- DL manuals
- Abus
- Security System
- Terxon MX
- Installation Instructions Manual
Abus Terxon MX Installation Instructions Manual - page 77
77
UK
129 Deactivate external
To change the settings:
1. On the control unit, enter:
129
2. The LCD display shows: 129:ExtUnset OFF
3. Via the keypad, select from the following items
and press:
0
ExtUnset OFF
The user must first enter the entry zone
and thereby start the entry time before
he is able to deactivate using the
remote control.
1
ExtUnset OFF
The user can deactivate the alarm
centre without entering the entry zone.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
131 SIA report mode
To change the settings:
1. On the control unit, enter:
131
2. The LCD display shows: 131:Mode=Basic
3. Via the keypad, select from the following items
and press:
0
Mode=Basic
See the appendix for a description
1
Mode=Summary
See the appendix for a description
2
Mode=Intermd
See the appendix for a description
3
Mode=Full
See the appendix for a description
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
132 Transmit tampering as burglary
To change the settings:
1. On the control unit, enter:
132
2. The LCD display shows: 132:TA = BA OFF
3. Via the keypad, select from the following items
and press:
0
TA = BA OFF
The alarm centre transmits all SIA
reports as specified in command 131.
1
TA = BA ON
During an external alarm, the alarm
centre transmits tampering as a
burglary message and contact ID 130
instead of Contact ID 137.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
133 SIA Reset
To change the settings:
1. On the control unit, enter:
133
2. The LCD display shows: 133:SIA Rst OFF
3. Via the keypad, select from the following items
and press:
0
SIA Rst OFF
The alarm centre does not transmit any
SIA reset reports (fire, panic, technical,
tamper resets)
1
SIA Rst ON
The alarm centre transmits SIA resets.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
Summary of Terxon MX
Page 1
Uk uk intruder alarm panel terxon mx – installation instructions perfect security for the home and the office these installation instructions are an important product accessory. They contain important installation and operation information. Bear this in mind if you pass the product on to others. Sto...
Page 2: 1 Introduction
Uk uk 1 introduction dear customer, thank you for purchasing the burglar alarm panel terxon mx. You have purchased a product that has been designed and constructed according to the state-of-the- art, which complies with the current standards of domestic and european regulations. The ce has been prov...
Page 3: 3 Contents
3 uk 3 contents 1 introduction........................................................................................................................................2 2 usage in accordance with regulations ................................................................................................
Page 4
4 uk 16.1 program mode..........................................................................................................................32 16.2 overview of program menu ......................................................................................................33 16.3 settings in p...
Page 5: 4 Precautions
5 uk 4 precautions !Warning! To avoid fire and injury, please observe the following: • securely fasten the device at a dry location in the building. • ensure sufficient air circulation for the alarm centre. • do not expose the device to temperatures less than -10°c or more than 55°c. • the device is...
Page 6
6 uk 5 scope of delivery and accessories required scope of delivery • intruder alarm panel (“alarm centre”) • lcd operating panel • installation instructions • operating instructions you also need: alarm detector signal transmitter 12v/7ah rechargeable battery distributor cables optionally available...
Page 7
7 uk 6 notes on connection and extension options the burglar alarm panel is the basic device of an electronic security system for protecting your property (e.G.: apartment, house, garage, shops, etc.). In combination with other components such as detectors and signal transmitters, it secures the are...
Page 8
8 uk 7 notes on security system the terxon mx burglar alarm panel enables you to configure each of the 8 (max. 32) alarm zones optimally to suit your operating conditions. Recommendations: • distribute the external detectors in as small groups as possible to the zones (e.G., ground-floor detector to...
Page 9
9 uk the diagram below shows the correct usage of soldered distributors when connecting more than one detector to an alarm zone: as mentioned above, the alarm centre evaluates the alarm zones via the existing current flow. Most alarm detectors are normally closed, which means that the detectors inte...
Page 10
10 uk 8 overview of housing components 2 4 6 5 3 7 1 8 9.
Page 11
11 uk connection of 230v mains supply with primary fuse (t 250v 250ma). 230v ac / 12v dc transformer connector strip for siren, flashlight, programmable outputs, loudspeakers, 12vdc power supply and alarm zones. Connection of tamper contacts of the housing of the alarm centre. Terminal connector str...
Page 12: 9 Notes On Installation
12 uk 9 notes on installation 9.1 alarm centre fix the alarm centre to a flat, dry, vibration-free and heat- resistant surface. The cables for the power supply of the alarm centre, the alarm zones and the signalling equipment (siren, flashlight, any external loudspeakers, etc.) should be inconspicuo...
