5. Wide area measurement system
Synchrophasor report, 8 phasors
Configuration parameters for IEEE1344 and C37.118 protocol
PMUCONF
The IED supports the following IEEE synchrophasor standards:
• IEEE 1344-1995 (Both measurements and data
communication)
• IEEE Std C37.118-2005 (Both measurements and data
communication)
• IEEE Std C37.118.1–2011 and C37.118.1a-2014
(Measurements)
• IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for
both IEEE C37.118 and IEEE 1344 protocols. This means all the
required settings and parameters in order to establish and
define a number of TCP and/or UDP connections with one or
more PDC clients (synchrophasor client). This includes port
numbers, TCP/UDP IP addresses, and specific settings for
IEEE C37.118 as well as IEEE 1344 protocols.
Protocol reporting via IEEE 1344 and C37.118 PMUREPORT
The phasor measurement reporting block moves the phasor
calculations into an IEEE C37.118 and/or IEEE 1344
synchrophasor frame format. The PMUREPORT block contains
parameters for PMU performance class and reporting rate, the
IDCODE and Global PMU ID, format of the data streamed
through the protocol, the type of reported synchrophasors, as
well as settings for reporting analog and digital signals.
The message generated by the PMUREPORT function block is
set in accordance with the IEEE C37.118 and/or IEEE 1344
standards.
There are settings for Phasor type (positive sequence, negative
sequence or zero sequence in case of 3-phase phasor and L1,
L2 or L3 in case of single phase phasor), PMU's Service class
(Protection or Measurement), Phasor representation (polar or
rectangular) and the data types for phasor data, analog data
and frequency data.
Synchrophasor data can be reported to up to 8 clients over TCP
and/or 6 UDP group clients for multicast or unicast
transmission of phasor data from the IED. More information
regarding synchrophasor communication structure and
TCP/UDP configuration is available in Application Manual under
section C37.118 Phasor Measurement Data Streaming
Protocol Configuration.
Multiple PMU functionality can be configured in the IED, which
can stream out same or different data at different reporting
rates or different performance (service) classes.
6. Current protection
Instantaneous phase overcurrent protection PHPIOC
The instantaneous three phase overcurrent function has a low
transient overreach and short tripping time to allow use as a
high set short-circuit protection function.
Directional phase overcurrent protection, four steps OC4PTOC
Directional phase overcurrent protection, four steps
(OC4PTOC) has an inverse or definite time delay for each step.
All IEC and ANSI inverse time characteristics are available
together with an optional user defined time characteristic.
The directional function needs voltage as it is voltage polarized
with memory. The function can be set to be directional or non-
directional independently for each of the steps.
A second harmonic blocking level can be set for the function
and can be used to block each step individually.
Instantaneous residual overcurrent protection EFPIOC
The Instantaneous residual overcurrent protection (EFPIOC)
has a low transient overreach and short tripping times to allow
the use for instantaneous earth-fault protection, with the reach
limited to less than the typical eighty percent of the line at
minimum source impedance. EFPIOC is configured to measure
the residual current from the three-phase current inputs and
can be configured to measure the current from a separate
current input.
Directional residual overcurrent protection, four steps
EF4PTOC
Directional residual overcurrent protection, four steps
(EF4PTOC) can be used as main protection for phase-to-earth
faults. It can also be used to provide a system back-up, for
example, in the case of the primary protection being out of
service due to communication or voltage transformer circuit
failure.
EF4PTOC has an inverse or definite time delay independent for
each step.
All IEC and ANSI time-delayed characteristics are available
together with an optional user-defined characteristic.
EF4PTOC can be set to be directional or non-directional
independently for each step.
IDir, UPol and IPol can be independently selected to be either
zero sequence or negative sequence.
A second harmonic blocking can be set individually for each
step.
Directional operation can be combined together with the
corresponding communication logic in permissive or blocking
teleprotection scheme. The current reversal and weak-end
infeed functionality are available as well.
1MRK 506 372-BEN -
Line distance protection REL670 2.2
Product version: 2.2
ABB
31
Summary of REL670
Page 1
Relion® 670 series — line distance protection rel670 version 2.2 product guide.
Page 2
Contents 1. Application..................................................................... 3 2. Available functions........................................................10 3. Differential protection....................................................25 4. Impedance protection.......................
Page 3
1. Application the intelligent electronic device (ied) is used for the protection, control and monitoring of overhead lines and cables in solidly, impedance earthed or isolated networks. The ied can be used up to the high voltage levels. It is suitable for the protection of heavily loaded lines and ...
Page 4
Description of configuration a41 qb1 qb2 qa1 qb9 qc9 wa1 wa2 rel670 a41 – single breaker with three phase tripping for high ohmic and resonance earthed systems 12ai (6i+6u) zclc psch 67n sde psde in> oc4 ptoc 51_67 4(3i>) lc pttr 26 θ> cc rbrf 50bf 3i>bf other functions available from the function l...
Page 5
Description of configuration a42 qb1 qb2 qa1 qb9 qc9 wa1 wa2 rel670 a42 – single breaker with single or three phase tripping 12ai (6i+6u) cc rbrf 50bf 3i>bf 26 lc pttr θ> oc4 ptoc 51_67 4(3i>) vn mmxu met un vn mmxu met un wa2_vt wa1_vt line_ct line_vt smp ptrc 94 1->0 smb rrec 79 5(0 →1) smp ptrc 9...
Page 6
Description of configuration b42 qb1 wa1_qb6 line1_qb9 qb61 qb62 line2_qb9 wa2_qb6 wa1_qa1 tie_qa1 rel670 b42 – multi breaker with single or three phase tripping 12ai (6i+6u) vn mmxu met un lmb rflo 21fl fl etp mmtr met w/varh qb2 wa2_qa1 zmf pdis 21 z v msqi met usqi stb ptoc 50stb 3i>stb c msqi me...
