ABB relion REF615 Applications Manual

Other manuals for relion REF615: Applications Manual, Operation Manual, Product Manual
Manual is about: Feeder Protection and Control Relion 615 series

Summary of relion REF615

  • Page 1

    Relion ® 615 series feeder protection and control ref615 application manual.

  • Page 3

    Document id: 1mrs756378 issued: 2016-05-20 revision: s product version: 5.0 fp1 © copyright 2016 abb. All rights reserved.

  • Page 4

    Copyright this document and parts thereof must not be reproduced or copied without written permission from abb, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and ...

  • Page 5

    Disclaimer the data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intende...

  • Page 6

    Conformity this product complies with the directive of the council of the european communities on the approximation of the laws of the member states relating to electromagnetic compatibility (emc directive 2004/108/ec) and concerning electrical equipment for use within specified voltage limits (low-...

  • Page 7

    Table of contents section 1 introduction.......................................................................7 this manual........................................................................................ 7 intended audience.......................................................................

  • Page 8

    Default i/o connections.......................................................... 50 default disturbance recorder settings.....................................51 functional diagrams.................................................................... 53 functional diagrams for protection................

  • Page 9

    Functional diagrams for protection....................................... 119 functional diagrams for disturbance recorder......................126 functional diagrams for condition monitoring.......................127 functional diagrams for control and interlocking..................129 functional ...

  • Page 10

    Functional diagrams for disturbance recorder......................214 functional diagrams for condition monitoring.......................215 functional diagrams for control and interlocking..................217 functional diagrams for measurement functions ................ 220 functional diagrams fo...

  • Page 11

    Functional diagrams for condition monitoring.......................309 functional diagrams for control and interlocking..................311 functional diagrams for measurement functions ................ 315 functional diagrams for i/o and alarm leds ...................... 318 functional diagrams fo...

  • Page 12

    Section 5 ied physical connections............................................. 383 inputs..............................................................................................383 energizing inputs.......................................................................383 phase currents.........

  • Page 13

    Section 1 introduction 1.1 this manual the application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. 1...

  • Page 14

    1.3 product documentation 1.3.1 product documentation set planning & purchase engineering installation commissioning operation maintenance decommissioning, deinst allation & dispos al quick start guide quick installation guide brochure product guide operation manual installation manual connection di...

  • Page 15

    Document revision/date product version history h/2010-09-24 3.0 content updated k/2012-05-11 4.0 content updated to correspond to the product version l/2013-02-21 4.0 fp1 content updated to correspond to the product version m/2013-12-20 5.0 content updated to correspond to the product version n/2014...

  • Page 16

    The warning icon indicates the presence of a hazard which could result in personal injury. The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to eq...

  • Page 17

    1.4.3 functions, codes and symbols table 1: functions included in the relay function iec 61850 iec 60617 iec-ansi protection three-phase non-directional overcurrent protection, low stage phlptoc1 3i> (1) 51p-1 (1) phlptoc2 3i> (2) 51p-1 (2) three-phase non-directional overcurrent protection, high st...

  • Page 18

    Function iec 61850 iec 60617 iec-ansi residual overvoltage protection rovptov1 uo> (1) 59g (1) rovptov2 uo> (2) 59g (2) rovptov3 uo> (3) 59g (3) three-phase undervoltage protection phptuv1 3u 27 (1) phptuv2 3u 27 (2) phptuv3 3u 27 (3) three-phase overvoltage protection phptov1 3u> (1) 59 (1) phptov2...

  • Page 19

    Function iec 61850 iec 60617 iec-ansi multipurpose protection mapgapc1 map (1) map (1) mapgapc2 map (2) map (2) mapgapc3 map (3) map (3) mapgapc4 map (4) map (4) mapgapc5 map (5) map (5) mapgapc6 map (6) map (6) mapgapc7 map (7) map (7) mapgapc8 map (8) map (8) mapgapc9 map (9) map (9) mapgapc10 map...

  • Page 20

    Function iec 61850 iec 60617 iec-ansi earthing switch control esxswi1 i o esc (1) i o esc (1) disconnector position indication dcsxswi1 i o dc (1) i o dc (1) dcsxswi2 i o dc (2) i o dc (2) dcsxswi3 i o dc (3) i o dc (3) earthing switch indication essxswi1 i o es (1) i o es (1) essxswi2 i o es (2) i ...

  • Page 21

    Function iec 61850 iec 60617 iec-ansi rtd/ma measurement xrggio130 x130 (rtd) (1) x130 (rtd) (1) frequency measurement fmmxu1 f (1) f (1) iec 61850-9-2 le sampled value sending smvsender smvsender smvsender iec 61850-9-2 le sampled value receiving (voltage sharing) smvrcv smvrcv smvrcv other minimum...

  • Page 22

    16.

  • Page 23

    Section 2 ref615 overview 2.1 overview ref615 is a dedicated feeder protection and control relay designed for the protection, control, measurement and supervision of utility substations and industrial power systems including radial, looped and meshed distribution networks with or without distributed...

  • Page 24

    2.1.1 product version history product version product history 1.0 product released 1.1 • irig-b • support for parallel protocols added: iec 61850 and modbus • x130 bio added: optional for variants b and d • cb interlocking functionality enhanced • tcs functionality in hw enhanced • non-volatile memo...

  • Page 25

    Product version product history 4.0 fp1 • high-availability seamless redundancy (hsr) protocol • parallel redundancy protocol (prp-1) • parallel use of iec 61850 and dnp3 protocols • parallel use of iec 61850 and iec 60870-5-103 protocols • two selectable indication colors for leds (red or green) • ...

  • Page 26

    • configuration wizard • ar sequence visualizer • label printing • iec 61850 configuration • ied configuration migration download connectivity packages from the abb web site http://www.Abb.Com/substationautomation or directly with the update manager in pcm600. 2.2 operation functionality 2.2.1 optio...

  • Page 27

    Table 2: plug-in unit and case main unit slot id content options plug-in unit - hmi small (5 lines, 20 characters) large (10 lines, 20 characters) with sld small chinese (3 lines, 8 or more characters) large chinese (7 lines, 8 or more characters) with sld x100 auxiliary power/bo module 48-250 v dc/...

  • Page 28

    Main unit slot id content options case x130 ai/bi module only with configurations e, f, h, j, k and n: 3 phase voltage inputs (60-210 v) 1 residual voltage input (60-210 v) 4 binary inputs additionally with configurations h, j, k and n: 1 reference voltage input for secrsyn1 (60-210 v) ai/rtd/ma mod...

  • Page 29

    Table 3: input/output overview std. Conf. Order code digit analog channels binary channels 5-6 7-8 ct vt combi sensor bi bo rtd ma a aa / ab aa 4 1 - 3 4 po + 2 so - - b aa / ab ae 4 1 - 17 4 po + 9 so - - fa 4 1 - 17 4 po + 5 so + 3 hso - - fa / fb ac 4 1 - 11 4 po + 6 so 6 2 fg 4 1 - 11 4 po + 2 s...

  • Page 30

    Std. Conf. Order code digit analog channels binary channels 5-6 7-8 ct vt combi sensor bi bo rtd ma g l da ah 1 - 3 8 4 po + 6 so - - fd 1 - 3 8 4 po + 2 so + 3 hso - - k bc ad 5 5 - 12 4 po + 6 so - - fe 5 5 - 12 4 po + 2 so + 3 hso - - 2.4 local hmi the lhmi is used for setting, monitoring and con...

  • Page 31

    2.4.1 display the lhmi includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size. Table 4: small display character size 1) rows in the view characters per row s...

  • Page 32

    2.4.2 leds the lhmi includes three protection indicators above the display: ready, start and trip. There are 11 matrix programmable leds on front of the lhmi. The leds can be configured with pcm600 and the operation mode can be selected with the lhmi, whmi or pcm600. 2.4.3 keypad the lhmi keypad con...

  • Page 33

    • programmable leds and event lists • system supervision • parameter settings • measurement display • disturbance records • fault records • load profile record • phasor diagram • single-line diagram • importing/exporting parameters • report summary the menu tree structure on the whmi is almost ident...

  • Page 34

    2.6 authorization four user categories have been predefined for the lhmi and the whmi, each with different rights and default passwords. The default passwords in the protection relay delivered from the factory can be changed with administrator user rights. User authorization is disabled by default f...

  • Page 35

    The protection relay stores 2048 audit trail events to the nonvolatile audit trail. Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit trail and event list work according to the fifo principle. Nonvolatile memory is based on a memory type which does not need bat...

  • Page 36

    Pcm600. The audit trail cannot be reset, but pcm600 event viewer can filter data. Audit trail events can be configured to be visible also in lhmi/whmi event list together with process related events. To expose the audit trail events through event list, define the authority logging level parameter vi...

  • Page 37

    Communication protocol is supported by using the protocol converter spa-zc 302. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the protection relays, is only enabled by the iec 61850...

  • Page 38

    Managed ethernet switch with rstp support managed ethernet switch with rstp support client b client a network a network b guid-283597af-9f38-4fc7-b87a-73bfda272d0f v3 en figure 6: self-healing ethernet ring solution the ethernet ring solution supports the connection of up to 30 protection relays. If...

  • Page 39

    Iec 62439-3:2012 cancels and replaces the first edition published in 2010. These standard versions are also referred to as iec 62439-3 edition 1 and iec 62439-3 edition 2. The protection relay supports iec 62439-3:2012 and it is not compatible with iec 62439-3:2010. Prp each prp node, called a doubl...

  • Page 40

    • via an external redundancy box (redbox) or a switch capable of connecting to prp and normal networks • by connecting the node directly to lan a or lan b as san • by connecting the node to the protection relay's interlink port hsr hsr applies the prp principle of parallel operation to a single ring...

  • Page 41

    Unigear digital switchgear concept relies on the process bus together with current and voltage sensors. The process bus enables several advantages for the unigear digital like simplicity with reduced wiring, flexibility with data availability to all ieds, improved diagnostics and longer maintenance ...

  • Page 42

    Iec 61850 hsr sm v tr af fi c backup 1588 master clock managed hsr ethernet switch primary ieee 1588 v2 master clock secondary ieee 1588 v2 master clock (optional) managed hsr ethernet switch guid-7c56bc1f-f1b2-4e74-ab8e-05001a88d53d v4 en figure 10: example network topology with process bus, redund...

  • Page 43

    Section 3 ref615 standard configurations 3.1 standard configurations ref615 is available in twelve alternative standard configurations. The standard signal configuration can be altered by means of the signal matrix or the graphical application functionality of the protection and control ied manager ...

  • Page 44

    Description std. Conf. Directional and non-directional overcurrent and earth-fault protection, high-impedance restricted earth-fault protection, voltage and frequency based protection and measurements, synchro-check and circuit-breaker condition monitoring (optional power quality and fault locator) ...

  • Page 45

    Function iec 61850 a b c d e f g h j k l n phase discontinuity protection pdnsptoc 1 1 1 1 1 1 1 1 1 1 1 residual overvoltage protection rovptov 3 1) 3 1) 3 3 3 2) 3 3 2 3 2) 3 three-phase undervoltage protection phptuv 3 3 3 3 2 3 3 three-phase overvoltage protection phptov 3 3 3 3 2 3 3 positive-s...

  • Page 46

    Function iec 61850 a b c d e f g h j k l n voltage variation phqvvr (1) 7) (1) 7) (1) 7) (1) 7) voltage unbalance vsqvub (1) 7) (1) 7) (1) 7) (1) 7) control circuit-breaker control cbxcbr 1 1 1 1 1 1 1 1 1 1 1 1 disconnector control dcxswi 2 2 2 2 2 2 2 2 2 2 earthing switch control esxswi 1 1 1 1 1...

  • Page 47

    Function iec 61850 a b c d e f g h j k l n iec 61850-9-2 le sampled value receiving (voltage sharing) 8)9) smvrcv (1) (1) (1) (1) (1) (1) (1) (1) other minimum pulse timer (2 pcs) tpgapc 4 4 4 4 4 4 4 4 4 4 4 4 minimum pulse timer (2 pcs, second resolution) tpsgapc 1 1 1 1 1 1 1 1 1 1 1 1 minimum pu...

  • Page 48

    The suitability of the ied’s binary outputs which have been selected for primary device control should be carefully verified, for example make and carry and breaking capacity. If the requirements for the primary device control circuit are not met, using external auxiliary relays should be considered...

  • Page 49

    3.2 connection diagrams ref615 x13 light sensor input 1 1) x14 light sensor input 2 1) x15 light sensor input 3 1) 1) optional x130 module optional in ref615 conf b 2) the ied features an automatic short-circuit mechanism in the ct connector when plug-in unit is detached 3) ref615 conf b: bio0005 mo...

