Ablerex MSRT-Pro 1KVA User Manual - page 16
30
9. Specifications
MODEL ITEM
1K
2K
3K
CAPACITY
VA / W
1000 VA/700 W
2000 VA/1400 W
3000 VA/2100 W
Voltage Rating
110/140/160-300 VAC (Based on load percentage
0-25% / 25-50% / 50-100%)
Frequency Rating
45-65 Hz
Phase
Single phase with ground
Power Factor
0.
≧
98 (with full linear load)
Generator Input
Supported
INPUT
Input Connection
10 A, IEC 320-C14
10 A, IEC 320-C14
16 A, IEC 320-C20
Voltage
230 V, adjustable to 200/208/220/230/240
Voltage
Regulation
within±1% until low-battery warning
Frequency
(Synchronized
Range)
3 Hz or 1 Hz (selectable)
Frequency
(Battery Mode)
50/60 Hz ±0.1% unless synchronized to line
Current Crest
Ratio
3:1
Harmonic
Distortion
< 3% at full linear load
< 7% at full non-linear load
Output Waveform
Pure sine wave
Outlets
(3)
10 A, IEC 320-C13
(6)
10 A, IEC 320-C13
(6)
10A, IEC 320-C13
Line
mode
<
105% continuous
106-120% for 30 seconds transfer to bypass
121-150% for 10 seconds transfer to bypass
>
150% Immediately transfer to bypass.
Buzzer continuously alarms.
Battery
mode
<
105% continuous
106-120% for 30 seconds shuts down
121-150% for 10 seconds shuts down
>
150% Immediately shuts down.
Buzzer continuously alarms.
Output
Overload
capacity
Bypass
mode
<
105% continuous
106-120% for 250 seconds shuts down
121-130% for 125 seconds shuts down
131-135% for 50 seconds shuts down
136-145% for 20 seconds shuts down
146-148% for 5 seconds shuts down
149-157% for 2 seconds shuts down
158-176% for 1 seconds shuts down
177-187% for 0.32 seconds shuts down
>
188% for 0.16 seconds shuts down.
Buzzer continuously alarms.
31
Line mode
90%
90%
90%
Battery mode
85%
85%
85%
Efficiency
ECO
mode
96% 96% 96%
Number of
batteries
2 4 6
Battery type
12 V/7.2 Ah Sealed, non-spillage, maintenance-free, lead acid
Rated Battery
Voltage
24 VDC
48 VDC
72 VDC
Backup time (half
load)
> 10 min.
> 10 min.
> 10 min.
Backup time (full
load)
> 3 min.
> 3 min.
> 3 min.
Standard
2.2 A
1.4 A
1 A
Charge
Current
(Max.)
External
8.8 A
11.2 A
8 A
Recharge time (to
90%)
3hr 3hr 3hr
Floating Mode
Charging Voltage
27.4Vdc±1% 54.8Vdc±1% 82.2Vdc±1%
Bluk Mode
Charging Voltage
30.0Vdc±1% 60.0Vdc±1% 90.0Vdc±1%
Battery
DC leakage
current
≤ 30 µA with no AC applied and the unit in the off position
AC to DC
0 ms
Transfer time
Inverter to Bypass
4 ms (Typical)
4 ms (Typical) / 0 ms (Optional)
DC start
Yes
Self
Diagnostics
By panel button or software control
Standard
Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass
Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/ Fault/
Overload
LED
Optional
Programmable Outlet1/ Programmable Outlet2
Front Panel
Button
ON (Alarm Silence)/ OFF (Test/Level Button)
Battery Mode
Sounds once every 1.5 seconds
Low Battery
Sounds once every 0.2 seconds
Overload
Sounds once every 3 seconds
Normal alarm
Sounds once every 3 seconds
Audible Alarm
Fault Continuous
tone
Short Circuit
Bypass mode : Fuse
Normal Mode : Output Breaker/Electronic Circuit
Battery Mode : Output Breaker/Electronic Circuit
Battery ABDM
Protection
EPO(Optional)
UPS shuts down immediately.