Page 7
Description of configuration d42 qb1 qb2 qa1 qb9 qc9 wa1 wa2 rel670 d42 – single breaker with single or three phase tripping with pmu functionality cc rbrf 50bf 3i>bf 26 lc pttr θ> oc4 ptoc 51_67 4(3i>) other functions available from the function library s cilo 3 control s cswi 3 control rov2 ptov 5...
Page 8
Z 5 5 sc/vc o->i 3i> 4 4 in> 4 4 i->o close trip bus a bus b 21 51/67 51n/67n 79 25 94/86 3i> 50bf trip busbar en05000276.Vsd 3u> 59 3u 27 2 2 2 2 iec05000276-1 v1 en figure 5. The single breaker packages for single- and three phase tripping typical arrangement for one protection sub-system is shown...
Page 9
Z 5 5 sc/vc o->i 3i> 4 4 in> 4 4 3u> 2 2 3u 2 2 i->o close trip bus a 21 51/67 51n/67n 59 27 79 25 94/86 3i> 50bf trip busbar & cb2 3i> 50bf s sc/vc o->i i->o c lo s e t r ip 25 94/86 79 iec05000317-2-en.Vsd trip cb1/3 cb1 cb2 iec05000317 v2 en figure 6. The multi breaker packages for single- and th...
Page 10
2. Available functions the following tables list all the functions available in the ied. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. Main protection functions table 1. Example of quantities 2 = number of basic instances 0-3 = opt...
Page 11
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) differential protection hzpdif 87 high impedance differential protection, single phase 0-3 3-a02 3-a02 3-a02 ldrgfc 11rel additional security logic for different...
Page 12
Back-up protection functions iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) current protection phpioc 50 instantaneous phase overcurrent protection 0-3 1 1 1 1 oc4ptoc 51_67 1) directional phase overcurrent p...
Page 13
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) saptof 81 overfrequency protection 0-6 1b 3-e04 1b 3-e04 1b 3-e04 1b 3-e04 sapfrc 81 rate-of-change of frequency protection 0-6 1b 3-e04 1b 3-e04 1b 3-e04 1b 3-e...
Page 14
Control and monitoring functions iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) control sesrsyn 25 synchrocheck, energizing check and synchronizing 0-2 1 1 2 1 smbrrec 79 autorecloser 0-4 1 1b 1-h04 2b 2-h05 ...
Page 15
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) tmagapc trip matrix logic 12 12 12 12 12 almcalh logic for group alarm 5 5 5 5 5 wrncalh logic for group warning 5 5 5 5 5 indcalh logic for group indication 5 5...
Page 16
Table 2. Total number of instances for basic configurable logic blocks basic configurable logic block total number of instances and 280 gate 40 inv 420 lld 40 or 298 pulsetimer 40 rsmemory 40 srmemory 40 timerset 60 xor 40 table 3. Number of function instances in apc10 function name function descrip...
Page 17
Table 4. Number of function instances in apc15 function name function description total number of instances scilo interlocking 15 bb_es 3 a1a2_bs 2 a1a2_dc 3 abc_bc 1 bh_conn 1 bh_line_a 1 bh_line_b 1 db_bus_a 1 db_bus_b 1 db_line 1 abc_line 1 ab_trafo 1 scswi switch controller 15 sxswi circuit swit...
Page 18
Table 6. Total number of instances for extended logic package extended configurable logic block total number of instances and 180 gate 49 inv 180 lld 49 or 180 pulsetimer 89 rsmemory 40 slgapc 74 srmemory 130 timerset 109 vsgapc 120 xor 89 1mrk 506 372-ben - line distance protection rel670 2.2 produ...
Page 19
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) monitoring cvmmxn power system measurement 6 6 6 6 6 cmmxu current measurement 10 10 10 10 10 vmmxu voltage measurement phase-phase 6 6 6 6 6 cmsqi current seque...
Page 20
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) metering pcfcnt pulse-counter logic 16 16 16 16 16 etpmmtr function for energy calculation and demand handling 6 6 6 6 6 1mrk 506 372-ben - line distance protect...
Page 21
Communication iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) station communication lonspa, spa spa communication protocol 1 1 1 1 1 ade lon communication protocol 1 1 1 1 1 horzcomm network variables via lon ...
Page 22
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) iec 61850-9-2 process bus communication, 8 merging units 0-1 1-p30 1-p30 1-p30 1-p30 activlog activity logging 1 1 1 1 1 altrk service tracking 1 1 1 1 1 prp iec...
Page 23
Iec 61850 or function name ansi function description line distance rel670 (customized) rel670 (a41) rel670 (a42) rel670 (b42) rel670 (d42) zc1ppsch 85 phase segregated scheme communication logic for distance protection 0-2 1-b05 1-b05 1-b05 zcrwpsch 85 current reversal and weak-end infeed logic for ...
Page 24
Basic ied functions table 8. Basic ied functions iec 61850 or function name description interrsig self supervision with internal event list timesynchgen time synchronization module bininput, synchcan, synchgps, synchcmpps, synchlon, synchpph, synchpps, sntp, synchspa time synchronization ptp precisi...
Page 25
Table 9. Local hmi functions iec 61850 or function name ansi description lhmictrl local hmi signals language local human machine language screen local hmi local human machine screen behavior fnkeyty1–fnkeyty5 fnkeymd1– fnkeymd5 parameter setting function for hmi in pcm600 ledgen general led indicati...
Page 26
• startup element is sensitive enough to detect the abnormal status of the protected system • startup element does not influence the operation speed of main protection • startup element would detect the evolving faults, high impedance faults and three phase fault on weak side • it is possible to blo...
Page 27
Exporting end at phase to earth-faults on heavily loaded power lines. The distance protection zones can operate, independent of each other, in directional (forward or reverse) or non-directional mode. This makes them suitable, together with different communication schemes, for the protection of powe...