  • Page 50

    Ref615 x13 light sensor input 1 1) x14 light sensor input 2 1) x15 light sensor input 3 1) 16 17 19 18 x100 6 7 8 9 10 11 12 13 15 14 2 1 3 4 5 22 21 23 24 so2 tcs2 po4 so1 tcs1 po3 po2 po1 irf + - u aux 20 x130 1 2 3 4 5 6 bi 4 bi 3 bi 2 bi 1 bi 6 bi 5 8 9 7 x130 12 10 11 15 13 14 18 16 17 so3 so2 ...

  • Page 51

    Guid-f7601942-acf2-47e2-8f21-cd9c1d2bc1f0 v4 en figure 13: connection diagram for the e and f configurations 1mrs756378 s section 3 ref615 standard configurations ref615 45 application manual.

  • Page 52

    Ref615 16 17 19 18 x100 6 7 8 9 10 11 12 13 15 14 2 1 3 4 5 22 21 23 24 so2 tcs2 po4 so1 tcs1 po3 po2 po1 irf + - u aux 20 x110 3 4 5 6 7 8 9 10 bi 6 bi 5 bi 4 bi 3 bi 2 bi 8 bi 7 12 13 11 bi 1 1 2 x110 16 14 15 19 17 18 22 20 21 so3 so2 so1 23 so4 24 x130 1 2 x131 4 5 il1 7 8 u1 x132 4 5 il2 7 8 u2...

  • Page 53

    Guid-e8e2f79f-3dd8-46bd-8de7-87a30133a7ae v1 en figure 15: connection diagram for the h, j and n configurations 1mrs756378 s section 3 ref615 standard configurations ref615 47 application manual.

  • Page 54

    Ref615 x13 light sensor input 1 1) x14 light sensor input 2 1) x15 light sensor input 3 1) 1) optional 2) the ied features an automatic short-circuit mechanism in the ct connector when plug-in unit is detached 3) bio0005 module (8bi+4bo) alternative module bio0007 (8bi+3hso) 16 17 19 18 x100 6 7 8 9...

  • Page 55

    3.3 standard configuration a 3.3.1 applications the standard configuration for non-directional overcurrent and directional earth-fault protection is mainly intended for cable and overhead-line feeder applications in isolated and resonant-earthed distribution networks. The configuration also includes...

  • Page 56

    3.3.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and ...

  • Page 57

    Table 12: default connections for binary outputs binary output description x100-po1 close circuit breaker x100-po2 circuit breaker failure protection trip to upstream breaker x100-po3 open circuit breaker/trip coil 1 x100-po4 open circuit breaker/trip coil 2 x100-so1 general start indication x100-so...

  • Page 58

    Table 15: default disturbance recorder binary channels channel id text level trigger mode 1 phlptoc1 - start positive or rising 2 phhptoc1 - start positive or rising 3 phhptoc2 - start positive or rising 4 phiptoc1 - start positive or rising 5 nsptoc1 - start positive or rising 6 nsptoc2 - start pos...

  • Page 59

    Channel id text level trigger mode 22 intrptef1 - operate level trigger off 23 efhptoc1 - operate level trigger off 24 pdnsptoc1 - operate level trigger off 25 inrphar1 - blk2h level trigger off 26 t1pttr1 - operate level trigger off 27 rovptov1 - operate level trigger off rovptov2 - operate rovptov...

  • Page 60

    Depending on the communication protocol the required function block needs to be instantiated in the configuration. 3.3.3.1 functional diagrams for protection the functional diagrams describe the ieds protection functionality in detail and according to the factory set default connections. Four overcu...

  • Page 61

    Two negative-sequence overcurrent protection stages nsptoc1 and nsptoc2 are provided for phase unbalance protection. These functions are used to protect the feeder against phase unbalance. Nsptoc1 block ena_mult operate start nsptoc2 block ena_mult operate start or b1 b2 o nsptoc1_operate nsptoc1_op...

  • Page 62

    Or6 b1 b2 b3 b4 b5 b6 o defhpdef1_operate deflpdef1_operate deflpdef2_operate def_operate deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate deflpdef1_operate deflpdef2_operate defhpdef1_start...

  • Page 63

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start wpwde_operate guid-2ee794ad-2d14-49c7-ad33...

  • Page 64

    Non-directional (cross-country) earth-fault protection, using calculated io, efhptoc1 protects against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. Efhptoc1 block ena_mult operate...

  • Page 65

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu x120_bi2_cb_closed phiptoc1_operate phhptoc1_operate phhptoc2_operate defhpdef1_operate deflpdef2_operate ccbrbrf1_trret guid-434d2001-0d44-45d6-863f-dd...

  • Page 66

    The optional autoreclosing function is configured to be initiated by operate signals from a number of protection stages through the init_1...5 inputs. It is possible to create individual autoreclose sequences for each input. The autoreclosing function can be inhibited with the inhibit_recl input. By...

  • Page 67

    Residual overvoltage protection rovptov1 provides earth-fault protection by detecting an abnormal level of residual voltage. This can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. Rovptov1 block operate start rovptov2 block operate...

  • Page 68

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 general_start_pulse general_operate_pulse phiptoc1_operate...

  • Page 69

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_operate efpadm1_operate efp...

  • Page 70

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_ope...

  • Page 71

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 72

    Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm tcsscbr2_alarm tcsscbr2_alarm tcsscbr_blocking tcsscbr_blocking tcsscbr_alarm guid-f6281256-8b8d-41d9-ad19-014d604afcec v1 en figure 36: trip circuit supervision function or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi3...

  • Page 73

    Or b1 b2 o cb_close_command cbxcbr1_exe_cl darrec1_close_cb guid-186fe757-e2ed-483b-a0f9-7cf97278bc0c v1 en figure 39: circuit breaker control logic: signals for the closing coil of circuit breaker 1 or6 b1 b2 b3 b4 b5 b6 o cb_open_command trpptrc1_trip cbxcbr1_exe_op darrec1_open_cb guid-f8b92f5f-5...

  • Page 74

    3.3.3.5 functional diagrams for measurement functions the phase current inputs to the ied are measured by the three-phase current measurement function cmmxu1. The current input is connected to the x120 card in the back panel. Similarly, the sequence current measurement csmsqi1 measures the sequence ...

  • Page 75

    3.3.3.6 functional diagrams for i/o and alarm leds x120_bi3_cb_opened x120_bi2_cb_closed x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input 2 x120 (aim).X120-input 3 guid-1cc3270b-3a49-43c1-8c2f-0dfaf37fad58 v1 en figure 49: default binary inputs - x120 cb_close_command ccbrbrf1_...

  • Page 76

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o intrptef1_operate pdnsptoc1_operate efhptoc1_operate def_operate efpadm_operate wpwde_operate rovptov_operate t1pttr1_alarm phxptoc_operate nsptoc_operate...

  • Page 77

    Led10 ok alarm reset arcsarc_operate led9 ok alarm reset tcsscbr_alarm led7 ok alarm reset disturb_record_triggered led11 ok alarm reset darrec1_inpro led6 ok alarm reset ccbrbrf1_trbu guid-781e66e9-ce48-4da6-8159-86bed9295d7c v1 en figure 51: default led connection 3.3.3.7 other functions the confi...

  • Page 78

    Signal designation within the ied enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using pcm600. 3.4.2 functions condition monitoring and supervision or and control and indication 1) meas...

  • Page 79

    Table 16: default connections for binary inputs binary input description x110-bi2 directional earth-fault protection's basic angle control x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service position) indi...

  • Page 80

    Led description 9 trip circuit supervision alarm 10 arc protection operate 11 autoreclose in progress 3.4.2.2 default disturbance recorder settings table 19: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 uo 6 - 7 - 8 - 9 - 10 - 11 - 12 - table 20: default ...

  • Page 81

    Channel id text level trigger mode 11 efhptoc1 - start positive or rising 12 pdnsptoc1 - start positive or rising 13 t1pttr1 - start positive or rising 14 rovptov1 - start positive or rising 15 rovptov2 - start positive or rising 16 rovptov3 - start positive or rising 17 ccbrbrf1 - trret level trigg...

  • Page 82

    Channel id text level trigger mode 34 darrec1 - unsuc recl level trigger off 34 x120bi1 - ext oc blocking level trigger off 35 x120bi2 - cb closed level trigger off 36 x120bi3 - cb opened level trigger off 3.4.3 functional diagrams the functional diagrams describe the default input, output, alarm le...

  • Page 83

    Phiptoc1 block ena_mult operate start phlptoc1 block ena_mult operate start phhptoc1 block ena_mult operate start phhptoc2 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o phiptoc1_operate phiptoc1_operate phlptoc1_operate phlptoc1_operate phhptoc1_operate phhptoc1_operate phhptoc2_operate phhpt...

  • Page 84

    Inrphar1 block blk2h inrphar1_blk2h guid-ed765a4f-9f2b-4546-be25-269cbabc0f9d v1 en figure 55: inrush detector function two negative-sequence overcurrent protection stages nsptoc1 and nsptoc2 are provided for phase unbalance protection. These functions are used to protect the feeder against phase un...

  • Page 85

    Deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate deflpdef1_operate deflpdef2_operate deflpdef1_start deflpdef2_start defhpdef1_start x110_bi2_rca_control x110_bi2_rca_control x110_bi2_rca_co...

  • Page 86

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start wpwde_operate guid-a26e1e55-4059-462c-942f...

  • Page 87

    A dedicated non-directional earth-fault protection block efhptoc protects from double earth-fault situations in isolated or compensated networks. The protection function uses the calculated residual current originating from the phase currents. Efhptoc1 block ena_mult operate start efhptoc1_operate e...

  • Page 88

    Three arc protection arcsarc1...3 stages are included as an optional function. The arc protection offers individual function blocks for three arc sensors that can be connected to the ied. Each arc protection function block has two different operation modes, that is, with or without the phase and res...

  • Page 89

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 90

    The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connected to the cb spring charged binary inputs in this configuration. The open command from the autorecloser is connected directly to the bin...

  • Page 91

    Rovptov1 block operate start rovptov2 block operate start rovptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o rovptov1_operate rovptov1_operate rovptov2_operate rovptov2_operate rovptov3_operate rovptov3_operate rovptov1_start rovptov2_start rovptov3_start rovptov_operate guid-23a63895-a476-4096-bd...

  • Page 92

    Assigned to rst_lkout input of both the trip logic to enable external reset with a push button. Three other trip logics trpptrc3...4 are also available if the ied is ordered with high speed binary outputs options. Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4...

  • Page 93

    Depending on the parameter settings. Additionally, the selected signals from different functions and few binary inputs are also connected. Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 ...

  • Page 94

    Or b1 b2 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o sscbr1_trv_t_op_alm sscbr1_trv_t_cl_alm sscbr1_spr_chr_alm sscbr1_opr_alm sscbr1_opr_lo sscbr1_ipow_alm sscbr1_ipow_lo sscbr1_cb_life_alm sscbr1_mon_alm sscbr1_pres_alm sscbr1_pres_lo sscbr1_alarms guid-ed84a0bd-a150-4bba-8a82-8ac4b3cae673 v...

  • Page 95

    Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm tcsscbr2_alarm tcsscbr2_alarm tcsscbr_blocking tcsscbr_blocking tcsscbr_alarm guid-0b65c9fd-deb8-4895-82a8-725a1a3e7896 v1 en figure 75: trip circuit supervision function or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi3...

  • Page 96

    Disconnector or breaker truck and earth-switch position status, status of the trip logics, gas pressure alarm and circuit-breaker spring charging status. The okpos output from dcsxswi defines whether the disconnector or breaker truck is either open (in test position) or close (in service position). ...

  • Page 97

    Not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_bi3_gas_pressure_alarm dcsxswi1_okpos essxswi1_openpos x110_bi4_cb_spring_charged guid-3c981db3-efc0-490c-ae96-2c5b16cc7e00 v1 en figure 82: circuit breaker close enable logic the configurati...

  • Page 98

    The residual voltage input is connected to the x120 card in the back panel and is measured by the residual voltage measurement resvmmxu1. The measurements can be seen from the lhmi and they are available under the measurement option in the menu selection. Based on the settings, function blocks can g...

  • Page 99

    3.4.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi2_rca_control x...

  • Page 100

    Upsteam_oc_blocking oc_operate_pulse ef_operate_pulse trpptrc3_trip trpptrc4_trip trpptrc5_trip x110 (bio).X110-so1 x110 (bio).X110-so2 x110 (bio).X110-so3 x110 (bio-h).X110-hso1 x110 (bio-h).X110-hso2 x110 (bio-h).X110-hso3 guid-3a0c4edb-878a-4282-86b2-894775bbeee5 v2 en figure 93: default binary o...

  • Page 101

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o intrptef1_operate pdnsptoc1_operate efhptoc1_operate def_operate efpadm_operate wpwde_operate rovptov_operate t1pttr1_alarm phxptoc_operate nsptoc_operate...

  • Page 102

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset ccbrbrf1_trbu darrec1_inpro disturb_record_triggered tcsscbr_alarm sscbr1_alarms arcsarc_operate guid-5545434b-1c8a-45a3-992c-567617dae58a v1 en figure 95: default led connection...

