

    Xx05000003.Vsd c b e f a d iec05000003 v1 en figure 11. 1/2 x 19” case with rear cover xx05000004.Vsd iec05000004 v1 en figure 12. Side-by-side mounting case size a b c d e f 6u, 1/2 x 19” 10.47 8.81 7.92 9.53 9.96 8.10 6u, 3/4 x 19” 10.47 13.23 7.92 9.53 9.96 12.52 6u, 1/1 x 19” 10.47 17.65 7.92 9....

  • Page 33

    • wall mounting kit see ordering for details about available mounting alternatives. Line differential protection red670 ansi 1mrk505226-bus d customized product version: 1.2 abb 33.

  • Page 34

    20. Connection diagrams table 1. Designations for 1/2 x 19” casing with 1 trm slot 1mrk002801-ac-2-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x51 and x52 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs48...

  • Page 35

    Table 2. Designations for 3/4 x 19” casing with 1 trm slot 1mrk002801-ac-3-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x101 and x102 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313 tr...

  • Page 36

    Table 3. Designations for 3/4 x 19” casing with 2 trm slot 1mrk002801-ac-4-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x71 and x72 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, x32...

  • Page 37

    Table 4. Designations for 1/1 x 19” casing with 1 trm slot 1mrk002801-ac-5-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x161 and x162 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm,rs485 or gtm x312, x313 trm...

  • Page 38

    Table 5. Designations for 1/1 x 19” casing with 2 trm slots 1mrk002801-ac-6-670-1.2-pg v1 en module rear positions psm x11 bim, bom, som, iom or mim x31 and x32 etc. To x131 and x132 slm x301:a, b, c, d ldcm, irig-b or rs485 x302 ldcm or rs485 x303 oem x311:a, b, c, d ldcm, rs485 or gtm x312, x313, ...

  • Page 39

    Table 6. Ct/vt-input designation current/voltage configuration (50/60 hz) ai01 ai02 ai03 ai04 ai05 ai06 ai07 ai08 ai09 ai10 ai11 ai12 12i, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 12i, 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 5a 9i+3v, 1a 1a 1a 1a 1a 1a 1a 1a 1a 1a 110-220v 110-220v 110-220v 9i+3v, 5a 5a 5...

  • Page 40

    1mrk002802-ab-11-670-1.2-pg-ansi v1 en figure 15. Binary input module (bim). Input contacts named xa corresponds to rear position x31, x41, etc. And input contacts named xb to rear position x32, x42, etc. 1mrk002802-ab-12-670-1.2-pg-ansi v1 en figure 16. Binary output module (bom). Output contacts n...

  • Page 41

    1mrk002802-ab-8-670-1.2-pg-ansi v1 en figure 20. Ied with basic functionality communication interfaces line differential protection red670 ansi 1mrk505226-bus d customized product version: 1.2 abb 41.

  • Page 42

    21. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...

  • Page 43

    Table 8. Trm - energizing quantities, rated values and limits for measuring transformer modules quantity rated value nominal range current i n = 1 or 5 a (0-1.8) × i n at i n = 1 a (0-1.6) × i n at i n = 5 a permissive overload 1.1 × i n cont. 1.8 × i n for 30 min at i n = 1 a 1.6 × i n for 30 min a...

  • Page 44

    Auxiliary dc voltage table 11. Psm - power supply module quantity rated value nominal range auxiliary dc voltage, el (input) el = (24 - 60) v el = (90 - 250) v el ± 20% el ± 20% power consumption 50 w typically - auxiliary dc power in-rush - binary inputs and outputs table 12. Bim - binary input mod...

  • Page 45

    Table 13. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v 48/60 v 125 v 220/250 v max. 0.05 w/input max. 0.1 w/input ...

  • Page 46

    Table 15. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs 10 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 1000 v rms 800 v dc curr...

  • Page 47

    Table 16. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 250 v r...

  • Page 48

    Table 17. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48 - 60 vdc 110 - 250 vdc number of outputs 6 6 impedance open state ~300 kΩ ~810 kΩ test voltage across open contact, 1 min no galvanic separati...