Page 28
En05000034.Vsd r x forward operation reverse operation iec05000034 v1 en figure 10. Typical quadrilateral distance protection zone with phase selection, quadrilateral characteristic with settable angle function frpspdis activated the independent measurement of impedance for each fault loop together ...
Page 29
The independent measurement of impedance for each fault loop together with a sensitive and reliable built-in phase selection makes the function suitable in applications with single pole tripping and autoreclosing. Built-in adaptive load compensation algorithm prevents overreaching of zone 1 at load ...
Page 30
Power swing detection zmrpsb power swings may occur after disconnection of heavy loads or trip of big generation plants. Power swing detection function (zmrpsb ) is used to detect power swings and initiate block of all distance protection zones. Occurrence of earth-fault currents during a power swin...
Page 31
5. Wide area measurement system synchrophasor report, 8 phasors configuration parameters for ieee1344 and c37.118 protocol pmuconf the ied supports the following ieee synchrophasor standards: • ieee 1344-1995 (both measurements and data communication) • ieee std c37.118-2005 (both measurements and d...
Page 32
The residual current can be calculated by summing the three- phase currents or taking the input from the neutral ct. Four step directional negative phase sequence overcurrent protection ns4ptoc four step directional negative phase sequence overcurrent protection (ns4ptoc) has an inverse or definite ...
Page 33
Normally the own breaker is tripped to correct such a situation. If the situation persists the surrounding breakers should be tripped to clear the unsymmetrical load situation. The pole discordance protection function (ccpdsc) operates based on information from auxiliary contacts of the circuit brea...
Page 34
Radial feeder protection papgapc the radial feeder protection (papgapc) function is used to provide protection of radial feeders having passive loads or weak end in-feed sources. It is possible to achieve fast tripping using communication system with remote end or delayed tripping not requiring comm...
Page 35
Function block smai. However the main difference is that it can be used to extract any frequency component from the input signal. Thus it can, for example, be used to build sub- synchronous resonance protection for synchronous generator. 11. Secondary system supervision current circuit supervision c...
Page 36
Breaker to reclose first and the second will only close if the fault proved to be transient. Each auto reclosing function can be configured to co-operate with the synchrocheck function. Apparatus control apc the apparatus control functions are used for control and supervision of circuit breakers, di...
Page 37
Ied. This representation is identical to that of an sxcbr or sxswi function. Goose function block to receive a switching device goosexlnrcv the goose xln receive component is used to collect information from another device’s xcbr/xswi logical node sent over process bus via goose. The goose xln recei...
Page 38
To accomplish this, three separate communication channels, that is, one per phase, each capable of transmitting a signal in each direction is required. Zc1ppsch can be completed with the current reversal and wei logic for phase segregated communication, when found necessary in blocking and permissiv...
Page 39
Direct transfer trip dtt low active power and power factor protection lappgapc low active power and power factor protection (lappgapc) function measures power flow. It can be used for protection and monitoring of: • phase wise low active power • phase wise low power factor • phase wise reactive powe...
Page 40
General start matrix block smagapc the start matrix (smagapc) merges start and directional output signals from different application functions and creates a common start and directional output signal ( stdir ) to be connected to the trip function. The idea is to provide general start and directional...
Page 41
Copied to si_out output. The time part of single position input is copied to time output. The quality bits in the common part and the indication part of inputs signal are copied to the corresponding quality output. • invalidqt function which sets quality invalid of outputs according to a "valid" inp...
Page 42
15. Monitoring measurements cvmmxn, cmmxu, vnmmxu, vmmxu, cmsqi, vmsqi the measurement functions are used to get on-line information from the ied. These service values make it possible to display on-line information on the local hmi and on the substation automation system about: • measured voltages,...
Page 43
Function. The result is magnitude and phase angle before and during the fault for each analog input signal. The trip value recorder information is available for the disturbances locally in the ied. The trip value recorder information is an integrated part of the disturbance record (comtrade file). D...
Page 44
Especially on heavily loaded long lines, where the source voltage angles can be up to 35-40 degrees apart, the accuracy can be still maintained with the advanced compensation included in fault locator. Event counter with limit supervison l4ufcnt the limit counter (l4ufcnt) provides a settable counte...
Page 45
• graphical display capable of showing a user defined single line diagram and provide an interface for controlling switchgear. • navigation buttons and five user defined command buttons to shortcuts in the hmi tree or simple commands. • 15 user defined three-color leds. • communication port for pcm6...
Page 46
Or equipment, either on the substation automation (sa) bus or substation monitoring (sm) bus. Available communication protocols are: • iec 61850-8-1 communication protocol • iec/uca 61850-9-2le communication protocol • lon communication protocol • spa communication protocol • iec 60870-5-103 communi...
Page 47
Function commands for iec 60870-5-103 i103cmd i103cmd is a command function block in control direction with pre-defined output signals. The signals are in steady state, not pulsed, and stored in the ied in case of restart. Ied commands for iec 60870-5-103 i103iedcmd i103iedcmd is a command block in ...
Page 48
22. Hardware description hardware modules numeric processing module num the numeric processing module (num) is a cpu module that handles all protection functions and logic. Num provides up to four optical ethernet ports of type lc (one basic and three optional). Power supply module psm the power sup...
Page 49
Layout and dimensions dimensions c b d e a iec08000163-2-en.Vsd iec08000163 v2 en figure 15. Case with rear cover iec08000165-2-en.Vsdx j g f k h iec08000165 v2 en figure 16. Case with rear cover and 19” rack mounting kit iec06000182-2-en.Vsd iec06000182 v2 en figure 17. A 1/2 x 19” size ied side-by...