  • Page 103

    3.4.3.8 other functions the configuration includes few instances of multipurpose protection function mapgapc, high-impedance fault detection function phiz, runtime counter for machines and devices mdsopt and different types of timers and control functions. These functions are not included in applica...

  • Page 104

    3.5.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and ...

  • Page 105

    Table 21: default connections for binary inputs binary input description x120-bi1 blocking of overcurrent instantaneous stage x120-bi2 circuit breaker closed indication x120-bi3 circuit breaker open indication x120-bi4 reset of master trip lockout table 22: default connections for binary outputs bin...

  • Page 106

    Channel description 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - table 25: default disturbance recorder binary channels channel id text level trigger mode 1 phlptoc1 - start positive or rising 2 phhptoc1 - start positive or rising 3 phhptoc2 - start positive or rising 4 phiptoc1 - start positive or rising 5 n...

  • Page 107

    Channel id text level trigger mode 22 inrphar1 - blk2h level trigger off 23 t1pttr1 - operate level trigger off 24 arcsarc1 - arc flt det level trigger off arcsarc2 - arc flt det arcsarc3 - arc flt det 25 arcsarc1 - operate positive or rising 26 arcsarc2 - operate positive or rising 27 arcsarc3 - op...

  • Page 108

    Phiptoc1 block ena_mult operate start phlptoc1 block ena_mult operate start phhptoc1 block ena_mult operate start phhptoc2 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o phiptoc1_operate phiptoc1_operate phlptoc1_operate phlptoc1_operate phhptoc1_operate phhptoc1_operate phhptoc2_operate phhpt...

  • Page 109

    Nsptoc1 block ena_mult operate start nsptoc2 block ena_mult operate start or b1 b2 o nsptoc1_operate nsptoc1_operate nsptoc2_operate nsptoc2_operate nsptoc1_start nsptoc2_start nsptoc_operate guid-a0e1f246-e42c-4732-b0de-bdc3f4a16cdc v1 en figure 100: negative sequence overcurrent protection functio...

  • Page 110

    Phase discontinuity protection pdnsptoc1 protects from interruptions in the normal three-phase load supply, for example, in downed conductor situations. Pdnsptoc1 block operate start pdnsptoc1_operate pdnsptoc1_start guid-72dbeefc-1ad7-4930-a949-a340cf2767aa v1 en figure 103: phase discontinuity pro...

  • Page 111

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 112

    Darrec1 init_1 init_2 init_3 init_4 init_5 init_6 del_init_2 del_init_3 del_init_4 blk_recl_t blk_rclm_t blk_therm cb_pos cb_ready inc_shotp inhibit_recl recl_on sync open_cb close_cb cmd_wait inpro locked prot_crd unsuc_recl ar_on ready active or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or b1 b...

  • Page 113

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_operate eflptoc1_operate efhptoc1_operate efiptoc1_...

  • Page 114

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 115

    Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm tcsscbr2_alarm tcsscbr2_alarm tcsscbr_blocking tcsscbr_blocking tcsscbr_alarm guid-74bd5a42-e773-4714-9edf-97f22b96687a v1 en figure 112: trip circuit supervision function or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi...

  • Page 116

    Cbxcbr1 posopen posclose ena_open ena_close blk_open blk_close au_open au_close trip sync_ok sync_itl_byp selected exe_op exe_cl op_req cl_req openpos closepos okpos open_enad close_enad true x120_bi3_cb_opened x120_bi2_cb_closed cbxcbr1_ena_close cbxcbr1_exe_cl cbxcbr1_exe_op false cbxcbr1_au_open ...

  • Page 117

    And b1 b2 o and b1 b2 o or b1 b2 o false false cbxcbr1_au_close control_local control_remote guid-d25a5ad0-e5bf-476a-b844-9701d5ec44e7 v1 en figure 118: external closing command for circuit breaker and b1 b2 o and b1 b2 o or b1 b2 o false false cbxbcr1_au_open control_local control_remote guid-defd1...

  • Page 118

    Fltrfrc1 block cb_clrd guid-f70a913a-4b5d-45d2-b12f-981d54dca89e v2 en figure 123: other measurements: data monitoring 3.5.3.6 functional diagrams for i/o and alarm leds x120_bi3_cb_opened x120_bi2_cb_closed x120_bi4_rst_lockout x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input ...

  • Page 119

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or b1 b2 o eflptoc2_operate pdnsptoc1_operate t1pttr1_alarm phxptoc_operate efxptoc_operate nsptoc_operate guid-39c29981-e86d-4570-b841-cf19a89767cf v1 en 1mrs756378 s section 3 ref615 standard config...

  • Page 120

    Led9 ok alarm reset led10 ok alarm reset tcsscbr_alarm arcsarc_operate led7 ok alarm reset disturb_record_triggered led11 ok alarm reset darrec1_inpro led6 ok alarm reset ccbrbrf1_trbu guid-a2456ab1-db3f-4717-b4e8-7bfcbf271d1f v1 en figure 126: default led connection 3.5.3.7 other functions the conf...

  • Page 121

    Signal designation within the ied enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using pcm600. 3.6.2 functions condition monitoring and supervision or and control and indication 1) meas...

  • Page 122

    Table 26: default connections for binary inputs binary input description x110-bi2 autoreclose external start command x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service position) indication x110-bi6 circui...

  • Page 123

    Led description 9 trip circuit supervision alarm 10 arc protection operate 11 autoreclose in progress 3.6.2.2 default disturbance recorder settings table 29: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - table 30: default d...

  • Page 124

    Channel id text level trigger mode 16 phiptoc1 - operate level trigger off phhptoc1 - operate phhptoc2 - operate phlptoc1 - operate 17 nsptoc1 - operate level trigger off nsptoc2 - operate 18 eflptoc1 - operate level trigger off efhptoc1 - operate efiptoc1 - operate 19 x110bi2 - ext start autoreclos...

  • Page 125

    The ied offers six different settings groups which can be set based on individual needs. Each group can be activated or deactivated using the setting group settings available in the ied. Depending on the communication protocol the required function block needs to be instantiated in the configuration...

  • Page 126

    Or6 b1 b2 b3 b4 b5 b6 o upsteam_oc_blocking phhptoc2_start guid-6b581162-38e0-40fb-95dc-3360616da749 v1 en figure 129: upstream blocking logic the output blk2h of three-phase inrush detector inrphar1 enables either blocking the function or multiplying the active settings for any of the available ove...

  • Page 127

    Efhptoc1 block ena_mult operate start eflptoc1 block ena_mult operate start efiptoc1 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o eflptoc1_operate eflptoc1_operate efhptoc1_operate efhptoc1_operate efiptoc1_operate efiptoc1_operate eflptoc1_start efiptoc1_start efhptoc1_start efxptoc_operate...

  • Page 128

    Circuit breaker failure protection ccbrbrf1 is initiated via the start input by number of different protection functions available in the ied. The breaker failure protection function offers different operating modes associated with the circuit breaker position and the measured phase and residual cur...

  • Page 129

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 130

    The autoreclosing function can be inhibited with the inhibit_recl input. By default, few selected protection function operations are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The ...

  • Page 131

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 general_start general_operate phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_...

  • Page 132

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_operate eflptoc1_operate efhptoc1_operate efiptoc1_...

  • Page 133

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 134

    Sscbr1 block posopen posclose open_cb_exe close_cb_exe pres_alm_in pres_lo_in spr_chr_st spr_chr rst_ipow rst_cb_wear rst_trv_t rst_spr_t trv_t_op_alm trv_t_cl_alm spr_chr_alm opr_alm opr_lo ipow_alm ipow_lo cb_life_alm mon_alm pres_alm pres_lo openpos invalidpos closepos cb_close_command cb_open_co...

  • Page 135

    It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Set the parameters for tcsscbr properly. Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm tc...

  • Page 136

    Essxswi1 posopen posclose openpos closepos okpos essxswi1_openpos x110_bi8_es1_opened x110_bi7_es1_closed guid-5602152f-6f87-4d49-86af-e4968e4b88bb v1 en figure 150: earthing switch 1 the circuit breaker closing is enabled when the ena_close input is activated. The input can be activated by the conf...

  • Page 137

    Or6 b1 b2 b3 b4 b5 b6 o cb_open_command cbxcbr1_exe_op trpptrc1_trip darrec1_open_cb guid-26be8b84-99df-44e7-ba2e-09efc6a4ea76 v1 en figure 153: signals for opening coil of circuit breaker 1 not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_...

  • Page 138

    3.6.3.5 functional diagrams for measurement functions the phase current inputs to the ied are measured by the three-phase current measurement function cmmxu1. The current input is connected to the x120 card in the back panel. The sequence current measurement csmsqi1 measures the sequence current and...

  • Page 139

    3.6.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi2_ext_start_aut...

  • Page 140

    Upsteam_oc_blocking oc_operate_pulse ef_operate_pulse trpptrc3_trip trpptrc4_trip trpptrc5_trip x110 (bio).X110-so1 x110 (bio).X110-so2 x110 (bio).X110-so3 x110 (bio-h).X110-hso1 x110 (bio-h).X110-hso2 x110 (bio-h).X110-hso3 guid-23f52e72-342a-4629-89cc-fc401cd94b21 v1 en figure 164: binary outputs ...

  • Page 141

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or b1 b2 o eflptoc2_operate pdnsptoc1_operate phxptoc_operate efxptoc_operate t1pttr1_alarm nsptoc_operate guid-b26bbb64-d189-4246-a5a7-db8fc8e86445 v1 en 1mrs756378 s section 3 ref615 standard config...

  • Page 142

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset ccbrbrf1_trbu darrec1_inpro disturb_record_triggered tcsscbr_alarm sscbr1_alarms arcsarc_operate guid-45ba8cde-2d5a-4bfc-aeb7-b9d3c1d044f9 v1 en figure 166: default led connectio...

  • Page 143

    3.6.3.8 other functions the configuration includes few instances of multi-purpose protection function mapgapc, high impedance fault detection function phiz, runtime counter mdsopt and different types of timers and control functions. These functions are not included in application configuration but t...

  • Page 144

    3.7.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and ...

  • Page 145

    Table 31: default connections for binary inputs binary input description x110-bi1 mcb open x110-bi2 directional earth-fault protection's basic angle control x110-bi3 circuit breaker low gas pressure alarm x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service p...

  • Page 146

    Led description 8 circuit breaker condition monitoring alarm 9 supervision alarm 10 arc fault detected 11 autoreclose in progress 3.7.2.2 default disturbance recorder settings table 34: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 uo 6 u1 7 u2 8 u3 9 - 10...

  • Page 147

    Channel id text level trigger mode 10 intrptef1 - start positive or rising 11 efhptoc1 - start positive or rising 12 pdnsptoc1 - start positive or rising 13 t1pttr1 - start positive or rising 14 rovptov1 - start positive or rising 15 rovptov2 - start positive or rising 16 rovptov3 - start positive o...

  • Page 148

    Channel id text level trigger mode 32 darrec1 - close cb level trigger off darrec1 - unsuc recl 33 darrec1 - inpro level trigger off 34 x120bi1 - ext oc blocking level trigger off 35 x120bi2 - cb closed level trigger off 36 x120bi3 - cb opened level trigger off 37 seqspvc1 - fusef3ph level trigger o...

  • Page 149

    Phiptoc1 block ena_mult operate start phlptoc1 block ena_mult operate start phhptoc1 block ena_mult operate start phhptoc2 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o phiptoc1_operate phiptoc1_operate phlptoc1_operate phlptoc1_operate phhptoc1_operate phhptoc1_operate phhptoc2_operate phhpt...

  • Page 150

    Inrphar1 block blk2h inrphar1_blk2h guid-b5386a2a-119f-44af-ad39-d601263bf734 v1 en figure 171: inrush detector function two negative-sequence overcurrent protection stages nsptoc1 and nsptoc2 are provided for phase unbalance protection. These functions are used to protect the feeder against phase u...

  • Page 151

    Or6 b1 b2 b3 b4 b5 b6 o deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate defhpdef1_operate deflpdef1_operate deflpdef1_operate deflpdef2_operate deflpdef2_operate defhpdef1_start deflpdef2_s...

  • Page 152

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start x110_bi2_rca_control x110_bi2_rca_control ...

  • Page 153

    Non-directional earth-fault protection efhptoc protects against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. The function is blocked in case of detection of a failure in secondary...

  • Page 154

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu x120_bi2_cb_closed phiptoc1_operate phhptoc1_operate phhptoc2_operate defhpdef1_operate deflpdef2_operate efpadm2_operate efpadm3_operate wpwde2_operate...

  • Page 155

    Trpptrc3 block operate rst_lkout trip cl_lkout trpptrc4 block operate rst_lkout trip cl_lkout trpptrc5 block operate rst_lkout trip cl_lkout trpptrc3_trip trpptrc4_trip trpptrc5_trip arcsarc1_operate arcsarc2_operate arcsarc3_operate x120_bi4_rst_lockout x120_bi4_rst_lockout x120_bi4_rst_lockout gui...

