ABB relion REF615 Product Manual

Other manuals for relion REF615: Applications Manual, Applications Manual, Operation Manual
Manual is about: Feeder Protection and Control Relion 615 series

Summary of relion REF615

  • Page 1

    Power products feeder protection and control ref615 product guide.

  • Page 2

    Abb 2 feeder protection and control ref615 product version: 2.0 1mrs756379 d contents disclaimer the information in this document is subject to change without notice and should not be construed as a commitment by abb oy. Abb oy assumes no responsibility for any errors that may appear in this documen...

  • Page 3

    Abb 3 feeder protection and control ref615 product version: 2.0 1mrs756379 d issued: december 2007 revision: d / 03 mar 2009 1. Description ref615, member of abb’s 615 product series, is a dedicated feeder protection ied designed for the protection, measurement and supervision of utility substations...

  • Page 4

    Abb 4 feeder protection and control ref615 product version: 2.0 1mrs756379 d functionality a b c d e f protection directional earth-fault, low-set stage, instance 1 • • - - • • directional earth-fault, low-set stage, instance 2 • • - - • • directional earth-fault, high-set stage • • - - • • non-dire...

  • Page 5

    Abb 5 feeder protection and control ref615 product version: 2.0 1mrs756379 d 1) basic interlocking functionality: closing of the circuit breaker can be enabled by a binary input signal. The actual interlocking scheme is implemented outside the ied. The binary input serves as a “master interlocking i...

  • Page 6

    Abb 6 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 1 protection function overview of standard configuration a and b 3. Protection functions the ied offers directional and non-direc- tional overcurrent and thermal overload protection, directional and non-directional ear...

  • Page 7

    Abb 7 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 2 protection function overview of standard configuration c and d fig. 3 protection function overview of standard configuration e.

  • Page 8

    Abb 8 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 4 protection function overview of standard configuration f.

  • Page 9

    Abb 9 feeder protection and control ref615 product version: 2.0 1mrs756379 d 4. Application the feeder protection ied ref615 can be supplied either with directional or nondi- rectional earth-fault protection. Directional earth-fault protection is mainly used in isolated or compensated networks, wher...

  • Page 10

    Abb 10 feeder protection and control ref615 product version: 2.0 1mrs756379 d formers. The residual current for the earth- fault protection is derived from the phase currents. When applicable, the core-balance current transformers can be used for meas- uring the residual current, especially when sen...

  • Page 11

    Abb 11 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 7 protection and control of two incoming feeders using ieds with standard configuration f. The two incoming feeders can be connected in parallel by closing the busbar- sectionalizing breaker. To achive selective overc...

  • Page 12

    Abb 12 feeder protection and control ref615 product version: 2.0 1mrs756379 d 5. Control the ied offers control of one circuit breaker with dedicated push-buttons for opening and closing. Interlocking schemes required by the application are configured with the signal matrix tool in pcm600. 6. Measur...

  • Page 13

    Abb 13 feeder protection and control ref615 product version: 2.0 1mrs756379 d protection blocks, time stamp, etc. The fault recording can be triggered by the start signal or the trip signal of a protection block, or by both. The available measurement modes include dft, rms and peak-to-peak. In addi-...

  • Page 14

    Abb 14 feeder protection and control ref615 product version: 2.0 1mrs756379 d 15. Access control to protect the ied from unauthorized access and to maintain information integrity, the ied is provided with a four-level, role-based authentication system with administrator- programmable individual pass...

  • Page 15

    Abb 15 feeder protection and control ref615 product version: 2.0 1mrs756379 d tion functionality, for example, horizontal communication between the ieds, is only enabled by the iec 61850 communication protocol. The iec 61850 communication implemen- tation supports all monitoring and control function...

  • Page 16

    Abb 16 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 4. Supported communication interfaces and protocols interfaces / protocols with optional arc protection without arc protection ethernet (rj-45 or lc) + 3 arc sensors serial (rs-485) +irig-b + 3 arc sensors ethernet (...

  • Page 17

    Abb 17 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 6. Power supply type: type 1 type 2 u aux nominal 100, 110, 120, 220, 240 v ac, 50 and 60 hz 48, 60, 110, 125, 220, 250 v dc 24, 30, 48, 60 v dc u aux variation 38...110% of u n (38...264 v ac) 80...120% of u n (38.4...

  • Page 18

    Abb 18 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 7. Energizing inputs description value rated frequency 50/60 hz ± 5 hz current inputs rated current, i n 0.2/1 a 1) 1/5 a thermal withstand capabil- ity: • continuously • for 1 s • for 10 s 4 a 100 a 25 a 20 a 500 a ...

  • Page 19

    Abb 19 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 10. Signal outputs and irf output description value rated voltage 250 v ac/dc continuous contact carry 5 a make and carry for 3.0 s 10 a make and carry 0.5 s 15 a breaking capacity when the control-circuit time const...