Page 50
Case size (mm)/(inches) a b c d e f g h j k 6u, 1/2 x 19” 265.9/ 10.47 223.7/ 8.81 242.1/ 9.53 255.8/ 10.07 205.7/ 8.10 190.5/ 7.50 203.7/ 8.02 - 228.6/ 9.00 - 6u, 3/4 x 19” 265.9/ 10.47 336.0/ 13.23 242.1/ 9.53 255.8/ 10.07 318.0/ 12.52 190.5/ 7.50 316.0/ 12.4 - 228.6/ 9.00 - 6u, 1/1 x 19” 265.9/ 1...
Page 51
23. Connection diagrams the connection diagrams are delivered in the ied connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.Abb.Com/protection-control . Connection diagrams for iec customized products connection diag...
Page 52
24. Technical data general definitions reference value the specified value of an influencing factor to which are referred the characteristics of the equipment nominal range the range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the speci...
Page 53
Energizing quantities, rated values and limits analog inputs table 10. Trm - energizing quantities, rated values and limits for protection transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1 or 5 a operating range (0-100) ...
Page 54
Table 11. Trm - energizing quantities, rated values and limits for measuring transformer description value frequency rated frequency f r 50/60 hz operating range f r ± 10% current inputs rated current i r 1a 5 a operating range (0-1.8) × i r (0-1.6) × i r thermal withstand 80 × i r for 1 s 25 × i r ...
Page 55
Auxiliary dc voltage table 14. Psm - power supply module quantity rated value nominal range auxiliary dc voltage, el (input) el = (24-60) v el = (100-250) v el ± 20% el ± 20% power consumption 50 w typically - auxiliary dc power in-rush - binary inputs and outputs table 15. Bim - binary input module...
Page 56
Table 16. Bim - binary input module with enhanced pulse counting capabilities quantity rated value nominal range binary inputs 16 - dc voltage, rl 24/30 v 48/60 v 110/125 v 220/250 v rl ± 20% rl ± 20% rl ± 20% rl ± 20% power consumption 24/30 v 48/60 v 110/125 v 220/250 v max. 0.05 w/input max. 0.1 ...
Page 57
Table 18. Iom - binary input/output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs 10 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 1000 v rms 800 v dc curr...
Page 58
Table 19. Iom with mov and iom 220/250 v, 110ma - contact data (reference standard: iec 61810-2) function or quantity trip and signal relays fast signal relays (parallel reed relay) binary outputs iom: 10 iom: 2 max system voltage 250 v ac, dc 250 v dc test voltage across open contact, 1 min 250 v r...
Page 59
Table 20. Som - static output module (reference standard: iec 61810-2): static binary outputs function of quantity static binary output trip rated voltage 48-60 vdc 110-250 vdc number of outputs 6 6 impedance open state ~300 kΩ ~810 kΩ test voltage across open contact, 1 min no galvanic separation n...
Page 60
Table 22. Bom - binary output module contact data (reference standard: iec 61810-2) function or quantity trip and signal relays binary outputs 24 max system voltage 250 v ac, dc test voltage across open contact, 1 min 1000 v rms current carrying capacity per relay, continuous per relay, 1 s per proc...
Page 61
Table 25. Frequency influence (reference standard: iec 60255–1) dependence on within nominal range influence frequency dependence, operate value f r ±2.5 hz for 50 hz f r ±3.0 hz for 60 hz ±1.0%/hz frequency dependence for distance protection operate value f r ±2.5 hz for 50 hz f r ±3.0 hz for 60 hz...
Page 62
Table 27. Insulation test type test values reference standard dielectric test 2.0 kv ac, 1 min. Iec 60255-27 ansi c37.90 impulse voltage test 5 kv, 1.2/50 m s, 0.5 j insulation resistance > 100 m w at 500 vdc table 28. Environmental tests test type test value reference standard cold operation test t...
Page 63
Differential protection table 31. High impedance differential protection, single phase hzpdif function range or value accuracy operate voltage (10-900) v i=u/r ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio >95% at (30-900) v - maximum continuous power u>trip 2 /seriesresistor ≤200 w - op...
Page 64
Impedance protection table 33. Distance measuring zone, quad zmqpdis function range or value accuracy number of zones max 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, phase- to-phase and phase-to-earth (10-1000)% of ibase - posi...
Page 65
Table 34. Distance measuring zone, quadrilateral characteristic for series compensated lines zmcpdis, zmcapdis function range or value accuracy number of zones max 5 with selectable direction - minimum operate residual current, zone 1 (5-1000)% of ibase - minimum operate current, ph-ph and ph-e (10-...
Page 66
Table 36. Full-scheme distance protection, mho characteristic zmhpdis function range or value accuracy number of zones, ph-e max 5 with selectable direction - minimum operate current (10–30)% of ibase - positive sequence impedance, ph-e loop (0.005–3000.000) w /phase ±2.0% static accuracy conditions...
Page 67
Table 38. Faulty phase identification with load encroachment fmpspdis function range or value accuracy load encroachment criteria: load resistance, forward and reverse (1.00–3000.00) w /phase (5–70) degrees ±2.0% static accuracy conditions: voltage range: (0.1–1.1) x u r current range: (0.5–30) x i ...
Page 68
Table 40. Phase selection, quadrilateral characteristic with settable angle frpspdis function range or value accuracy minimum operate current (5-500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reactive reach, positive sequence (0.50–3000.00) Ω/phase ±2.0% static accuracy ±2.0 degrees st...
Page 69
Table 41. High speed distance protection zmfpdis, zmfcpdis function range or value accuracy number of zones 3 selectable directions, 3 fixed directions - minimum operate current, ph-ph and ph-e (5-6000)% of ibase ±1.0% of i r positive sequence reactance reach, ph-e and ph-ph loop (0.01 - 3000.00) oh...