  • Page 49

    Table 19. Bom - binary output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays binary outputs 24 max system voltage 250 v ac, dc test voltage across open contact, 1 min 1000 v rms current carrying capacity per relay, continuous per relay, 1 s per proc...

  • Page 50

    Table 22. Frequency influence (reference standard: iec 60255–1) dependence on within nominal range influence frequency dependence, operate value f n ± 2.5 hz for 50 hz f n ± 3.0 hz for 60 hz ± 1.0% / hz frequency dependence for distance protection operate value f n ± 2.5 hz for 50 hz f n ± 3.0 hz fo...

  • Page 51

    Table 24. Insulation test type test values reference standard dielectric test 2.0 kv ac, 1 min. Ansi c37.90 impulse voltage test 5 kv, 1.2/50 ms, 0.5 j insulation resistance >100 mw at 500 vdc table 25. Environmental tests test type test value reference standard cold test test ad for 16 h at -25°c i...

  • Page 52

    Differential protection table 28. 1ph high impedance differential protection hzpdif (87) function range or value accuracy operate voltage (20-400) v i=v/r ± 1.0% of i n reset ratio >95% - maximum continuous power v>pickup 2 /seriesresistor ≤200 w - operate time 10 ms typically at 0 to 10 x v d - res...

  • Page 53

    Table 30. Additional security logic for differential protection stsggio (11) function range or value accuracy operate current, zero sequence (1-100)% of lbase ±1,0% of i n operate current, low operation (1-100)% of lbase ±1,0% of i n operate voltage, phase to neutral (1-100)% of vbase ± 0,5% of v n ...

  • Page 54

    Impedance protection table 31. Distance measuring zone, quad zmqpdis (21) function range or value accuracy number of zones 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, phase- to-phase and phase-to-ground (10-1000)% of ibase - po...

  • Page 55

    Table 32. Distance measuring zone, quadrilateral characteristic for series compensated lines zmcpdis, zmcapdis (21) function range or value accuracy number of zones 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, phase- phase and p...

  • Page 56

    Table 34. Full-scheme distance protection, mho characteristic zmhpdis (21) function range or value accuracy number of zones with selectable directions 5 with selectable direction - minimum operate current (10–30)% of i base - positive sequence impedance, phase-to-ground loop (0.005–3000.000) w/phase...

  • Page 57

    Table 36. Distance measuring zone, quadrilateral characteristic, separate settings zmrpdis, zmrapdis (21) function range or value accuracy number of zones 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, phase- to-phase and phase-to...

  • Page 58

    Table 37. Phase selection with load encroachment, quadrilateral characteristic frpspdis (21) function range or value accuracy minimum operate current (5-500)% of ibase - reactive reach, positive sequence (0.50–3000.00) Ω/phase ± 2.0% static accuracy ± 2.0 degrees static angular accuracy conditions: ...

  • Page 59

    Table 40. Phase preference logic pplphiz function range or value accuracy operate value, phase-to-phase and phase-to-neutral undervoltage (10.0 - 100.0)% of vbase ± 0,5% of v n reset ratio, undervoltage - operate value, residual voltage (5.0 - 70.0)% of vbase ± 0,5% of v n reset ratio, residual volt...

  • Page 60

    Current protection table 42. Instantaneous phase overcurrent protection phpioc (50) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - operate time 25 ms typically at 0 to 2 x i set - reset time 25 ms typically at 2...

  • Page 61

    Table 44. Instantaneous residual overcurrent protection efpioc (50n) function range or value accuracy operate current (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - operate time 25 ms typically at 0 to 2 x i set - reset time 25 ms typically at 2 to 0 x i set -...

  • Page 62

    Table 46. Four step negative sequence overcurrent protection ns4ptoc (46i2) function range or value accuracy operate value, negative sequence current, step 1-4 (1-2500)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio > 95% - timers (0.000-60.000) s ± 0.5% ± 10 ms inverse charac...

  • Page 63

    Table 47. Sensitive directional residual overcurrent and power protection sdepsde (67n) function range or value accuracy operate level for 3i 0 ·cosj directional residual overcurrent (0.25-200.00)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n at low setting: (0.25-1.00)% of i n : ±0.05% ...