  • Page 20

    Abb 20 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 14. Degree of protection of flush-mounted ied description value front side ip 54 rear side, connection terminals ip 20 table 15. Environmental conditions description value operating temperature range -25...+55ºc (con...

  • Page 21

    Abb 21 feeder protection and control ref615 product version: 2.0 1mrs756379 d radio frequency interference tests: • conducted, common mode • radiated, amplitude-modulated • radiated, pulse-modulated according to iec 61000-4-6 and iec 60255-22-6, level 3 10 v (emf), f = 150 khz...80 mhz according to ...

  • Page 22

    Abb 22 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 18. Insulation tests description value dielectric tests: according to iec 60255-5 • test voltage 2 kv, 50 hz, 1 min 500 v, 50 hz, 1min, communication impulse voltage test: according to iec 60255-5 • test voltage 5 kv...

  • Page 23

    Abb 23 feeder protection and control ref615 product version: 2.0 1mrs756379 d protection functions table 24. Three-phase non-directional overcurrent protection (phxptoc) operation accuracy depending on the frequency of the current measured: f n ±2hz phlptoc ±1.5% of the set value or ±0.002 x i n phh...

  • Page 24

    Abb 24 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 25. Three-phase non-directional overcurrent protection (phxptoc) main settings parameter function value (range) step start value phlptoc 0.05...5.00 x i n 0.01 phhptoc 0.10...40.00 x i n 0.01 phiptoc 1.00...40.00 x i...

  • Page 25

    Abb 25 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 26. Three-phase directional overcurrent protection (dphxpdoc) operation accuracy depending on the frequency of the current/voltage measured: f n ±2hz dphlpdoc current: ±1.5% of the set value or ±0.002 x i n voltage: ...

  • Page 26

    Abb 26 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 28. Non-directional ef protection (efxptoc) operation accuracy depending on the frequency of the current measured: f n ±2hz eflptoc ±1.5% of the set value or ±0.002 x i n efhptoc and efiptoc ±1.5% of set value or ±0....

  • Page 27

    Abb 27 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 30. Directional ef protection (defxpdef) operation accuracy depending on the frequency of the current measured: f n ±2hz deflpdef current: ±1.5% of the set value or ±0.002 x i n voltage: ±1.5% of the set value or ±0....

  • Page 28

    Abb 28 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 31. Directional ef protection (defxpdef) main settings parameter function value (range) step start value deflpdef 0.010...5.000 x i n 0.005 defhpdef 0.10...40.00 x i n 0.01 directional mode deflpdef and defhpdef 1=no...

  • Page 29

    Abb 29 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 34. Three-phase overvoltage protection (phptov) operation accuracy depending on the frequency of the voltage measured: f n ±2hz ±1.5% of the set value or ±0.002 x u n start time 1) 2) minimum typical maximum u fault ...

  • Page 30

    Abb 30 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 36. Three-phase undervoltage protection (phptuv) operation accuracy depending on the frequency of the voltage measured: f n ±2hz ±1.5% of the set value or ±0.002 x u n start time 1) 2) minimum typical maximum u fault...

  • Page 31

    Abb 31 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 39. Positive sequence undervoltage protection (psptuv) main settings parameter function value (range) step start value psptuv 0.010...1.200 x u n 0.001 operate delay time psptuv 40...120000 ms 10 voltage block value ...

  • Page 32

    Abb 32 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 42. Residual overvoltage protection (rovptov) operation accuracy depending on the frequency of the voltage measured: f n ±2hz ±1.5% of the set value or ±0.002 x u n start time 1) 2) minimum typical maximum u fault = ...

  • Page 33

    Abb 33 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 46. Phase discontinuity protection (pdnsptoc) operation accuracy depending on the frequency of the current measured: fn ±2hz ±2% of the set value start time reset time reset ratio typical 0.96 retardation time operat...

  • Page 34

    Abb 34 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 50. Three-phase thermal overload (t1pttr) operation accuracy depending on the frequency of the current measured: fn ±2hz current measurement: ±0.5% or ±0.002 x i n (at currents in the range of 0.01…4.00 x i n ) opera...

  • Page 35

    Abb 35 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 52. Three-phase inrush current detection (inrphar) operation accuracy at the frequency f=f n current measurement: ±1.5% of set value or ±0.002 x in ratio i2f/i1f measurement: ±5.0% of set value reset time +35 ms / -0...

  • Page 36

    Abb 36 feeder protection and control ref615 product version: 2.0 1mrs756379 d control functions table 57. Autoreclosure (darrec) operation accuracy ±1.0% of the set value or ±20 ms table 55. Arc protection (arcsarc) main settings parameter function value (range) step phase start value (operating pha...