Page 70
Table 42. Power swing detection zmrpsb function range or value accuracy reactive reach (0.10-3000.00) w /phase ±2.0% static accuracy conditions: voltage range: (0.1-1.1) x u r current range: (0.5-30) x i r angle: at 0 degrees and 85 degrees resistive reach (0.10–1000.00) w /loop power swing detectio...
Page 71
Table 46. Phase preference logic pplphiz function range or value accuracy operate value, phase-to-phase and phase-to-neutral undervoltage (1 - 100)% of ubase ±0.5% of u r reset ratio, undervoltage - operate value, residual voltage (5 - 300)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r res...
Page 72
Table 48. Automatic switch onto fault logic zcvpsof parameter range or value accuracy operate voltage, detection of dead line (1–100)% of ubase ±0.5% of u r operate current, detection of dead line (1–100)% of ibase ±1.0% of i r time delay to operate for the switch onto fault function (0.03-120.00) s...
Page 73
Wide area measurement system table 49. Protocol reporting via ieee 1344 and c37.118 pmureport influencing quantity range accuracy signal frequency ± 0.1 x f r ≤ 1.0% tve signal magnitude: voltage phasor current phasor (0.1–1.2) x u r (0.5–2.0) x i r phase angle ± 180° harmonic distortion 10% from 2n...
Page 74
Current protection table 50. Instantaneous phase overcurrent protection phpioc function range or value accuracy operate current (5-2500)% of lbase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50–2500)% of ibase - operate time at 0 to 2 x i set min. = 15 ms max. = 25 ms - res...
Page 75
Table 52. Instantaneous residual overcurrent protection efpioc function range or value accuracy operate current (5-2500)% of lbase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (50–2500)% of lbase - operate time at 0 to 2 x i set min. = 15 ms max. = 25 ms - reset time at 2 x i s...
Page 76
Table 53. Directional residual overcurrent protection, four steps ef4ptoc function range or value accuracy operate current, step 1-4 (1-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - relay characteristic angle (rca) (-180 to 180) degrees ±2.0...
Page 77
Table 54. Four step directional negative phase sequence overcurrent protection ns4ptoc function range or value accuracy operate current, step 1 - 4 (1-2500)% of lbase ±1.0% of i r at i £ i r ±1.0% of i at i > i r reset ratio > 95% at (10-2500)% of ibase - independent time delay at 0 to 2 x i set , s...
Page 78
Table 55. Sensitive directional residual overcurrent and power protection sdepsde function range or value accuracy operate level for 3i 0 ·cos j directional residual overcurrent (0.25-200.00)% of ibase ±1.0% of i r at i £ i r ±1.0% of i at i > i r operate level for ·3i 0 ·3u 0 cos j directional resi...
Page 79
Table 56. Thermal overload protection, one time constant lcpttr/lfpttr function range or value accuracy reference current (2-400)% of ibase ±1.0% of i r reference temperature (0-300)°c, (0 - 600)°f ± 1.0°c, ±2.0°f operate time: 2 2 2 2 2 ln p trip amb p ref ref i i t t t i i i t t - = - - - × é ù ê ...
Page 80
Table 58. Stub protection stbptoc function range or value accuracy operating current (5-2500)% of ibase ± 1.0% of i r at i ≤ i r ± 1.0% of i at i > i r reset ratio > 95% at (50-2500)% of ibase - independent time delay at 0 to 2 x i set (0.000-60.000) s ± 0.2% or ± 30 ms whichever is greater operate ...
Page 81
Table 62. Broken conductor check brcptoc function range or value accuracy minimum phase current for operation (5–100)% of ibase ±1.0% of i r unbalance current operation (50–90)% of maximum current ±1.0% of i r independent operate time delay (0.000-60.000) s ±0.2% or ±45 ms whichever is greater indep...
Page 82
Table 63. Voltage-restrained time overcurrent protection vrpvoc function range or value accuracy start overcurrent (2.0 - 5000.0)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% - operate time, start overcurrent at 0 to 2 x i set min. = 15 ms - max. = 30 ms res...
Page 83
Voltage protection table 64. Two step undervoltage protection uv2ptuv function range or value accuracy operate voltage, low and high step (1.0–100.0)% of ubase ±0.5% of u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r internal blocking level, step 1 and step 2 (1–50)% of ubase ±0.5% of u r ...
Page 84
Table 65. Two step overvoltage protection ov2ptov function range or value accuracy operate voltage, step 1 and 2 (1.0-200.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r inverse time characteristics for...
Page 85
Table 66. Two step residual overvoltage protection rov2ptov function range or value accuracy operate voltage, step 1 - step 2 (1.0-200.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r absolute hysteresis (0.0–50.0)% of ubase ± 0.5% of u r at u ≤ u r ± 0.5% of u at u > u r inverse time ch...
Page 86
Table 68. Voltage differential protection vdcptov function range or value accuracy voltage difference for alarm and trip (2.0–100.0) % of ubase ±0.5% of u r under voltage level (1.0–100.0) % of ubase ±0.5% of u r independent time delay for voltage differential alarm at 0.8 x udalarm to 1.2 x udalarm...
Page 87
Frequency protection table 71. Underfrequency protection saptuf function range or value accuracy operate value, start function, at symmetrical three phase voltage (35.00-75.00) hz ±2.0 mhz operate time, start at f set + 0.02 hz to f set - 0.02 hz fn = 50 hz min. = 80 ms - max. = 95 ms fn = 60 hz min...
Page 88
Table 73. Rate-of-change of frequency protection sapfrc function range or value accuracy operate value, start function (-10.00-10.00) hz/s ±10.0 mhz/s operate value, restore enable frequency (45.00-65.00) hz ±2.0 mhz definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is greater ...
Page 89
Multipurpose protection table 74. General current and voltage protection cvgapc function range or value accuracy measuring current input phase1, phase2, phase3, posseq, - negseq, -3*zeroseq, maxph, minph, unbalanceph, phase1-phase2, phase2-phase3, phase3-phase1, maxph-ph, minph-ph, unbalanceph- ph -...