  • Page 64

    Table 47. Sensitive directional residual overcurrent and power protection sdepsde (67n) , continued function range or value accuracy operate time, non-directional residual over current 60 ms typically at 0 to 2 x i set - reset time, non-directional residual over current 60 ms typically at 2 to 0 x i...

  • Page 65

    Table 49. Breaker failure protection ccrbrf (50bf) function range or value accuracy operate phase current (5-200)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n reset ratio, phase current > 95% - operate residual current (2-200)% of lbase ± 1.0% of i n at i £ i n ± 1.0% of i at i > i n re...

  • Page 66

    Table 52. Directional underpower protection guppdup (37) function range or value accuracy power level (0.0–500.0)% of sbase at low setting: (0.5-2.0)% of sbase (2.0-10)% of sbase ± 1.0% of s r at s r ± 1.0% of s at s > s r characteristic angle (-180.0–180.0) degrees 2 degrees timers (0.00-6000.00) s...

  • Page 67

    Voltage protection table 55. Two step undervoltage protection uv2ptuv (27) function range or value accuracy operate voltage, low and high step (1–100)% of vbase ± 0.5% of v n absolute hysteresis (0–100)% of vbase ± 0.5% of v n internal blocking level, step 1 and step 2 (1–100)% of vbase ± 0.5% of v ...

  • Page 68

    Table 57. Two step residual overvoltage protection rov2ptov (59n) function range or value accuracy operate voltage, step 1 and step 2 (1-200)% of vbase ± 0.5% of v n at v n ± 1.0% of v at v > v n absolute hysteresis (0–100)% of vbase ± 0.5% of v n at v n ± 1.0% of v at v > v n inverse time character...

  • Page 69

    Table 60. Loss of voltage check lovptuv (27) function range or value accuracy operate voltage (0–100)% of vbase ± 0.5% of v n pulse timer (0.050–60.000) s ± 0.5% ± 10 ms timers (0.000–60.000) s ± 0.5% ± 10 ms line differential protection red670 ansi 1mrk505226-bus d customized product version: 1.2 a...

  • Page 70

    Frequency protection table 61. Underfrequency protection saptuf (81) function range or value accuracy operate value, pickup function (35.00-75.00) hz ± 2.0 mhz operate time, pickup function 100 ms typically - reset time, pickup function 100 ms typically - operate time, definite time function (0.000-...

  • Page 71

    Table 63. Rate-of-change frequency protection sapfrc (81) function range or value accuracy operate value, pickup function (-10.00-10.00) hz/s ± 10.0 mhz/s operate value, internal blocking level (0-100)% of vbase ± 0.5% of v n operate time, pickup function 100 ms typically - line differential protect...

  • Page 72

    Multipurpose protection table 64. General current and voltage protection cvgapc function range or value accuracy measuring current input phase a, phase b, phase c, posseq, negseq, 3*zeroseq, maxph, minph, unbalanceph, phase a-phase b, phase b-phase c, phase c-phase a, maxph- ph, minph-ph, unbalancep...

  • Page 73

    Table 64. General current and voltage protection cvgapc , continued function range or value accuracy reset time pickup undervoltage 25 ms typically at 0 to 2 x v set - high and low voltage limit, voltage dependent operation (1.0 - 200.0)% of vbase ± 1.0% of v n for v n ± 1.0% of v for v>v n directio...

  • Page 74

    Secondary system supervision table 65. Current circuit supervision ccsrdif (87) function range or value accuracy operate current (5-200)% of i n ± 10.0% of i n at i £ i n ± 10.0% of i at i > i n block current (5-500)% of i n ± 5.0% of i n at i £ i n ± 5.0% of i at i > i n table 66. Fuse failure supe...

  • Page 75

    Control table 67. Synchronizing, synchronism check and energizing check sesrsyn (25) function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage ratio, v bus /v line 0.500 - 2.000 - voltage high limit for synchronism check (50.0-120.0)% of vbasebus and vbaseline ± 0....