  • Page 156

    Darrec1 init_1 init_2 init_3 init_4 init_5 init_6 del_init_2 del_init_3 del_init_4 blk_recl_t blk_rclm_t blk_therm cb_pos cb_ready inc_shotp inhibit_recl recl_on sync open_cb close_cb cmd_wait inpro locked prot_crd unsuc_recl ar_on ready active or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 ...

  • Page 157

    Rovptov1 block operate start rovptov2 block operate start rovptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o rovptov1_operate rovptov1_operate rovptov2_operate rovptov2_operate rovptov3_operate rovptov3_operate rovptov1_start rovptov2_start rovptov3_start rovptov_operate guid-7d97d55f-a89b-47fb-9b...

  • Page 158

    Lockout and latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, binary input x120:bi4 has been assigned to rst_lkout input of both the trip logic to enable external reset with a push button. Three other trip logics trpptrc3...4 are als...

  • Page 159

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_ope...

  • Page 160

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 161

    The circuit-breaker condition monitoring function sscbr1 supervises the switch status based on the connected binary input information and the measured current levels. Sscbr1 introduces various supervision methods. Sscbr1 block posopen posclose open_cb_exe close_cb_exe pres_alm_in pres_lo_in spr_chr_...

  • Page 162

    Blocked by the master trip trpptrc1 and trpptrc2 and the circuit breaker open signal. It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Tcsscbr1 block alarm tcsscbr2 block alar...

  • Page 163

    Essxswi1 posopen posclose openpos closepos okpos essxswi1_openpos x110_bi8_es1_opened x110_bi7_es1_closed guid-80a3714d-28ab-41ed-909c-8b77d552115a v1 en figure 197: earthing switch 1 the circuit breaker closing is enabled when the ena_close input is activated. The input can be activated by the conf...

  • Page 164

    Or6 b1 b2 b3 b4 b5 b6 o cb_open_command cbxcbr1_exe_op trpptrc1_trip darrec1_open_cb guid-adccb058-4d03-49fe-b434-c81296bf655d v1 en figure 200: circuit breaker control logic: signals for opening coil of circuit breaker 1 not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out trpptrc2_trip cbxcbr...

  • Page 165

    And b1 b2 o and b1 b2 o or b1 b2 o false false cbxcbr1_au_close control_local control_remote guid-d63ae948-455c-498a-824f-6ef494c57c06 v1 en figure 203: external closing command for circuit breaker 1 and b1 b2 o and b1 b2 o or b1 b2 o false false cbxbcr1_au_open control_local control_remote guid-53b...

  • Page 166

    Csmsqi1 guid-6a3f5e6f-1761-48a6-95b3-ed80c4c52230 v1 en figure 206: current measurement: sequence current measurement rescmmxu1 block high_alarm high_warn guid-069dc247-81c1-42c2-bcda-b0bf14a689d1 v1 en figure 207: current measurement: residual current measurement vmmxu1 block high_alarm high_warn l...

  • Page 167

    Ldprlrc1 rstmem mem_warn mem_alarm guid-1585f0d5-fc5a-4d1d-bf63-661830ad6291 v2 en figure 214: other measurement: load record profile 3.7.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm...

  • Page 168

    X120_bi3_cb_opened x120_bi2_cb_closed x120_bi4_rst_lockout x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input 2 x120 (aim).X120-input 3 x120 (aim).X120-input 4 guid-a7c227b5-59d1-4e93-9b61-aad367d93dc0 v1 en figure 216: binary inputs - x120 terminal block upsteam_oc_blocking oc_o...

  • Page 169

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o intrptef1_operate pdnsptoc1_operate efhptoc1_operate defxpdef_operate rovptov_operate phxptoc_operate t1pttr1_alarm nsptoc_operate guid-c8cfa43b-974d-4635...

  • Page 170

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu darrec1_inpro seqspvc1_fusef_3ph seqspvc1_fusef_u disturb_record_triggered sscbr1_alarms tcsscbr_alarm ccspvc1_alarm arcsarc_operate guid-9c...

  • Page 171

    3.7.3.8 other functions the configuration includes few instances of multipurpose protection mapgapc, high -impedance fault detection phiz, runtime counter for machines and devices mdsopt and different types of timers and control functions. These functions are not included in application configuratio...

  • Page 172

    3.8.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and ...

  • Page 173

    Table 36: default connections for binary inputs binary input description x110-bi1 mcb open x110-bi2 directional earth-fault protection's basic angle control x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (serv...

  • Page 174

    Led description 7 disturbance recorder triggered 8 circuit breaker condition monitoring alarm 9 supervision alarm 10 arc fault detected 11 autoreclose in progress 3.8.2.2 default disturbance recorder settings table 39: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il...

  • Page 175

    Channel id text level trigger mode 9 efpadm3 - start positive or rising wpwde3 - start 10 intrptef1 - start positive or rising 11 efhptoc1 - start positive or rising 12 pdnsptoc1 - start positive or rising 13 t1pttr1 - start positive or rising 14 phptov1 - start positive or rising 15 phptov2 - start...

  • Page 176

    Channel id text level trigger mode 35 phptov1 - operate level trigger off phptov2 - operate phptov3 - operate 36 phptuv1 - operate level trigger off phptuv2 - operate phptuv3 - operate 37 rovptov1 - operate level trigger off rovptov2 - operate rovptov3 - operate psptuv1 - operate nsptov2 - operate 3...

  • Page 177

    The phase voltages to the ied are fed from a voltage transformer. The residual voltage to the ied is fed from either residually connected vts, an open delta connected vt or internally calculated. The ied offers six different settings groups which can be set based on individual needs. Each group can ...

  • Page 178

    Dphhpdoc1 block ena_mult non_dir operate start dphlpdoc1 block ena_mult non_dir operate start dphlpdoc2 block ena_mult non_dir operate start or6 b1 b2 b3 b4 b5 b6 o dphlpdoc2_operate dphlpdoc2_operate dphhpdoc1_operate dphhpdoc1_operate dphlpdoc1_operate dphlpdoc1_operate dphlpdoc1_start dphlpdoc2_s...

  • Page 179

    Feeder against phase unbalance. Both the negative sequence overcurrent protections are blocked in case of detection in failure in secondary circuit of current transformer. Nsptoc1 block ena_mult operate start nsptoc2 block ena_mult operate start or b1 b2 o nsptoc1_operate nsptoc1_operate nsptoc2_ope...

  • Page 180

    Or6 b1 b2 b3 b4 b5 b6 o deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate defhpdef1_operate deflpdef1_operate deflpdef1_operate deflpdef2_operate deflpdef2_operate deflpdef1_start deflpdef2_s...

  • Page 181

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start x110_bi2_rca_control x110_bi2_rca_control ...

  • Page 182

    Non-directional (cross-country) earth-fault protection, using calculated io, efhptoc1 protects against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. The function is blocked in case...

  • Page 183

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu x120_bi2_cb_closed phiptoc1_operate dphhpdoc1_operate dphlpdoc1_operate efpadm2_operate efpadm3_operate defhpdef1_operate deflpdef2_operate wpwde2_opera...

  • Page 184

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 185

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connect...

  • Page 186

    Phptov1 block operate start phptov2 block operate start phptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o phptov1_operate phptov1_operate phptov2_operate phptov2_operate phptov3_operate phptov3_operate phptov1_start phptov2_start phptov3_start phptov_operate guid-a11ea1d0-3a52-4887-9cc5-3c30268d29...

  • Page 187

    The residual overvoltage protection rovptov provides earth-fault protection by detecting an abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. Rovptov1 block operate start rovptov2 block operat...

  • Page 188

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 ...

  • Page 189

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 190

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 191

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 192

    Set the parameters for sscbr1 properly. Sscbr1 block posopen posclose open_cb_exe close_cb_exe pres_alm_in pres_lo_in spr_chr_st spr_chr rst_ipow rst_cb_wear rst_trv_t rst_spr_t trv_t_op_alm trv_t_cl_alm spr_chr_alm opr_alm opr_lo ipow_alm ipow_lo cb_life_alm mon_alm pres_alm pres_lo openpos invalid...

  • Page 193

    Not in out x110_bi4_cb_spring_charged cb_spring_discharged guid-176f56d4-41ca-4646-aaa1-38e65632d403 v1 en figure 250: logic for start of circuit breaker spring charging two separate trip circuit supervision functions are included: tcsscbr1 for power output x100:po3 and tcsscbr2 for power output x10...

  • Page 194

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi3_cb_opened trpptrc1_trip tcsscbr_blocking guid-4b5c2a2d-72e3-4848-b40b-da6d221a4fac v1 en figure 252: logic for blocking of trip circuit supervision 3.8.3.4 functional diagrams for control and interlocking two types of disconnector and earthing switch fu...

  • Page 195

    Cbxcbr1 posopen posclose ena_open ena_close blk_open blk_close au_open au_close trip sync_ok sync_itl_byp selected exe_op exe_cl op_req cl_req openpos closepos okpos open_enad close_enad true x120_bi3_cb_opened x120_bi2_cb_closed cbxcbr1_ena_close cbxcbr1_exe_cl cbxcbr1_exe_op cbxcbr1_blk_close fals...

  • Page 196

    Or6 b1 b2 b3 b4 b5 b6 o cbxcbr1_blk_close t1pttr1_blk_close guid-c8d94dd3-db60-4456-b663-a45877ae2d18 v1 en figure 259: circuit breaker 1 close blocking logic the configuration includes the logic for generating the circuit breaker external closing and opening command with the ied in local or remote ...

  • Page 197

    Voltage and the residual voltage measurement resvmmxu1 measures the residual voltage. The measurements can be seen in the lhmi and they are available under the measurement option in the menu selection. Based on the settings, function blocks can generate low alarm or warning and high alarm or warning...

  • Page 198

    Pemmxu1 rstacm guid-9d027ef7-0ce3-4e0b-8b57-3a4392363a46 v1 en figure 268: other measurement: three-phase power and energy measurement fltrfrc1 block cb_clrd guid-848c6501-5e08-40fd-823d-11dc11ffac29 v2 en figure 269: other measurement: data monitoring ldprlrc1 rstmem mem_warn mem_alarm guid-54d8f3d...

  • Page 199

    3.8.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi2_rc...

  • Page 200

    X120_bi3_cb_opened x120_bi2_cb_closed x120_bi4_rst_lockout x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input 2 x120 (aim).X120-input 3 x120 (aim).X120-input 4 guid-f44b3ffd-f2e1-4535-8500-ec14611c708e v1 en figure 272: default binary inputs - x120 upsteam_oc_blocking oc_operate_...

  • Page 201

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o phiptoc1_operate intrptef1_operate pdnsptoc1_operate efhptoc1_operate psptuv1_operate nsptov1_operate phptuv_operate phptov_operat...

  • Page 202

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu seqspvc1_fusef_u seqspvc1_fusef_3ph darrec1_inpro sscbr1_alarms disturb_record_triggered tcsscbr_alarm ccspvc1_alarm arcsarc_operate guid-cb...

  • Page 203

    Tpgapc2 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o oc_operate_pulse ef_operate_pulse phiptoc1_operate intrptef1_operate efhptoc1_operate dphxpdoc_operate defxpdef_operate efpadm_operate rovptov_operate wpwde_operate guid-ef44331e-734b-42a8-90d7-66a4db74d377 v1 en figure 276: timer logic fo...

  • Page 204

    3.9.2 functions condition monitoring and supervision or and feeder protection and control relay standard configuration protection local hmi r l clear esc i o configuration a system hmi time authorization r l clear esc i o u12 0. 0 kv p 0.00 kw q 0.00 kvar il2 0 a a remarks optional function no. Of in...

  • Page 205

    Table 41: default connections for binary inputs binary input description x110-bi1 circuit breaker closed indication x110-bi2 circuit breaker open indication x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (serv...

  • Page 206

    3.9.2.2 default disturbance recorder settings table 44: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 u1 6 u2 7 u3 8 - 9 - 10 - 11 - 12 - table 45: default disturbance recorder binary channels channel id text level trigger mode 1 dphlpdoc1 - start positive...

  • Page 207

    Channel id text level trigger mode 17 nsptov1 - trbu positive or rising 18 phptuv1 - start positive or rising 19 phptuv2 - start positive or rising 20 phptuv3 - start positive or rising 21 rovptov1 - start positive or rising 22 rovptov2 - start positive or rising 23 rovptov3 - start positive or risi...

  • Page 208

    Channel id text level trigger mode 36 seqspvc1 - fusef3ph level trigger off 37 seqspvc1 - fusefu level trigger off 38 ccspvc1 - fail level trigger off 39 x110bi1 - cb closed level trigger off 40 x110bi2 - cb opened level trigger off 41 arcsarc1 - arc flt det level trigger off arcsarc2 - arc flt det ...