Page 90
Table 74. General current and voltage protection cvgapc , continued function range or value accuracy start undervoltage, step 1 - 2 (2.0 - 150.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r independent time delay, overvoltage at 0.8 x u set to 1.2 x u set , step 1 - 2 (0.00 - 6000.00) s ...
Page 91
Table 74. General current and voltage protection cvgapc , continued function range or value accuracy undervoltage: critical impulse time 10 ms typically at 1.2 x u set to 0.8 x u set - impulse margin time 15 ms typically - 1mrk 506 372-ben - line distance protection rel670 2.2 product version: 2.2 a...
Page 92
Secondary system supervision table 75. Current circuit supervision ccsspvc function range or value accuracy operate current (10-200)% of ibase ±10.0% of i r at i ≤ i r ±10.0% of i at i > i r reset ratio, operate current >90% block current (20-500)% of ibase ±5.0% of i r at i ≤ i r ±5.0% of i at i > ...
Page 93
Control table 78. Synchronizing, synchrocheck and energizing check sesrsyn function range or value accuracy phase shift, j line - j bus (-180 to 180) degrees - voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of ubase ±0.5% of u r at u ≤ u r ±0.5% of u at u > u r reset ratio, sync...
Page 94
Table 79. Autorecloser smbrrec function range or value accuracy dead time: shot 1 “t1 1ph” shot 1 “t1 2ph” shot 1 “t1 3ph “ shot 1 “t1 3phhs” (0.000-120.000) s ±0.2% or ±35 ms whichever is greater dead time: shot 2 “t2 3ph” shot 3 “t3 3ph” shot 4 “t4 3ph” shot 5 “t5 3ph” (0.00-6000.00) s ±0.2% or ±3...
Page 95
Scheme communication table 80. Scheme communication logic with delta based blocking scheme signal transmit zcpsch function range or value accuracy scheme type off intertrip permissive ur permissive or blocking deltablocking - operate voltage, delta u (0–100)% of ubase ±5.0% of Δu operate current, de...
Page 96
Table 83. Current reversal and weak-end infeed logic for phase segregated communication zc1wpsch function range or value accuracy detection level phase to neutral voltage (10-90)% of ubase ±0.5% of u r detection level phase to phase voltage (10-90)% of ubase ±0.5% of u r reset ratio - operate time f...
Page 97
Direct transfer trip table 87. Low active power and power factor protection lappgapc function range or value accuracy operate value, low active power (2.0-100.0)% of sbase ±1.0% of s r reset ratio, low active power - operate value, low power factor 0.00-1.00 ±0.02 independent time delay to operate f...
Page 98
Table 90. Carrier receive logic lccrptrc function range or value accuracy operation mode 1 out of 2 2 out of 2 - independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is greater table 91. Negative sequence overvoltage protection lcnsptov function range or value accuracy operate value, ne...
Page 99
Table 93. Negative sequence overcurrent protection lcnsptoc function range or value accuracy operate value, negative sequence overcurrent (3 - 2500)% of ibase ±1.0% of ir at i ≤ i r ±1.0% of i at i > i r reset ratio, negative sequence overcurrent >95% at (50–2500)% of ibase - operate time, start at ...
Page 100
Table 95. Three phase overcurrent lcp3ptoc function range or value accuracy operate value, overcurrent (5-2500)% of ibase ±1.0% of i r at i ≤ i r ±1.0% of i at i > i r reset ratio, overcurrent > 95% at (50-2500)% of ibase - start time at 0 to 2 x i set min. = 10 ms max. = 25 ms - reset time at 2 x i...
Page 101
Logic table 97. Tripping logic common 3-phase output smpptrc function range or value accuracy trip action 3-ph, 1/3-ph, 1/2/3-ph - minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater evolving fault del...
Page 102
Table 105. Number of and instances logic block quantity with cycle time 3 ms 8 ms 100 ms and 60 60 160 table 106. Number of gate instances logic block quantity with cycle time 3 ms 8 ms 100 ms gate 10 10 20 table 107. Number of inv instances logic block quantity with cycle time 3 ms 8 ms 100 ms inv ...
Page 103
Table 113. Number of timerset instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms timerset 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms table 114. Number of xor instances logic block quantity with cycle time 3 ms 8 ms 100 ms xor 10 10 20 table 115. Number of andqt in...
Page 104
Table 121. Number of pulsetimerqt instances logic block quantity with cycle time range or value accuracy 3 ms 8 ms 100 ms pulsetimerqt - 10 30 (0.000–90000.000) s ±0.5% ±10 ms table 122. Number of rsmemoryqt instances logic block quantity with cycle time 3 ms 8 ms 100 ms rsmemoryqt - 10 30 table 123...
Page 105
Table 127. Number of b16i instances function quantity with cycle time 3 ms 8 ms 100 ms b16i 6 4 8 table 128. Number of btigapc instances function quantity with cycle time 3 ms 8 ms 100 ms btigapc 4 4 8 table 129. Number of ib16 instances function quantity with cycle time 3 ms 8 ms 100 ms ib16 6 4 8 ...
Page 106
Monitoring table 135. Power system measurement cvmmxn function range or value accuracy frequency (0.95-1.05) x f r ± 2.0 mhz voltage (10 to 300) v ± 0.3% of u at u ≤ 50 v ± 0.2% of u at u > 50 v current (0.1-4.0) x i r ± 0.8% of i at 0.1 x i r i 0.2 x i r ± 0.5% of i at 0.2 x i r i 0.5 x i r ± 0.2% ...