  • Page 76

    Table 68. Autorecloser smbrrec (79) function range or value accuracy number of autoreclosing shots 1 - 5 - autoreclosing open time: shot 1 - t1 1ph shot 1 - t1 2ph shot 1 - t1 3phhs shot 1 - t1 3phdld (0.000-60.000) s ± 0.5% ± 10 ms shot 2 - t2 shot 3 - t3 shot 4 - t4 shot 5 - t5 (0.00-6000.00) s ex...

  • Page 77

    Scheme communication table 69. Scheme communication logic for distance or overcurrent protection zcpsch (85) function range or value accuracy scheme type intertrip permissive underreach permissive overreach blocking - co-ordination time for blocking communication scheme (0.000-60.000) s ± 0.5% ± 10 ...

  • Page 78

    Table 72. Current reversal and weak-end infeed logic for phase segregated communication zc1wpsch function range or value accuracy detection pickup phase to neutral voltage (10-90)% of vbase ± 0.5% of v n detection pickup phase to phase voltage (10-90)% of vbase ± 0.5% of v n reset ratio - operate ti...

  • Page 79

    Direct transfer trip table 75. Low active power and power factor protection lappgapc (37_55) function range or value accuracy operate value, low active power (2.0-100.0)% of sbase ± 1,0% of s n reset ratio, low active power - transient overreach, low active power - operate value, low power factor 0....

  • Page 80

    Table 79. Negative sequence overvoltage protection lcnsptov (47) function range or value accuracy operate value, negative sequence overvoltage (1-200)% of vbase ± 0.5% of v n at v n ± 0.5% of v at v>v n reset ratio, negative sequence overvoltage >95% - operate time, start 20 ms typically at 0 to 2xv...

  • Page 81

    Table 82. Zero sequence overcurrent protection lczsptoc (51n) function range or value accuracy operate value, zero sequence overcurrent (1-2500)% of ibase ± 1.0% of i n at i n ± 1.0% of i at i>i n reset ratio, zero sequence overcurrent >95% - operate time, start 20 ms typically at 0 to 2xi set 15 ms...

  • Page 82

    Logic table 85. Tripping logic smpptrc (94) function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms timers (0.000-60.000) s ± 0.5% ± 10 ms table 86. Configurable logic blocks logic block quantity with cycle time range or value a...

  • Page 83

    Monitoring table 87. Measurements cvmmxn function range or value accuracy frequency (0.95-1.05) × f n ± 2.0 mhz voltage (0.1-1.5) ×v n ± 0.5% of v n at v£v n ± 0.5% of v at v > v n connected current (0.2-4.0) × i n ± 0.5% of i n at i £ i n ± 0.5% of i at i > i n active power, p 0.1 x v n n 0.2 x i n...

  • Page 84

    Table 91. Current sequence component measurement cmsqi function range or value accuracy current positive sequence, i1 three phase settings (0.1–4.0) × i n ± 0.2% of i n at i ≤ 0.5 × i n ± 0.2% of i at i > 0.5 × i n current zero sequence, 3i0 three phase settings (0.1–1.0) × i n ± 0.2% of i n at i ≤ ...

  • Page 85

    Table 95. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 120 maximum number of analog inputs 30 + 10 (e...

  • Page 86

    Table 98. Indications function value buffer capacity maximum number of indications presented for single disturbance 96 maximum number of recorded disturbances 100 table 99. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturbance ...

  • Page 87

    Metering table 102. Pulse counter pcggio function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 103. Energy metering etpmmtr function range or value accuracy energy metering kwh export/import, kvarh export/ import inp...

  • Page 88

    Station communication table 104. Iec 61850-8-1 communication protocol function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 608–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–19200 bd protocol tcp/...

  • Page 89

    Table 109. Slm – spa/iec 60870-5-103/dnp3 port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (3000ft/1000 m typically *) plastic fiber: 7 db (80ft/25 m typically *) diameter glass fiber: 62.5/125 mm plastic fi...

  • Page 90

    Remote communication table 113. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm or 50/125 µm singlemode 9/125 µm singlemode 9/125 µm wave length 850 nm 1310 nm 1550 nm optica...