  • Page 209

    Four overcurrent stages are offered for overcurrent and short-circuit protection. Three of them include directional functionality dphxpdoc. Phiptoc1 block ena_mult operate start phiptoc1_operate phiptoc1_start guid-9e341f53-8ab2-4a2c-b776-b26d19cab8f9 v1 en figure 279: overcurrent protection functio...

  • Page 210

    The output blk2h of three-phase inrush detector inrphar1 enables either blocking the function or multiplying the active settings for any of the available overcurrent or earth-fault function blocks. Inrphar1 block blk2h inrphar1_blk2h guid-48cccd5a-6f4f-4ff7-9d75-85e2b0ddd8a9 v1 en figure 282: inrush...

  • Page 211

    Or6 b1 b2 b3 b4 b5 b6 o deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate defhpdef1_operate deflpdef1_operate deflpdef1_operate deflpdef2_operate deflpdef2_operate deflpdef1_start deflpdef2_s...

  • Page 212

    Efpadm1 block release operate start efpadm2 block release operate start efpadm3 block release operate start or6 b1 b2 b3 b4 b5 b6 o efpadm1_operate efpadm1_operate efpadm2_operate efpadm2_operate efpadm3_operate efpadm3_operate efpadm1_start efpadm2_start efpadm3_start efpadm_operate guid-80b32305-0...

  • Page 213

    T1pttr1 blk_opr ena_mult temp_amb operate start alarm blk_close t1pttr1_blk_close t1pttr1_start t1pttr1_operate t1pttr1_alarm guid-0b72f2eb-41ef-44cd-9dd4-ca416dfbf0cb v1 en figure 289: thermal overcurrent protection function circuit breaker failure protection ccbrbrf1 is initiated via the start inp...

  • Page 214

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 215

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connect...

  • Page 216

    Phptov1 block operate start phptov2 block operate start phptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o phptov1_operate phptov1_operate phptov2_operate phptov2_operate phptov3_operate phptov3_operate phptov1_start phptov2_start phptov3_start phptov_operate guid-becfc2b1-ef62-45b3-87e3-0400340a8b...

  • Page 217

    The residual overvoltage protection rovptov provides earth-fault protection by detecting an abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. Rovptov1 block operate start rovptov2 block operat...

  • Page 218

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 ...

  • Page 219

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 220

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 221

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or...

  • Page 222

    Circuit-breaker condition monitoring sscbr1 supervises the switch status based on the connected binary input information and the measured current levels. Sscbr1 introduces various supervision methods. Set the parameters for sscbr1 properly. Sscbr1 block posopen posclose open_cb_exe close_cb_exe pres...

  • Page 223

    It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Set the parameters for tcsscbr1 properly. Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm t...

  • Page 224

    Essxswi1 posopen posclose openpos closepos okpos essxswi1_openpos x110_bi8_es1_opened x110_bi7_es1_closed guid-e6cdefac-d921-4392-a83c-d5366b8a41ba v1 en figure 310: earth switch control logic the circuit breaker closing is enabled when the ena_close input is activated. The input can be activated us...

  • Page 225

    Or6 b1 b2 b3 b4 b5 b6 o cb_open_command cbxcbr1_exe_op trpptrc1_trip darrec1_open_cb guid-63db00f4-441b-4b7e-8f02-500921b8c9c6 v1 en figure 313: signals for opening coil of circuit breaker 1 not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_...

  • Page 226

    And b1 b2 o and b1 b2 o or b1 b2 o false false cbxcbr1_au_close control_local control_remote guid-41def2a2-16e7-4c8c-a8c6-81f1d751ec08 v1 en figure 316: external closing command for circuit breaker 1 and b1 b2 o and b1 b2 o or b1 b2 o false false cbxbcr1_au_open control_local control_remote guid-b21...

  • Page 227

    Csmsqi1 guid-03a8d15a-b365-41a6-9888-177a22d366cb v1 en figure 319: current measurement: sequence current measurement rescmmxu1 block high_alarm high_warn guid-9a19a4d2-2931-4710-8ad2-9ce31907a4ac v1 en figure 320: current measurement: residual current measurement vmmxu1 block high_alarm high_warn l...

  • Page 228

    3.9.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi2_cb_opened x110_bi1_cb_closed x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_...

  • Page 229

    Upsteam_oc_blocking oc_operate_pulse ef_operate_pulse voltage_operate_pulse trpptrc3_trip trpptrc4_trip trpptrc5_trip x110 (bio).X110-so1 x110 (bio).X110-so2 x110 (bio).X110-so3 x110 (bio).X110-so4 x110 (bio-h).X110-hso1 x110 (bio-h).X110-hso2 x110 (bio-h).X110-hso3 guid-a5f194c9-0208-467c-a115-6bf1...

  • Page 230

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o phiptoc1_operate efhptoc1_operate psptuv1_operate nsptov1_operate pdnsptoc1_operate phptov_operate phptuv_operate dphxpdoc_operate...

  • Page 231

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu seqspvc1_fusef_u seqspvc1_fusef_3ph darrec1_inpro sscbr1_alarms disturb_record_triggered tcsscbr_alarm ccspvcf1_alarm arcsarc_operate guid-a...

  • Page 232

    Tpgapc3 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o voltage_operate_pulse psptuv1_operate nsptov1_operate phptuv_operate phptov_operate guid-600e062d-9aab-444b-a7ed-4a8ff894c55a v1 en figure 332: timer logic for voltage operate pulse 3.9.3.8 other functions the configuration includes few instances of ...

  • Page 233

    3.10.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and...

  • Page 234

    Table 46: default connections for binary inputs binary input description x110-bi1 busbar vt secondary mcb open x110-bi2 line vt secondary mcb open x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service positi...

  • Page 235

    Led description 7 disturbance recorder triggered 8 circuit breaker condition monitoring alarm 9 supervision alarm 10 arc fault detected 11 autoreclose in progress 3.10.2.2 default disturbance recorder settings table 49: default disturbance recorder analog channels channel description 1 il1 2 il2 3 i...

  • Page 236

    Channel id text level trigger mode 14 phptov3 - start positive or rising 15 phptuv1 - start positive or rising 16 phptuv2 - start positive or rising 17 phptuv3 - start positive or rising 18 rovptov1 - start positive or rising 19 rovptov2 - start positive or rising 20 rovptov3 - start positive or ris...

  • Page 237

    Channel id text level trigger mode 38 ccspvc1 - fail level trigger off 39 x120bi1 - ext oc blocking level trigger off 40 x120bi2 - cb closed level trigger off 41 x120bi3 - cb opened level trigger off 42 secrsyn1 - sync inpro level trigger off 43 secrsyn1 - sync ok level trigger off 44 secrsyn1 - cl ...

  • Page 238

    3.10.3.1 functional diagrams for protection the functional diagrams describe the ieds protection functionality in detail and according to the factory set default connections. Four non-directional overcurrent stages are offered for overcurrent and short-circuit protection. Three-phase non-directional...

  • Page 239

    The output blk2h of three-phase inrush detector inrphar1 enables either blocking the function or multiplying the active settings for any of the available overcurrent or earth-fault function blocks. Inrphar1 block blk2h inrphar1_blk2h guid-984a0c31-460f-48f5-aa9d-fd0f798db0ee v1 en figure 336: inrush...

  • Page 240

    Efhptoc1 block ena_mult operate start eflptoc1 block ena_mult operate start efiptoc1 block ena_mult operate start eflptoc2 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o eflptoc1_operate eflptoc1_operate efhptoc1_operate efhptoc1_operate efiptoc1_operate efiptoc1_operate eflptoc2_operate eflpt...

  • Page 241

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu x120_bi2_cb_closed phiptoc1_operate phhptoc1_operate phhptoc2_operate eflptoc1_operate efhptoc1_operate efiptoc1_operate eflptoc2_operate arcsarc1_opera...

  • Page 242

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 243

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed using the cb_ready input in darrec1. The signal, and other required signals, are connec...

  • Page 244

    Phptov1 block operate start phptov2 block operate start phptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o phptov1_operate phptov1_operate phptov2_operate phptov2_operate phptov3_operate phptov3_operate phptov1_start phptov2_start phptov3_start phptov_operate guid-168b0eca-ec3a-4e24-bb38-040d20f5ee...

  • Page 245

    The residual overvoltage protection rovptov provides earth fault protection by detecting an abnormal level of residual voltage. It can be used, for example, as a non- selective backup protection for the earth-fault functionality. Rovptov1 block operate start rovptov2 block operate start rovptov3 blo...

  • Page 246

    Frpfrq1 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq3 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq2 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg or6 b1 b2 b3 b4 b5 b6 o frpfrq3_operate frpfrq3_operate frpfrq2_opera...

  • Page 247

    Or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o general_st...

  • Page 248

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_ope...

  • Page 249

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phhptoc2_operate nsptoc2_ope...

  • Page 250

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 251

    Seqspvc1 block cb_closed discon_open mincb_open fusef_3ph fusef_u x120_bi2_cb_closed x110_bi1_bus_vt_mcb_open seqspvc1_fusef_u seqspvc1_fusef_3ph guid-36463825-15e3-43eb-8747-6b52feb5ccc9 v2 en figure 352: fuse failure supervision function circuit-breaker condition monitoring sscbr1 supervises the s...

  • Page 252

    Not in out x110_bi4_cb_spring_charged cb_spring_discharged guid-2e6d31bf-26f4-47cf-8e05-295bb466e4ad v1 en figure 355: logic for start of circuit-breaker spring charging two separate trip circuit supervision functions are included: tcsscbr1 for power output x100:po3 and tcsscbr2 for power output x10...

  • Page 253

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi3_cb_opened trpptrc1_trip tcsscbr_blocking guid-75c22aa4-4f3d-4f1e-9e7f-82c1ab76d23f v1 en figure 357: logic for blocking of trip circuit supervision 3.10.3.4 functional diagrams for control and interlocking the main purpose of the synchronism and energiz...

  • Page 254

    Essxswi1 posopen posclose openpos closepos okpos essxswi1_openpos x110_bi8_es1_opened x110_bi7_es1_closed guid-5bc3fc2d-0bbf-40f3-84fd-34804a0a9354 v1 en figure 360: earth switch control logic the circuit breaker closing is enabled when the ena_close input is activated. The input can be activated by...

  • Page 255

    Or6 b1 b2 b3 b4 b5 b6 o cb_open_command cbxcbr1_exe_op trpptrc1_trip darrec1_open_cb guid-a6e3fb5d-548a-4bc0-9cff-be0045ff8ec5 v1 en figure 363: signals for opening coil of circuit breaker 1 not in out and6 b1 b2 b3 b4 b5 b6 o not in out and b1 b2 o cbxcbr1_ena_close trpptrc1_trip x110_bi3_gas_press...

  • Page 256

    3.10.3.5 functional diagrams for measurement functions the phase current inputs to the ied are measured by the three-phase current measurement function cmmxu1. The current input is connected to the x120 card in the back panel. The sequence current measurement csmsqi1 measures the sequence current an...

  • Page 257

    Vsmsqi1 guid-ae2f63c6-4370-4d54-881e-0f9b39b3a528 v1 en figure 371: voltage measurement: sequence voltage measurement resvmmxu1 block high_alarm high_warn guid-816e4ce2-6d0e-4608-b26d-dd624b2534f8 v1 en figure 372: voltage measurement: residual voltage measurement vmmxu2 block high_alarm high_warn l...

  • Page 258

    3.10.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi1_b...

  • Page 259

    X120_bi3_cb_opened x120_bi2_cb_closed x120_bi4_rst_lockout x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input 2 x120 (aim).X120-input 3 x120 (aim).X120-input 4 guid-4baa9a5d-93c8-4db9-937f-05be3716e9f2 v1 en figure 379: default binary inputs - x120 oc_operate_pulse ef_operate_pul...

  • Page 260

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o and b1 b2 o x120_bi3_cb_opened secrsyn1_sync_ok pdnsptoc1_operate phptov_operate phptuv_operate frequency_operate efxptoc_operate rovptov_operate phxptoc_operate nsp...

  • Page 261

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu seqspvc1_fusef_u seqspvc1_fusef_3ph darrec1_inpro sscbr1_alarms disturb_record_triggered tcsscbr_alarm ccspvc1_alarm arcsarc_operate guid-80...

  • Page 262

    Tpgapc3 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o voltage_and_freq_operate_pulse phptov_operate phptuv_operate frequency_operate guid-a3cade4f-e483-4565-883d-8f8b63b1968e v1 en figure 384: timer logic for voltage and frequency operate pulse 3.10.3.8 other functions the configuration includes few ins...

  • Page 263

    3.11.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and...

  • Page 264

    Table 51: default connections for binary inputs binary input description x110-bi1 busbar vt secondary mcb open x110-bi2 line vt secondary mcb open x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service positi...