Page 107
Table 138. Voltage measurement phase-earth vnmmxu function range or value accuracy voltage (5 to 175) v ±0.5% of u at u ≤ 50 v ±0.2% of u at u > 50 v phase angle (5 to 175) v ±0.5 degrees at u ≤ 50 v ±0.2 degrees at u > 50 v table 139. Current sequence measurement cmsqi function range or value accur...
Page 108
Table 142. Disturbance report drprdre function range or value accuracy pre-fault time (0.05–9.90) s - post-fault time (0.1–10.0) s - limit time (0.5–10.0) s - maximum number of recordings 100, first in - first out - time tagging resolution 1 ms see table 175 maximum number of analog inputs 30 + 10 (...
Page 109
Table 144. Insulation supervision for liquid medium function ssiml function range or value accuracy oil alarm level 1.00-100.00 ±10.0% of set value oil lockout level 1.00-100.00 ±10.0% of set value temperature alarm level -40.00-200.00 ±2.5% of set value temperature lockout level -40.00-200.00 ±2.5%...
Page 110
Table 148. Indications function value buffer capacity maximum number of indications presented for single disturbance 352 maximum number of recorded disturbances 100 table 149. Event recorder function value buffer capacity maximum number of events in disturbance report 150 maximum number of disturban...
Page 111
Metering table 154. Pulse-counter logic pcfcnt function setting range accuracy input frequency see binary input module (bim) - cycle time for report of counter value (1–3600) s - table 155. Function for energy calculation and demand handling etpmmtr function range or value accuracy energy metering k...
Page 112
Station communication table 156. Communication protocols function value protocol iec 61850-8-1 communication speed for the ieds 100base-fx protocol iec 60870–5–103 communication speed for the ieds 9600 or 19200 bd protocol dnp3.0 communication speed for the ieds 300–115200 bd protocol tcp/ip, ethern...
Page 113
Table 161. Slm – lon port quantity range or value optical connector glass fiber: type st plastic fiber: type hfbr snap-in fiber, optical budget glass fiber: 11 db (1000m/3000 ft typically *) plastic fiber: 7 db (10m/35ft typically *) fiber diameter glass fiber: 62.5/125 m m plastic fiber: 1 mm *) de...
Page 114
Remote communication table 165. Line data communication module characteristic range or value type of ldcm short range (sr) medium range (mr) long range (lr) type of fiber graded-index multimode 62.5/125 µm graded-index multimode 50/125 µm singlemode 9/125 µm singlemode 9/125 µm peak emission wave le...
Page 115
Hardware ied table 166. Case material steel sheet front plate stainless steel with cut-out for hmi surface treatment aluzink preplated steel finish light grey (ral 7035) table 167. Water and dust protection level according to iec 60529 front ip40 (ip54 with sealing strip) sides, top and bottom ip40 ...
Page 116
Table 172. Num: number of ethernet ports num 4 ethernet ports 1 basic, 3 optional ethernet connection type sfp optical lc carrier modules supported oem, ldcm table 173. Oem: number of ethernet ports oem 2 ethernet ports ethernet connection type sfp optical lc 1mrk 506 372-ben - line distance protect...
Page 117
Basic ied functions table 174. Self supervision with internal event list data value recording manner continuous, event controlled list size 40 events, first in-first out table 175. Time synchronization, time tagging function value time tagging accuracy of the synchrophasor data ± 1 µs time tagging r...
Page 118
Table 179. Irig-b quantity rated value number of channels irig-b 1 number of optical channels 1 electrical connector: electrical connector irig-b bnc pulse-width modulated 5 vpp amplitude modulated – low level – high level 1-3 vpp 3 x low level, max 9 vpp supported formats irig-b 00x, irig-b 12x acc...
Page 119
Inverse characteristic table 180. Ansi inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 en i = i measured /i set 0.1...
Page 120
Table 181. Iec inverse time characteristics function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set 0.10 ≤ k ≤ 3.00 1.5 x i set ≤ i ≤ 20 x i set iec 60255-151, ±2.0% or ±40 ms whichever is greater iec normal inve...
Page 121
Table 183. Ansi inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en reset characteristic: ( ) 2 1 = × - tr t k i equat...
Page 122
Table 184. Iec inverse time characteristics for sensitive directional residual overcurrent and power protection function range or value accuracy operating characteristic: ( ) 1 = × - æ ö ç ÷ ç ÷ è ø p a t k i equation1251-small v1 en i = i measured /i set 0.10 ≤ k ≤ 2.00 1.5 x i set ≤ i ≤ 20 x i set...
Page 123
Table 186. Ansi inverse time characteristics for voltage restrained time overcurrent protection function range or value accuracy operating characteristic: ( ) 1 p a t b k tdef i æ ö ç ÷ = + × + ç ÷ ç - ÷ è ø equation1249-small v2 en reset characteristic: ( ) 2 1 = × - tr t k i equation1250-small v1 ...
Page 124
Table 188. Inverse time characteristics for overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.035 32 0.5 ...
Page 125
Table 189. Inverse time characteristics for undervoltage protection function range or value accuracy type a curve: = æ ö ç ÷ è ø k t u u u equation1431-small v1 en u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 0.055 32 0.5 × = + × - ...
Page 126
Table 190. Inverse time characteristics for residual overvoltage protection function range or value accuracy type a curve: = - > > æ ö ç ÷ è ø t k u u u equation1436-small v1 en u> = u set u = u measured k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater type b curve: 2.0 480 32 0...
Page 127
25. Ordering for customized ied table 191. General guidelines guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the de...
Page 128
Table 196. Differential functions function function identification ordering no position available qty selected qty notes and rules high impedance differential protection, single phase hzpdif 1mrk005904-hb 6 0-3 additional security logic for differential protection ldrgfc 1mrk005904-ta 15 0-1 table 1...
Page 129
Table 198. Impedance functions, alternatives function function identification ordering no position available qty selected qty notes and rules note: one and only one of alternatives 1 to 6 must be selected. *) selected qty = 0 for functions in unselected alternatives. Alternative 1 distance protectio...