  • Page 91

    Hardware ied table 114. Case material steel sheet front plate steel sheet profile with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 115. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom i...

  • Page 92

    Basic ied functions table 119. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 120. Time synchronization, time tagging function value time tagging resolution, events and sampled measurement values 1 ms t...

  • Page 93

    Table 123. Irig-b quantity rated value number of channels irig-b 1 number of channels pps 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x accurac...

  • Page 94

    Inverse characteristic table 124. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) = + × - æ ö ç ÷ ç ÷ è ø 1 p a t b td i equation1651 v1 en reset characteristic: ( ) = × - 2 1 tr t td i equation1652 v1 en i = i measured /i set td = (0.05-999) in steps...

  • Page 95

    Table 125. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) = × - æ ö ç ÷ ç ÷ è ø 1 p a t td i equation1653 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 - time delay to reset, iec inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms ...

  • Page 96

    Table 126. Ri and rd type inverse time characteristics function range or value accuracy ri type inverse characteristic = × - 1 0.236 0.339 t td i equation1656 v1 en i = i measured /i set td = (0.05-999) in steps of 0.01 iec 60255-151, 5% + 40 ms rd type logarithmic inverse characteristic = - × æ ö ç...

  • Page 97

    Table 128. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø td t vpickup v vpickup equation1658 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: × = + - × - æ ö ç ÷ è ø 2.0 480 0.055 32 0.5 td t vpic...

  • Page 98

    Table 129. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - æ ö ç ÷ è ø t td v vpickup vpickup equation1661 v1 en v = v measured td = (0.05-1.10) in steps of 0.01 5% +40 ms type b curve: = × - × - - æ ö ç ÷ è ø 2.0 480 32 0.5 0.035 t...

  • Page 99

    22. Ordering guidelines carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Please refer to the available functions ta...

  • Page 100

    Optional functions differential protection 1ph high impedance differential protection (hzpdif, 87) qty: 1 2 3 1mrk 002 901-hb additional security logic for differential protection (stsggio, 11rel) qty: 1mrk 002 903-pa line differential protection red670 ansi 1mrk505226-bus d customized product versi...

  • Page 101

    Impedance protection rule: one and only one of the alternatives (alt. 1-4) can be ordered alternative 1: rule: distance protection and directional impedance must be ordered together note: phase selection fdpspdis always included in this package) distance protection zones, quadrilateral characteristi...

  • Page 102

    Phase selection, quadrilateral characteristic with settable angle (frpspdis, 21) qty: 1 2 1mrk 002 925-xa directional impedance quadrilateral (zdrdir, 21d) qty: 1 2 1mrk 002 904-yb note: optional with alternative 1 directional impedance element for mho characteristic (zdmrdir, 21d) qty: 1 2 1mrk 002...

  • Page 103

    Current protection instantaneous phase overcurrent protection (phpioc, 50) qty: 1 2 3 1mrk 002 906-ac four step phase overcurrent protection (oc4ptoc, 51/67) qty: 1mrk 002 906-bd instantaneous residual overcurrent protection (efpioc, 50n) qty: 1mrk 002 906-cc four step residual overcurrent protectio...

  • Page 104

    Frequency protection underfrequency protection (saptuf, 81) qty: 1 2 1mrk 002 908-nc overfrequency protection (saptof, 81) qty: 1 2 1mrk 002 908-rc rate-of-change frequency protection (sapfrc, 81) qty: 1 2 1mrk 002 908-sb multipurpose protection general current and voltage protection (cvgapc) qty: 1...

  • Page 105

    Direct transfer trip direct transfer trip (dtt) qty: 1mrk 002 927-xa station communication note: require 2-channel oem iec 62439-3 edition 1 parallel redundancy protocol 1mrk 002 924-yr iec 62439-3 edition 2 parallel redundancy protocol 1mrk 002 924-ys first local hmi user dialogue language rule: on...

  • Page 106

    Analog system rule: one transformer input module must be ordered note: the same type of connection terminals has to be ordered for both trms transformer input module, compression terminals 12i, 1a, 50/60 hz qty: 1 2 1mrk 002 247-cg transformer input module, compression terminals 12i, 5a, 50/60 hz qt...