  • Page 265

    Led description 7 disturbance recorder triggered 8 circuit breaker condition monitoring 9 circuit supervision alarm 10 arc fault detected 11 autoreclose in progress 3.11.2.2 default disturbance recorder settings table 54: default disturbance recorder analog channels channel description 1 il1 2 il2 3...

  • Page 266

    Channel id text level trigger mode 15 phptov2 - start positive or rising 16 phptov3 - start positive or rising 17 psptuv1 - start positive or rising 18 nsptov1 - start positive or rising 19 phptuv1 - start positive or rising 20 phptuv2 - start positive or rising 21 phptuv3 - start positive or rising...

  • Page 267

    Channel id text level trigger mode 40 ccspvc1 - fail level trigger off 41 x120 bi1 - ext oc blocking level trigger off 42 x120 bi2 - cb closed level trigger off 43 x120 bi3 - cb opened level trigger off 44 arcsarc1 - arc flt det level trigger off arcsarc2 - arc flt det arcsarc3 - arc flt det 45 darr...

  • Page 268

    The ied offers six different settings groups which can be set based on individual needs. Each group can be activated or deactivated using the setting group settings available in the ied. Depending on the communication protocol the required function block needs to be instantiated in the configuration...

  • Page 269

    The upstream blocking from the start of the second low stage of three-phase directional overcurrent protection dphlpdoc2 is connected to the binary output x110:so1. This output can be used for sending a blocking signal to the relevant overcurrent protection stage of the ied at the infeeding bay. Or6...

  • Page 270

    Earth-fault protection or for cable intermittent earth-fault protection in compensated networks. Deflpdef2 block ena_mult rca_ctl operate start deflpdef1 block ena_mult rca_ctl operate start defhpdef1 block ena_mult rca_ctl operate start defhpdef1_operate deflpdef1_operate deflpdef2_operate deflpdef...

  • Page 271

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start wpwde_operate guid-088c6730-9479-4a5f-bb6b...

  • Page 272

    Non-directional (cross-country) earth-fault protection, using calculated io, efhptoc1 protects against double earth-fault situations in isolated or compensated networks. This protection function uses the calculated residual current originating from the phase currents. Efhptoc1 block ena_mult operate...

  • Page 273

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu x120_bi2_cb_closed phiptoc1_operate dphhpdoc1_operate dphlpdoc1_operate efpadm2_operate efpadm3_operate defhpdef1_operate deflpdef2_operate wpwde2_opera...

  • Page 274

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 275

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connect...

  • Page 276

    Phptov1 block operate start phptov2 block operate start phptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o phptov1_operate phptov1_operate phptov2_operate phptov2_operate phptov3_operate phptov3_operate phptov1_start phptov2_start phptov3_start phptov_operate guid-45958b3a-52bd-4fdb-beba-97e966dff9...

  • Page 277

    The residual overvoltage protection rovptov provides earth fault protection by detecting an abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. Rovptov1 block operate start rovptov2 block operat...

  • Page 278

    Frpfrq1 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq3 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq2 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg or6 b1 b2 b3 b4 b5 b6 o frpfrq3_operate frpfrq3_operate frpfrq2_opera...

  • Page 279

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 ...

  • Page 280

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 281

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate dphlpdoc2_operate dphhpdoc1_operate nsptoc1_operate dp...

  • Page 282

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 283

    Seqspvc1 block cb_closed discon_open mincb_open fusef_3ph fusef_u x120_bi2_cb_closed x110_bi1_bus_vt_mcb_open seqspvc1_fusef_u seqspvc1_fusef_3ph guid-ddde0b45-9241-4a6d-9bb8-342d8da0c295 v2 en figure 412: fuse failure supervision function circuit-breaker condition monitoring sscbr1 supervises the s...

  • Page 284

    Not in out x110_bi4_cb_spring_charged cb_spring_discharged guid-d93c83eb-1197-4108-97e1-d13e39536796 v1 en figure 415: logic for start of circuit-breaker spring charging two separate trip circuit supervision functions are included: tcsscbr1 for power output x100:po3 and tcsscbr2 for power output x10...

  • Page 285

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi3_cb_opened trpptrc1_trip tcsscbr_blocking guid-8e139357-424e-400b-a463-137229e9b0dc v1 en figure 417: logic for blocking trip circuit supervision 3.11.3.4 functional diagrams for control and interlocking the main purpose of the synchronism and energizing...

  • Page 286

    Essxswi1 posopen posclose openpos closepos okpos essxswi1_openpos x110_bi8_es1_opened x110_bi7_es1_closed guid-efcdb6f6-3081-4d3d-bb35-1a525173ee10 v1 en figure 420: earth switch control logic the circuit breaker closing is enabled when the ena_close input is activated. The input can be activated by...

  • Page 287

    Connect the additional signals by the application for closing of circuit breaker. Not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out and b1 b2 o trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_bi3_gas_pressure_alarm dcsxswi1_okpos essxswi1_openpos x110_bi4_cb_spring_charged secrsyn1_sync_o...

  • Page 288

    And b1 b2 o and b1 b2 o or b1 b2 o false false cbxcbr1_au_close control_local control_remote guid-f71c5f96-7155-43cf-830f-96c7ef7b1dc3 v1 en figure 426: external closing command for circuit breaker 1 and b1 b2 o and b1 b2 o or b1 b2 o false false cbxbcr1_au_open control_local control_remote guid-f0b...

  • Page 289

    Cmmxu1 block high_alarm high_warn low_warn low_alarm guid-b0c3bb58-7029-49d0-9617-e432e26969e8 v1 en figure 428: current measurement: three-phase current measurement csmsqi1 guid-6af87abd-4c95-4753-8827-f9cec888853e v1 en figure 429: current measurement: sequence current measurement rescmmxu1 block ...

  • Page 290

    Fmmxu1 guid-31f768f6-7fb2-41c6-a75e-a1e847791946 v1 en figure 435: other measurement: frequency measurement pemmxu1 rstacm guid-48f72f18-d585-404e-a529-864e7baa8907 v1 en figure 436: other measurement: three-phase power and energy measurement fltrfrc1 block cb_clrd guid-114b06b5-7d33-47b0-9907-7f199...

  • Page 291

    3.11.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi1_b...

  • Page 292

    X120_bi3_cb_opened x120_bi2_cb_closed x120_bi4_rst_lockout x120_bi1_ext_oc_blocking x120 (aim).X120-input 1 x120 (aim).X120-input 2 x120 (aim).X120-input 3 x120 (aim).X120-input 4 guid-dbca4227-d1c9-470a-9ecb-0317ef860796 v1 en figure 440: default binary inputs - x120 oc_operate_pulse ef_operate_pul...

  • Page 293

    The led main application sheet contains programmable led function blocks with initialization logic. If any led function block is missing, insert it from the object library. 1mrs756378 s section 3 ref615 standard configurations ref615 287 application manual.

  • Page 294

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o and b1 b2 o or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o x120_bi3_cb_opened secrsyn1_sync_ok phiptoc1_operate intrptef1_operate pdnsptoc1_operate efhptoc1_operate psptuv1_oper...

  • Page 295

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu seqspvc1_fusef_u seqspvc1_fusef_3ph darrec1_inpro sscbr1_alarms disturb_record_triggered tcsscbr_alarm ccspvc1_alarm arcsarc_operate guid-c1...

  • Page 296

    Or6 b1 b2 b3 b4 b5 b6 o tpgapc3 in1 in2 out1 out2 voltage_and_freq_operate_pulse psptuv1_operate nsptov1_operate phptuv_operate phptov_operate frequency_operate guid-9295344e-02c4-40e7-b098-8a31ebd29f66 v1 en figure 445: timer logic for voltage and frequency operate pulse 3.11.3.8 other functions th...

  • Page 297

    3.12.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and...

  • Page 298

    Table 56: default connections for binary inputs binary input description x110-bi1 busbar vt secondary mcb open x110-bi2 line vt secondary mcb open x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service positi...

  • Page 299

    Led description 7 disturbance recorder triggered 8 high impedance restricted earth-fault protection operated 9 circuit breaker condition monitoring or supervision alarm 10 arc fault detected 11 autoreclose in progress 3.12.2.2 default disturbance recorder settings table 59: default disturbance recor...

  • Page 300

    Channel id text level trigger mode 15 phptov1 - start positive or rising 16 phptov2 - start positive or rising 17 phptuv1 - start positive or rising 18 phptuv2 - start positive or rising 19 rovptov1 - start positive or rising 20 rovptov2 - start positive or rising 21 frpfrq1 - start positive or risi...

  • Page 301

    Channel id text level trigger mode 41 x130bi1 - ext oc blocking level trigger off 42 x130bi2 - cb closed level trigger off 43 x130bi3 - cb opened level trigger off 44 secrsyn1 - sync inpro level trigger off 45 secrsyn1 - sync ok level trigger off 46 secrsyn1 - cl fail al level trigger off 47 secrsyn...

  • Page 302

    3.12.3.1 functional diagrams for protection the functional diagrams describe the protection functionality of the ieds in detail and according to the factory set default connections. Five overcurrent stages are offered for overcurrent and short-circuit protection. Two of them include directional func...

  • Page 303

    The output blk2h of three-phase inrush detector inrphar1 enables either blocking the function or multiplying the active settings for any of the available overcurrent or earth-fault function blocks. Inrphar1 block blk2h inrphar1_blk2h guid-c4b49350-27f3-4310-ac69-1b01cd67f03b v1 en figure 449: inrush...

  • Page 304

    Efhptoc1 block ena_mult operate start eflptoc1 block ena_mult operate start efiptoc1 block ena_mult operate start eflptoc2 block ena_mult operate start or6 b1 b2 b3 b4 b5 b6 o eflptoc2_operate eflptoc2_operate eflptoc1_operate eflptoc1_operate efhptoc1_operate efhptoc1_operate efiptoc1_operate efipt...

  • Page 305

    Hrefpdif1 block operate start hrefpdif1_operate hrefpdif1_start guid-8034927a-76eb-4106-8ace-2408181cf096 v1 en figure 453: high impedance restricted earth-fault protection function three-phase thermal protection for feeders, cables and distribution transformers t1pttr1 detects overloads under varyi...

  • Page 306

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu eflptoc2_operate x130_bi2_cb_closed phiptoc1_operate phlptoc1_operate phhptoc1_o...

  • Page 307

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 308

    The autoreclosing function can be inhibited with the inhibit_recl input. By default, few selected protection function operations are connected to this input. A control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The ...

  • Page 309

    Darrec1 init_1 init_2 init_3 init_4 init_5 init_6 del_init_2 del_init_3 del_init_4 blk_recl_t blk_rclm_t blk_therm cb_pos cb_ready inc_shotp inhibit_recl recl_on sync open_cb close_cb cmd_wait inpro locked prot_crd unsuc_recl ar_on ready active or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or b1 b...

  • Page 310

    Rovptov1 block operate start rovptov2 block operate start or6 b1 b2 b3 b4 b5 b6 o rovptov2_operate rovptov2_operate rovptov1_operate rovptov1_operate rovptov1_start rovptov2_start rovptov_operate guid-02dc3919-900f-41a1-82da-28b3fe236f56 v1 en figure 462: residual voltage protection function the sel...

  • Page 311

    Frpfrq1 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq3 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq2 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg or6 b1 b2 b3 b4 b5 b6 o frpfrq3_operate frpfrq3_operate frpfrq2_opera...

  • Page 312

    Or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o general_st...

  • Page 313

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate eflptoc1_operate efhptoc1_operate efiptoc1_o...

  • Page 314

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate eflptoc1_operate efhptoc1_operate efiptoc1_o...

  • Page 315

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or...

  • Page 316

    Seqspvc1 block cb_closed discon_open mincb_open fusef_3ph fusef_u x120_bi2_cb_closed x110_bi1_bus_vt_mcb_open seqspvc1_fusef_u seqspvc1_fusef_3ph guid-58eaf3fe-89b5-4e66-8ebe-35edd5887a78 v2 en figure 469: fuse failure supervision function circuit-breaker condition monitoring sscbr1 supervises the s...

  • Page 317

    Blocked by the master trip trpptrc1 and trpptrc2 and the circuit breaker open signal. It is assumed that there is no external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Tcsscbr1 block alarm tcsscbr2 block alar...

  • Page 318

    Secrsyn1 block cl_command bypass sync_inpro sync_ok cl_fail_al cmd_fail_al lldb lllb dllb dldb secrsyn1_sync_ok block_secrsyn1 secrsyn1_sync_inpro secrsyn1_cl_fail_al secrsyn1_cmd_fail_al or b1 b2 o x110_bi1_bus_vt_mcb_open x110_bi2_line_vt_mcb_open block_secrsyn1 guid-ac5a98e3-6e38-4375-a1f0-d1baab...

  • Page 319

    Cbxcbr1 posopen posclose ena_open ena_close blk_open blk_close au_open au_close trip sync_ok sync_itl_byp selected exe_op exe_cl op_req cl_req openpos closepos okpos open_enad close_enad true x120_bi3_cb_opened x120_bi2_cb_closed cbxcbr1_ena_close cbxcbr1_exe_cl cbxcbr1_exe_op cbxcbr1_blk_close fals...