Page 130
Table 200. Current functions function function identification ordering no position available qty selected qty notes and rules instantaneous phase overcurrent protection phpioc 1mrk005910-ad 1 0-3 directional phase overcurrent protection, four steps oc4ptoc 1mrk005910-bc 2 0-3 instantaneous residual ...
Page 131
Table 207. General calculation position 1 s table 208. General calculation functions function function identification ordering no position available qty selected qty notes and rules multipurpose filter smaihpac 1mrk005915-kb 1 0-6 table 209. Secondary system supervision position 1 2 3 g table 210. S...
Page 132
Table 216. Logic functions function function identification ordering no position available qty selected qty notes and rules configurable logic blocks q/t 1mrk005922-mx 1 0-1 extension logic package 1mrk005922-az 2 0-1 table 217. Monitoring position 1 2 3 m 1 0 table 218. Monitoring functions functio...
Page 133
Table 223. Mounting selection mounting details with ip40 of protection from the front ordering no selection notes and rules no mounting kit included x 19" rack mounting kit for 1/2 x 19" case or 2xrhgs6 or rhgs12 1mrk002420-bb a 19" rack mounting kit for 3/4 x 19" case or 3xrhgs6 1mrk002420-ba b 19"...
Page 134
Table 226. Analog system selection analog system ordering no selection notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x0 x0...
Page 135
Table 228. Maximum quantity of i/o modules, with ringlug terminals note: only every second slot can be used. Case sizes bim iom bom/ som mim maximum in case 1/1 x 19” rack casing, one (1) trm 7 6 4 4 7 **) possible locations: p3, p5, p7, p9, p11, p13, p15 1/1 x 19” rack casing, two (2) trm 5 5 4 4 5...
Page 136
Table 229. Binary input/output module selection binary input/ output modules ordering no selection notes and rules slot position (front view/rear view) p3/x31 p4/x41 p5/x51 p6/x61 p7/x71 p8/x81 p9/x91 p10/x101 p11/x111 p12/x121 p13/x131 p14/x141 p15/x151 p16/x161 1/2 case with 1 trm █ █ █ these blac...
Page 137
Table 229. Binary input/output module selection, continued binary input/ output modules ordering no selection notes and rules iom 8 inputs, 10+2 outputs, rl220, 220-250vdc, 50ma 1mrk000173-ce p1 p1 p1 p1 p1 p1 p1 p1 p1 p1 p1 p1 p1 p1 iom 8 inputs 10+2 outputs, rl220, 220-250vdc, 110ma 1mrk000173-cf ...
Page 138
Table 230. Station communication, remote end serial communication and time synchronization selection station communication, remote end serial communication and time synchronization ordering no selection notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 ...
Page 139
26. Ordering for pre-configured ied guidelines carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. Pcm600 can be used to make changes and/or additions to the delivered factory configurat...
Page 140
Language ordering no #4 notes and rules first local hmi user dialogue language hmi language, english iec 1mrk002930-aa b1 additional local hmi user dialogue language no additional hmi language x0 hmi language, english us 1mrk002920-ub a12 selection for position #4 b1 casing ordering no #5 notes and ...
Page 141
Analog system ordering no #9 notes and rules when more than one trm is selected, the connector type on both trms must be the same (a compression or b ring lug). Slot position (front view/rear view) p40/x401 p41/x411 no transformer input module included x0 x0 only valid if iec 61850-9-2 process bus c...
Page 142
Binary input/ output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1 bim and 1 bom required in positions p3 and p4 in rel a42, b42 and d42. B42 requires one extra bim in position p5. 1 iom r...
Page 143
Binary input/ output modules ordering no #10 notes and rules for pulse counting, for example kwh metering, the bim with enhanced pulse counting capabilities must be used. Note: 1 bim and 1 bom required in positions p3 and p4 in rel a42, b42 and d42. B42 requires one extra bim in position p5. 1 iom r...
Page 144
Station communication, remote end serial communication and time synchronization ordering no #11 notes and rules slot position (front view/rear view) p30:1/x301 p30:2/x302 p30:3/x303 p30:4/x304 p30:5/x305 p30:6/x306 p30:6:1/x3061 p30:6:2/x3062 p31:1/x311 p31:2/x312 p31:3/x313 p32:2/x322 p32:3/x323 ld...
Page 145
27. Ordering for accessories accessories gps antenna and mounting details gps antenna, including mounting kits quantity: 1mrk 001 640-aa cable for antenna, 20 m (appx. 65 ft) quantity: 1mrk 001 665-aa cable for antenna, 40 m (appx. 131 ft) quantity: 1mrk 001 665-ba interface converter (for remote en...
Page 146
External resistor unit high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 1ph quantity: 1 2 3 rk 795 101-ma high impedance resistor unit with resistor and voltage dependent resistor 20-100v, 3ph quantity: rk 795 101-mb high impedance resistor unit with resistor and vo...
Page 147
User documentation rule: specify the number of printed manuals requested application manual iec quantity: 1mrk 506 369-uen ansi quantity: 1mrk 506 369-uus technical manual iec quantity: 1mrk 506 370-uen ansi quantity: 1mrk 506 370-uus commissioning manual iec quantity: 1mrk 506 371-uen ansi quantity...
Page 148
Ansi quantity: 1mrk 511 398-uus cyber security deployment guideline iec quantity: 1mrk 511 399-uen application guide, communication set-up iec quantity: 1mrk 505 382-uen reference information for our reference and statistics we would be pleased to be provided with the following application data: cou...
Page 149
149.
Page 150
— abb ab grid automation products 721 59 västerås, sweden phone: +46 (0) 21 32 50 00 abb.Com/protection-control © copyright 2017 abb. All rights reserved. Specifications subject to change without notice. 1mrk 506 372-ben.