  • Page 107

    Transformer input module, compression terminals 6i, 5a, 50/60 hz qty: 1 1mrk 002 247-dh transformer input module, ring lug terminals 12i, 1a, 50/60 hz qty: 1 2 1mrk 002 247-cc transformer input module, ring lug terminals 12i, 5a, 50/60 hz qty: 1 2 1mrk 002 247-cd transformer input module, ring lug t...

  • Page 108

    Transformer input module, ring lug terminals 6i, 1a, 50/60 hz qty: 1 1mrk 002 247-dc transformer input module, ring lug terminals 6i, 5a, 50/60 hz qty: 1 1mrk 002 247-dd note: one analog digital conversion module, with time synchronization is always delivered with each transformer input module. Case...

  • Page 109

    Binary input/output modules make bim with 50 ma inrush current the primary choice. Bim with 50 ma inrush current fulfill additional standards. As a consequence the emc withstand capability is further increased. For pulse counting, for example kwh metering, the bim with enhanced pulse counting capabi...

  • Page 110

    Binary input module (bim) with enhanced pulse counting capabilities, 16 inputs rl 24-30 vdc qty: 1 2 3 4 5 6 8 9 10 11 12 13 7 14 1mrk 000 508-ha rl 48-60 vdc qty: 1 2 3 4 5 6 8 9 10 11 12 13 7 14 1mrk 000 508-ea rl 110-125 vdc qty: 1 2 3 4 5 6 8 9 10 11 12 13 7 14 1mrk 000 508-fa rl 220-250 vdc qty...

  • Page 111

    Make iom with 50 ma inrush current the primary choice. Iom with 50 ma inrush current fulfill additional standards. As a consequence the emc withstand capability is further increased. Iom with 30 ma inrush current is still available. Binary input/output module (iom) 8 inputs, 10 outputs, 2 high-speed...

  • Page 112

    Station communication ports note: optical ethernet module, 2 glass interfaces is not allowed together with slm. Optical ethernet module, 1 channel glass 1mrk 002 266-aa optical ethernet module, 2 channel glass 1mrk 002 266-ba serial and lon communication module, supports spa/iec 60870-5-103, lon and...

  • Page 113

    Flush mounting kit for terminal quantity: 1mrk 000 020-y flush mounting kit + ip54 sealing (factory mounted). Cannot be ordered separately thus must be specified when ordering a terminal. Quantity: 1mrk 002 420-ea accessories gps antenna and mounting details gps antenna, including mounting kits quan...

  • Page 114

    Protection cover protective cover for rear side of rhgs6, 6u, 1/4 x 19” quantity: 1mrk 002 420-ae protective cover for rear side of terminal, 6u, 1/2 x 19” quantity: 1mrk 002 420-ac protective cover for rear side of terminal, 6u, 3/4 x 19” quantity: 1mrk 002 420-ab protective cover for rear side of ...

  • Page 115

    Rule: specify additional quantity of ied connect cd requested . Quantity: 1mrk 002 290-ab rule: specify the number of printed manuals requested operator’s manual ansi quantity: 1mrk 505 223-uus technical reference manual ansi quantity: 1mrk 505 222-uus installation and commissioning manual ansi quan...

  • Page 116

    Connection and installation components 1mrk 513 003-ben test system, combitest 1mrk 512 001-ben accessories for 670 series ieds 1mrk 514 012-ben 670 series spa and signal list 1mrk 500 092-wus iec 61850 data objects list for 670 series 1mrk 500 091-wus engineering manual 670 series 1mrk 511 240-uus ...

  • Page 117

    117.

  • Page 118

    Contact us abb inc. 1021 main campus drive raleigh, nc 27606, usa phone toll free: 1-800-help-365, menu option #8 abb inc. 3450 harvester road burlington, on l7n 3w5, canada phone toll free: 1-800-help-365, menu option #8 abb mexico s.A. De c.V. Paseo de las americas no. 31 lomas verdes 3a secc. 531...