  • Page 320

    Not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out and b1 b2 o trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_bi3_gas_pressure_alarm dcsxswi1_okpos essxswi1_openpos x110_bi4_cb_spring_charged secrsyn1_sync_ok guid-6ee55602-0579-4751-a44b-fc1a13105bb7 v1 en figure 481: circuit breaker 1 cl...

  • Page 321

    And b1 b2 o and b1 b2 o or b1 b2 o false false cbxbcr1_au_open control_local control_remote guid-3d63aade-4d5e-47d2-b05f-54245a9157e8 v1 en figure 484: external opening command for circuit breaker 3.12.3.5 functional diagrams for measurement functions the phase current inputs to the ied are measured...

  • Page 322

    Csmsqi1 guid-4d375bc8-564e-482c-b177-e3c4d5f9ebe6 v1 en figure 486: current measurement: sequence current measurement rescmmxu1 block high_alarm high_warn guid-424ff806-e6a8-4646-88e1-bbafb01c82df v1 en figure 487: current measurement: residual current measurement rescmmxu2 block high_alarm high_war...

  • Page 323

    Fmmxu1 guid-ed9bf264-f1ea-4a40-b9ba-ce67b5b4c46d v1 en figure 493: other measurement: frequency measurement pemmxu1 rstacm guid-d9e08f0f-dc98-462e-bbf8-b06bfa9ea144 v1 en figure 494: other measurement: three phase power and energy measurement fltrfrc1 block cb_clrd guid-e8a8cc10-4013-4cdd-8526-7bb04...

  • Page 324

    3.12.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi1_b...

  • Page 325

    X130_bi3_cb_opened x130_bi2_cb_closed x130_bi4_rst_lockout x130_bi1_ext_oc_blocking x130 (aim).X130-input 1 x130 (aim).X130-input 2 x130 (aim).X130-input 3 x130 (aim).X130-input 4 guid-83b68f9e-9c82-4634-aabb-fd6276d53fcc v1 en figure 498: binary input - x130 terminal block oc_operate_pulse ef_opera...

  • Page 326

    Led5 ok alarm reset frequency_operate led2 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o defxpdef_operate efxptoc_operate rovptov_operate led1 ok alarm reset or b1 b2 o dphxpdoc_operate phxptoc_operate led3 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o t1pttr1_operate phptov_operate phptuv_operate nsptoc_operate ...

  • Page 327

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trbu hrefpdif1_operate seqspvc1_fusef_u seqspvc1_fusef_3ph darrec1_inpro disturb_record_triggered tcsscbr_alarm ccspv1_alarm sscbr1_alarms arcsar...

  • Page 328

    Or6 b1 b2 b3 b4 b5 b6 o tpgapc3 in1 in2 out1 out2 voltage_and_freq_operate_pulse phptov_operate phptuv_operate frequency_operate guid-59484b34-0407-4d36-b78b-dbe34269795b v1 en figure 503: timer logic for voltage and frequency operate pulse 3.12.3.8 other functions the configuration includes few ins...

  • Page 329

    3.13.2 functions condition monitoring and supervision or and feeder protection and control relay standard configuration protection local hmi r l clear esc i o configuration a system hmi time authorization r l clear esc i o u12 0. 0 kv p 0.00 kw q 0.00 kvar il2 0 a a remarks optional function no. Of i...

  • Page 330

    Table 61: default connections for binary inputs binary input description x110-bi1 circuit breaker plug not inserted x110-bi2 circuit breaker spring discharged x110-bi3 circuit breaker open indication x110-bi4 circuit breaker closed indication x110-bi5 circuit breaker truck out (test position) indica...

  • Page 331

    3.13.2.2 default disturbance recorder settings table 64: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 u1 6 u2 7 u3 8 - 9 - 10 - 11 - 12 - table 65: default disturbance recorder binary channels channel id text level trigger mode 1 dphlpdoc1 - start positiv...

  • Page 332

    Channel id text level trigger mode 17 psptuv1 - start positive or rising 18 nsptov1 - start positive or rising 19 phptuv1 - start positive or rising 20 phptuv2 - start positive or rising 21 phptuv3 - start positive or rising 22 rovptov1 - start positive or rising 23 rovptov2 - start positive or risi...

  • Page 333

    Channel id text level trigger mode 35 phptov1 - operate level trigger off phptov2 - operate phptov3 - operate 36 phptuv1 - operate level trigger off phptuv2 - operate phptuv3 - operate 37 rovptov1 - operate level trigger off 41 x110bi4 - cb closed level trigger off 42 x110bi3 - cb opened level trigg...

  • Page 334

    The ied offers six different settings groups which can be set based on individual needs. Each group can be activated or deactivated using the setting group settings available in the ied. Depending on the communication protocol the required function block needs to be instantiated in the configuration...

  • Page 335

    This signal is not connected in the configuration. This output can be used for sending a blocking signal to the relevant overcurrent protection stage of the ied at the infeeding bay. Or6 b1 b2 b3 b4 b5 b6 o dphlpdoc2_start guid-7aea0818-3740-426b-89cb-128fc04d5e3d v1 en figure 507: upstream blocking...

  • Page 336

    Deflpdef2 block ena_mult rca_ctl operate start deflpdef2_operate deflpdef2_start deflpdef1 block ena_mult rca_ctl operate start deflpdef1_operate deflpdef1_start or6 b1 b2 b3 b4 b5 b6 o defhpdef1_operate deflpdef1_operate deflpdef2_operate defxpdef_operate defhpdef1 block ena_mult rca_ctl operate st...

  • Page 337

    Wpwde1 block rca_ctl operate start wpwde2 block rca_ctl operate start wpwde3 block rca_ctl operate start or6 b1 b2 b3 b4 b5 b6 o wpwde1_operate wpwde1_operate wpwde2_operate wpwde2_operate wpwde3_operate wpwde3_operate wpwde1_start wpwde2_start wpwde3_start wpwde_operate guid-2415f7df-2f35-4b56-b26e...

  • Page 338

    Non-directional (cross-country) earth-fault protection, using calculated io, efhptoc1 protects from double earth-fault situations in isolated or compensated networks. The protection function uses the calculated residual current originating from the phase currents. Efhptoc1 block ena_mult operate sta...

  • Page 339

    Ccbrbrf1 block start posclose cb_fault cb_fault_al trbu trret or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trret x110_bi4_cb_closed wpwde2_operate wpwde3_operate arcsarc1_operate arcsarc2_operate arcsarc3_operate efpadm2_operate deflpdef2_operate defhpdef1_operate...

  • Page 340

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 341

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connect...

  • Page 342

    Phptov1 block operate start phptov2 block operate start phptov3 block operate start or6 b1 b2 b3 b4 b5 b6 o phptov1_operate phptov1_operate phptov2_operate phptov2_operate phptov3_operate phptov3_operate phptov1_start phptov2_start phptov3_start phptov_operate guid-132f1d97-2e54-4924-b2bd-aa4ff91882...

  • Page 343

    The residual overvoltage protection rovptov provides earth fault protection by detecting an abnormal level of residual voltage. It can be used, for example, as a nonselective backup protection for the selective directional earth-fault functionality. Rovptov1 block operate start rovptov2 block operat...

  • Page 344

    Frpfrq1 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq3 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg frpfrq2 block operate opr_ofrq opr_ufrq opr_frg start st_ofrq st_ufrq st_frg or6 b1 b2 b3 b4 b5 b6 o frpfrq3_operate frpfrq3_operate frpfrq2_opera...

  • Page 345

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 ...

  • Page 346

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phptuv2_operate phptuv3_operate frpfrq1_operate frpfrq2_operate frpfrq3...

  • Page 347

    Or6 b1 b2 b3 b4 b5 b6 o trpptrc2 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o ccbrbrf1_trret trpptrc2_trip phptuv2_operate phptuv3_operate frpfrq1_operate frpfrq2_...

  • Page 348

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 349

    Seqspvc1 block cb_closed discon_open mincb_open fusef_3ph fusef_u x110_bi4_cb_closed seqpvc1_fusef_u seqpvc1_fusef_3ph guid-ddf6efe9-7547-4cad-8158-4a1a568c6b76 v2 en figure 531: fuse failure supervision function circuit-breaker condition monitoring sscbr1 supervises the switch status based on the c...

  • Page 350

    It is assumed that there is an external resistor in the circuit breaker tripping coil circuit connected in parallel with the circuit breaker normally open auxiliary contact. Set the parameters for tcsscbr1 properly. Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm t...

  • Page 351

    Dcsxswi1 posopen posclose openpos closepos okpos dcsxswi1_okpos x110_bi5_cb_truck_in_test x110_bi6_cb_truck_in_service and6 b1 b2 b3 b4 b5 b6 o dc1_close_enable essxswi1_openpos cbxcbr1_openpos guid-142ce220-f290-41cb-9e39-1b7080026beb v1 en figure 537: disconnector interlocking logic connect the ad...

  • Page 352

    Cbxcbr1 posopen posclose ena_open ena_close blk_open blk_close au_open au_close trip sync_ok sync_itl_byp selected exe_op exe_cl op_req cl_req openpos closepos okpos open_enad close_enad true cbxcbr1_close_enad cbxcbr1_ena_close cbxcbr1_exe_cl x110_bi3_cb_opened x110_bi4_cb_closed cbxcbr1_blk_close ...

  • Page 353

    Connect the higher-priority conditions before enabling the closing of circuit breaker. These conditions cannot be bypassed with bypass feature of the function. Or6 b1 b2 b3 b4 b5 b6 o cbxcbr1_blk_close t1pttr1_blk_close guid-adbc0393-0928-425b-bd65-5ac7f54440ea v1 en figure 543: circuit breaker clos...

  • Page 354

    Measurement rescmmxu1 measures the residual current. Residual current input is connected to the x130 card in the back panel. The three-phase bus side phase voltage inputs to the ied are measured by three-phase voltage measurement vmmxu1. The three-phase current input is connected to the x131, x132 a...

  • Page 355

    Vmmxu1 block high_alarm high_warn low_warn low_alarm guid-a7110fef-3870-45f8-b88b-3d93f2930b03 v1 en figure 549: voltage measurement: three-phase voltage measurement vsmsqi1 guid-690b0379-f909-4b29-b4e0-9cfe7e2d04a9 v1 en figure 550: voltage measurement: sequence voltage measurement fmmxu1 guid-9ca9...

  • Page 356

    3.13.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_cb_opened x110_bi4_cb_closed x110_bi5_cb_truck_in_test x110_bi6_cb_truck_in_service x110_bi7_es1_opened x110_bi8_es1_closed x110_bi1_plug_out x110_bi2_...

  • Page 357

    Trpptrc3_trip trpptrc4_trip trpptrc5_trip x110 (bio-h).X110-hso1 x110 (bio-h).X110-hso2 x110 (bio-h).X110-hso3 guid-666bbfad-0ef6-4707-99a3-7a5bf35cc725 v1 en figure 556: default binary outputs - x110 terminal block cb_open_command cb_close_command dc1_close_enable es1_close_enabled ccbrbrf1_trret c...

  • Page 358

    Led2 ok alarm reset or b1 b2 o phiptoc1_operate dphxpdoc_operate led3 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o efhptoc1_operate intrptef1_operate defxpdef_operate led4 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o pdnsptoc1_operate nsptoc1_operate nsptoc2_operate led5 ok alarm reset or b1 b2 o psptuv1_operat...

  • Page 359

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset or6 b1 b2 b3 b4 b5 b6 o or b1 b2 o or b1 b2 o or b1 b2 o cb_open_command tcsscbr_alarm seqpvc1_fusef_u rovptov_operate phptov_operate phptuv_operate frpfrq_operate seqpvc1_fusef_3ph ccspvc1_alarm ssc...

  • Page 360

    Tpgapc3 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o psptuv1_operate nsptov1_operate phptov_operate phptuv_operate frpfrq_operate guid-c791951b-7c53-4683-8683-f0ddb1cd50af v1 en figure 560: timer logic for voltage and frequency operate pulse 3.13.3.8 other functions the configuration includes few insta...

  • Page 361

    3.14.2 functions condition monitoring and supervision or and control and indication 1) measurement feeder protection and control relay standard configuration protection local hmi object ctrl 2) ind 3) cb dc es 1) check availability of binary inputs/outputs from technical documentation 2) control and...

  • Page 362

    Table 66: default connections for binary inputs binary input description x110-bi2 autoreclose external start command x110-bi3 circuit breaker low gas pressure indication x110-bi4 circuit breaker spring charged indication x110-bi5 circuit breaker truck in (service position) indication x110-bi6 circui...

  • Page 363

    Led description 9 trip circuit supervision alarm 10 arc protection operate 11 autoreclose in progress 3.14.2.2 default disturbance recorder settings table 69: default disturbance recorder analog channels channel description 1 il1 2 il2 3 il3 4 io 5 - 6 - 7 - 8 - 9 - 10 - 11 - 12 - table 70: default ...