  • Page 37

    Abb 37 feeder protection and control ref615 product version: 2.0 1mrs756379 d measurement functions table 58. Three-phase current measurement (cmmxu) operation accuracy depending on the frequency of the current measured: f n ±2hz ±0.5% or ±0.002 x in (at currents in the range of 0.01...4.00 x in) su...

  • Page 38

    Abb 38 feeder protection and control ref615 product version: 2.0 1mrs756379 d supervision functions table 64. Current circuit supervision (ccrdif) operate time 1) 1) including the delay of the output contact table 65. Current circuit supervision (ccrdif) main settings parameter values (range) unit d...

  • Page 39

    Abb 39 feeder protection and control ref615 product version: 2.0 1mrs756379 d 19. Display options the ied is available with two optional dis- plays, a large one and a small one. Both lcd displays offer full front-panel user-interface functionality with menu navigation and menu views. The large displ...

  • Page 40

    Abb 40 feeder protection and control ref615 product version: 2.0 1mrs756379 d 20. Mounting methods by means of appropriate mounting acces- sories the standard ied case for the 615 series ieds can be flush mounted, semi-flush mounted or wall mounted. The flush mount- ed and wall mounted ied cases can...

  • Page 41

    Abb 41 feeder protection and control ref615 product version: 2.0 1mrs756379 d 22. Selection and ordering data the ied type and serial number label identi- fies the protection ied. The label is placed above the hmi on the upper part of the plug- in-unit. An order number label is placed on the side of...

  • Page 42

    Abb 42 feeder protection and control ref615 product version: 2.0 1mrs756379 d h b f c a c a b n b b 1 a c n 1 x c # description 9 communication serial rs-485 (incl. Irig-b) a a glass fi bre st 1) 2) b b none n n 10 communication ethernet ethernet 100basefx (lc) a a ethernet 100basetx (rj-45) b b b n...

  • Page 43

    Abb 43 feeder protection and control ref615 product version: 2.0 1mrs756379 d h b f c a c a b n b b 1 a c n 1 x c # description 12 language english 1 english and german 3 13 front panel small lcd a large lcd b 14 option 1 auto-reclosing a arc protection 1) b arc protection and auto-reclosing 1) c no...

  • Page 44

    Abb 44 feeder protection and control ref615 product version: 2.0 1mrs756379 d 23. Accessories and ordering data table 69. Cables item order nr cable for optical sensors for arc protection 1.5 m 1mrs120534-1.5 cable for optical sensors for arc protection 3.0 m 1mrs120534-3.0 cable for optical sensors...

  • Page 45

    Abb 45 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 72. Supported functions function webhmi pcm600 ied signal configuration (signal matrix tool) - • iec 61850 communication configuration, goose (communication configuration tool) - • modbus ® communication configuratio...

  • Page 46

    Abb 46 feeder protection and control ref615 product version: 2.0 1mrs756379 d table 73. Supported abb solutions product version station automation com600 3.3 or later microscada pro 9.2 sp1 or later 25. Supported abb solutions the genuine iec 61850 implementation and abb’s connectivity package conce...

  • Page 47

    Abb 47 feeder protection and control ref615 product version: 2.0 1mrs756379 d 26. Terminal diagrams fig. 14 terminal diagram of standard configuration b.

  • Page 48

    Abb 48 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 15 terminal diagram of standard configuration d.

  • Page 49

    Abb 49 feeder protection and control ref615 product version: 2.0 1mrs756379 d fig. 16 terminal diagram of standard configuration e and f.

  • Page 50

    Abb 50 feeder protection and control ref615 product version: 2.0 1mrs756379 d 27. Certificates kema has issued an iec 61850 certificate level a 1 for ref615. Certificate number: 30710144-consulting 08-0115 28. References the www.Abb.Com/substationautomation por- tal offers you information about the ...

  • Page 51

    Abb 51 feeder protection and control ref615 product version: 2.0 1mrs756379 d 29. Functions, codes and symbols table 74. Ref615 functions, codes and symbols functions iec 61850 iec 60617 ansi protection functions three-phase non-directional overcurrent, low-set stage phlptoc 3i> 51p-1 three-phase no...

  • Page 52

    Abb 52 feeder protection and control ref615 product version: 2.0 1mrs756379 d functions iec 61850 iec 60617 ansi trip circuit supervision tcsscbr tcs tcm circuit-breaker condition monitoring sscbr cbcm cbcm disconnector position indication dcsxswi i o dc i o dc earthing switch indication essxswi i o...

  • Page 56

    Contact us abb oy, distribution automation p.O.Box 699 vsiting address: muottietie 2a fi-65101 vaasa, finland phone: +358 10 22 11 fax: +358 10 22 41094 www.Abb.Com/substationautomation 1mrs756379 d © copyright 2009 abb. All rights r eserved..