  • Page 364

    Channel id text level trigger mode 16 phiptoc1 - operate level trigger off phhptoc1 - operate phlptoc2 - operate phlptoc1 - operate 17 nsptoc1 - operate level trigger off nsptoc2 - operate 18 eflptoc1 - operate level trigger off efhptoc1 - operate efiptoc1 - operate 19 x110bi2 - ext start autoreclos...

  • Page 365

    The phase voltages to the ied are fed from a voltage transformer. The residual voltage to the ied is fed from either residually connected vts, an open delta connected vt or internally calculated. The ied offers six different settings groups which can be set based on individual needs. Each group can ...

  • Page 366

    The upstream blocking from the start of the second low stage of three-phase non- directional overcurrent protection phlptoc2 is connected to the binary output x110:so1. This output can be used for sending a blocking signal to the relevant overcurrent protection stage of the ied at the infeeding bay....

  • Page 367

    Efpadm, wattmetric-based earth-fault protection wpwde or harmonics-based earth-fault protection haefptoc. A dedicated protection stage intrptef is used either for transient based earth-fault protection or for cable intermittent earth-fault protection in compensated networks. Efhptoc1 block ena_mult ...

  • Page 368

    T1pttr1 blk_opr ena_mult temp_amb operate start alarm blk_close t1pttr1_start t1pttr1_operate t1pttr1_alarm guid-5995df50-e527-4a1a-8704-5d0e283131cf v1 en figure 569: thermal overcurrent protection function circuit breaker failure protection ccbrbrf1 is initiated via the start input by number of di...

  • Page 369

    Arcsarc1 block rem_flt_arc opr_mode operate arc_flt_det arcsarc2 block rem_flt_arc opr_mode operate arc_flt_det arcsarc3 block rem_flt_arc opr_mode operate arc_flt_det or6 b1 b2 b3 b4 b5 b6 o arcsarc1_operate arcsarc1_operate arcsarc2_operate arcsarc2_operate arcsarc3_operate arcsarc3_operate arcsar...

  • Page 370

    Control command to the circuit breaker, either local or remote, also blocks the autoreclosing function via the cbxcbr1-selected signal. The circuit breaker availability for the autoreclosing sequence is expressed with the cb_ready input in darrec1. The signal, and other required signals, are connect...

  • Page 371

    Or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o tpgapc1 in1 in2 out1 out2 or6 b1 b2 b3 b4 b5 b6 o general_start_pulse general_operate_pulse phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_opera...

  • Page 372

    Trpptrc1 block operate rst_lkout trip cl_lkout or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 b4 b5 b6 o trpptrc1_trip phiptoc1_operate phlptoc1_operate phhptoc1_operate nsptoc1_operate phlptoc2_operate nsptoc2_operate eflptoc1_operate efhptoc1_operate efiptoc1_...

  • Page 373

    Rdre1 c1 c2 c3 c4 c5 c6 c7 c8 c9 c10 c11 c12 c13 c14 c15 c16 c17 c18 c19 c20 c21 c22 c23 c24 c25 c26 c27 c28 c29 c30 c31 c32 c33 c34 c35 c36 c37 c38 c39 c40 c41 c42 c43 c44 c45 c46 c47 c48 c49 c50 c51 c52 c53 c54 c55 c56 c57 c58 c59 c60 c61 c62 c63 c64 triggered or6 b1 b2 b3 b4 b5 b6 o or6 b1 b2 b3 ...

  • Page 374

    Sscbr1 block posopen posclose open_cb_exe close_cb_exe pres_alm_in pres_lo_in spr_chr_st spr_chr rst_ipow rst_cb_wear rst_trv_t rst_spr_t trv_t_op_alm trv_t_cl_alm spr_chr_alm opr_alm opr_lo ipow_alm ipow_lo cb_life_alm mon_alm pres_alm pres_lo openpos invalidpos closepos cb_close_command cb_open_co...

  • Page 375

    Tcsscbr1 block alarm tcsscbr2 block alarm or b1 b2 o tcsscbr1_alarm tcsscbr1_alarm tcsscbr2_alarm tcsscbr2_alarm tcsscbr_blocking tcsscbr_blocking tcsscbr_alarm guid-d9b2a8ef-4b42-48d5-ad1d-e4a5131c2874 v1 en figure 580: trip circuit supervision function or6 b1 b2 b3 b4 b5 b6 o trpptrc2_trip x120_bi...

  • Page 376

    Disconnector or breaker truck and earth-switch position status, status of the trip logics, gas pressure alarm and circuit-breaker spring charging status. The okpos output from dcsxswi defines whether the disconnector or breaker truck is either open (in test position) or close (in service position). ...

  • Page 377

    Not in out and6 b1 b2 b3 b4 b5 b6 o not in out not in out trpptrc2_trip cbxcbr1_ena_close trpptrc1_trip x110_bi3_gas_pressure_alarm dcsxswi1_okpos essxswi1_openpos x110_bi4_cb_spring_charged guid-4bd1ba07-c7a7-4510-bab9-dbf3babd1a02 v1 en figure 587: circuit breaker close enable logic the configurat...

  • Page 378

    The measurements can be seen in the lhmi and they are available under the measurement option in the menu selection. Based on the settings, function blocks can generate low alarm or warning and high alarm or warning signals for the measured current values. Load profile record ldprlrc1 is included in ...

  • Page 379

    Vmmxu1 block high_alarm high_warn low_warn low_alarm guid-3b972de4-6494-4f05-a3a6-889b2c107cac v1 en figure 593: voltage measurement: three-phase voltage measurement vsmsqi1 guid-b73e15a5-5f01-4c52-b6cf-fc253e9c73cc v1 en figure 594: residual measurement: residual voltage measurement vmmxu2 block hi...

  • Page 380

    3.14.3.6 functional diagrams for i/o and alarm leds or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o or b1 b2 o x110_bi3_gas_pressure_alarm x110_bi4_cb_spring_charged x110_bi6_cb_truck_in_test x110_bi5_cb_truck_in_service x110_bi8_es1_opened x110_bi7_es1_closed x110_bi2_ext_start_au...

  • Page 381

    Upsteam_oc_blocking oc_operate_pulse ef_operate_pulse trpptrc3_trip trpptrc4_trip trpptrc5_trip x110 (bio).X110-so1 x110 (bio).X110-so2 x110 (bio).X110-so3 x110 (bio-h).X110-hso1 x110 (bio-h).X110-hso2 x110 (bio-h).X110-hso3 guid-3241c034-ac38-41ba-ac50-ca5fc1e9425e v1 en figure 602: binary outputs ...

  • Page 382

    Led1 ok alarm reset led2 ok alarm reset led3 ok alarm reset led4 ok alarm reset led5 ok alarm reset or b1 b2 o eflptoc2_operate pdnsptoc1_operate phxptoc_operate efxptoc_operate t1pttr1_alarm nsptoc_operate guid-0a540afb-3dd1-47a7-ae63-e65932766d34 v1 en section 3 1mrs756378 s ref615 standard config...

  • Page 383

    Led6 ok alarm reset led7 ok alarm reset led8 ok alarm reset led9 ok alarm reset led10 ok alarm reset led11 ok alarm reset ccbrbrf1_trbu darrec1_inpro disturb_record_triggered tcsscbr_alarm sscbr1_alarms arcsarc_operate guid-76107b29-33d4-4ca1-8f5c-d03382a9d583 v1 en figure 604: default led connectio...

  • Page 384

    3.14.3.8 other functions the configuration includes few instances of residual overvoltage protection, phase overvoltage and undervoltage protection, positive-sequence undervoltage protection, negative-sequence overvoltage protection, frequency protection, multipurpose protection mapgapc, high-impeda...

  • Page 385

    Section 4 requirements for measurement transformers 4.1 current transformers 4.1.1 current transformer requirements for non-directional overcurrent protection for reliable and correct operation of the overcurrent protection, the ct has to be chosen carefully. The distortion of the secondary current ...

  • Page 386

    Of the ct is distorted and it might have severe effects on the performance of the protection relay. In practise, the actual accuracy limit factor (f a ) differs from the rated accuracy limit factor (f n ) and is proportional to the ratio of the rated ct burden and the actual ct burden. The actual ac...

  • Page 387

    The adequate performance of the ct should be checked when the setting of the high set stage overcurrent protection is defined. The operate time delay caused by the ct saturation is typically small enough when the overcurrent setting is noticeably lower than f a . When defining the setting values for...

  • Page 388

    A071142 v1 en figure 606: example of three-stage overcurrent protection the maximum three-phase fault current is 41.7 ka and the minimum three-phase short circuit current is 22.8 ka. The actual accuracy limit factor of the ct is calculated to be 59. The start current setting for low-set stage (3i>) ...

  • Page 389

    Section 5 ied physical connections 5.1 inputs 5.1.1 energizing inputs 5.1.1.1 phase currents the ied can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied. However, at least terminals x120:7-8 must be connected. Table 72: phase current inputs include...

  • Page 390

    5.1.1.3 phase voltages table 76: phase voltage inputs included in configurations e, f, h, j, k and n terminal description x130:11-12 u1 x130:13-14 u2 x130:15-16 u3 table 77: reference voltage input for secrsyn1 included in configurations h, j, k and n terminal description x130:9-10 u12b 5.1.1.4 resi...

  • Page 391

    Table 81: auxiliary voltage supply terminal description x100:1 + input x100:2 - input 5.1.3 binary inputs the binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for remote control of ied settings. Binary inputs of...

  • Page 392

    Terminal description x110:4 bi4, + x110:5 bi4, - x110:6 bi5, + x110:10 bi5, - x110:7 bi6, + x110:10 bi6, - x110:8 bi7, + x110:10 bi7, - x110:9 bi8, + x110:10 bi8, - binary inputs of slot x120 are available with configurations c, d, e, f, h, j and n table 84: binary input terminals x120-1...6 termina...

  • Page 393

    Table 86: binary input terminals x130:1-9 terminal description x130:1 bi1, + x130:2 bi1, - x130:2 bi2, - x130:3 bi2, + x130:4 bi3, + x130:5 bi3, - x130:5 bi4, - x130:6 bi4, + x130:7 bi5, + x130:8 bi5, - x130:8 bi6, - x130:9 bi6, + binary inputs of slot x130 are available with configuration k and opt...

  • Page 394

    Table 88: light sensor input connectors terminal description x13 input light sensor 1 x14 input light sensor 2 x15 input light sensor 3 5.1.5 rtd/ma inputs it is possible to connect ma and rtd based measurement sensors to the ied if the ied is provided with optional rtd0001 module in standard config...

  • Page 395

    Terminal description x130:5 rtd1 (ai2), ground x130:6 rtd2 (ai3), + x130:7 rtd2 (ai3), - x130:8 rtd2 (ai3), ground 5.2 outputs 5.2.1 outputs for tripping and controlling output contacts po1, po2, po3 and po4 are heavy-duty trip contacts capable of controlling most circuit breakers. On delivery from ...

  • Page 396

    Table 92: output contacts x100:10-14 terminal description x100:10 so1, common x100:11 so1, nc x100:12 so1, no x100:13 so2, no x100:14 so2, no output contacts of slot x110 are available with configurations b, d, e, f, g, h, j, k, l and n. Table 93: output contacts x110:14-24 with bio0005 terminal des...

  • Page 397

    Table 95: output contacts x130:10-18 terminal description x130:10 so1, common x130:11 so1, no x130:12 so1, nc x130:13 so2, common x130:14 so2, no x130:15 so2, nc x130:16 so3, common x130:17 so3, no x130:18 so3, nc 5.2.3 irf the irf contact functions as an output contact for the self-supervision syst...

  • Page 398

    392.

  • Page 399

    Section 6 glossary 615 series series of numerical protection and control relays for protection and supervision applications of utility substations, and industrial switchgear and equipment ac alternating current ai analog input ascii american standard code for information interchange bi binary input ...

  • Page 400

    I/o input/output iec international electrotechnical commission iec 60870-5-103 1. Communication standard for protective equipment 2. A serial master/slave protocol for point-to-point communication iec 61850 international standard for substation communication and modeling iec 61850-8-1 a communicatio...

  • Page 401

    Modbus tcp/ip modbus rtu protocol which uses tcp/ip and ethernet to carry data between devices nc normally closed no normally open pcm600 protection and control ied manager po power output prp parallel redundancy protocol ptp precision time protocol rca also known as mta or base angle. Characteristi...

  • Page 402

    396.

  • Page 403

    397.

  • Page 404

    Contact us abb oy medium voltage products, distribution automation p.O. Box 699 fi-65101 vaasa, finland phone +358 10 22 11 fax +358 10 22 41094 www.Abb.Com/mediumvoltage www.Abb.Com/substationautomation abb india limited, distribution automation maneja works vadodara-390013, india phone +91 265 672...