Page 13: 10 Notes On Wiring
13 uk 10 notes on wiring 10.1 alarm centre terminal connector strip for tamper and alarm zones. Com a/t: connections for detector tampering cct 1…8: connections for alarm zones 1–8 terminal connector strip for 12v dc power supply of external equipment (e.G., detectors) aux: +12v permanent voltage fo...
Page 14
14 uk 10.2 control units the burglar alarm panel can operate with up to four control units connected via a bus. The control units can be connected as a ring or star to the alarm centre. Connect the control unit as follows: to next control unit / alarm centre terminal connector strip: 0v to next cont...
Page 15
15 uk connection meaning ac mains supply unit (ac in) contact for 230v main supply unit kick start jumper (ks) connect the two contacts of this jumper to start the alarm centre without a 230v mains power supply. Battery contact (+ -) connecting plug from standby power supply comms interface contact ...
Page 16
16 uk 10.3 detectors 10.3.1 door and window contacts door and window contacts monitor the opening of doors and windows. To activate the entry/exit delay time, at least one contact should be mounted on the main entrance door on which a control unit is also mounted. For transparency reasons, no more t...
Page 17
17 uk 10.3.3 smoke detector this burglar alarm panel allows the connection of smoke detectors. For these, program zone type “fire” or “smoke detector”, depending on the function of the smoke detector. This programming result in a special acoustic warning for persons present (pulsed alarm tone). 10.3...
Page 18
18 uk 10.4 outdoor siren and flashlight to deter burglars and alert the neighbourhood, we recommend connecting a siren and a flashlight to the alarm centre. Note that these alarm devices should be mounted as high as possible (e.G. At roof height) and the cables should not be visible. Outdoor acousti...
Page 19
19 uk 10.5 dialler the built-in telephone dialler of the alarm centre allows the most varied system messages to be transmitted to various numbers. Important: if you are using a dsl splitter as part of your telephone connection then make sure that this is installed before the alarm centre. The high-f...
Page 20
20 uk 10.7 fitting and connecting a loudspeaker an optional 16ohm loudspeaker is connected to the contacts ls and +. The loudspeaker can be integrated directly in the housing of the alarm centre. Alternatively, the loudspeaker can be mounted as an additional internal alarm away from the alarm centre...
Page 21
21 uk 10.10 connecting expansion modules the 8-zone wire expansion modules and the 8-zone radio expansion modules are connected to the 4-wire bus as follows. Make sure when connecting the 8-zone wire expansion module that the zone terminations (cc / deol) from the alarm centre and the expansion modu...
Page 22: 11 Single System Or
22 uk 11 single system or partitioned system the alarm centre can be operated as a single system or as a partitioned system. In the single system, all locations, and 3 sections of the locations, are simultaneously activated or deactivated. All control units, zones and outputs work for the entire sys...
Page 23: 12 Term Declaration
23 uk 12 term declaration before starting to program the alarm centre, you should understand the terms used. To start with, here is an explanation of possible zone types and their properties. Nu – not used a zone to which nothing is connected and therefore not used should be closed with a jumper and...
Page 24: 13 General Terms
24 uk sd – fire alarm this zone works just like a fire zone. In contrast to a fire zone, the connected fire alarms can be reset by briefly switching off the power supply and no alarm is triggered. However, the reset must be made via a switch output. The program menu can be exited only when this zone...
Page 25: 14 Specimen Installation
25 uk 14 specimen installation this specimen installation is intended to explain the use of terxon mx. Here we use a system with two users. One user (de)activates the alarm system using code input, the other with a chip key. Furthermore, two sensors, a motion sensor (xevox eco) and door/window conta...
Page 26
26 uk please read the operating instructions of the se1000. Please take care that you use the pulse setting for the keyswitch.The circuit shown above enables you to activate/deactivate the alarm system by turning the key in either direction. Here too, the tamper line is not yet connected to the syst...
Page 27
27 uk 8. Now enter via the control unit: 0 and then the factory- set programming code 7890 the following shows on the display: mult syst? 9. Press key 1 to create a partitioned system. Press key 0 to create a single system like we do. 10. The display shows: progr. Mode 11. You are now in the program...
Page 28
28 uk now we program additional transistor outputs for the leds of the key switch. The yellow led should light in deactivated alarm state, and the red led in activated alarm state of the alarm system. To program the first additional transistor output op4 or the state of the red led, enter 151 on the...
Page 29
29 uk if you use a loudspeaker with the system, you can test it in the programming menu under item 094. You have now made all settings in the programming menu. Exit the programming menu by entering 099 and confirming with . You are now in the user menu. We now add two users to the system. The first ...
Page 30
30 uk if you use the siren, transistor output op1 (programming menu: menu item 081) must be set to “bell” (00). Use the resistors provided to connect the sg1900 (1kohm). Do not forget to change the connector of the internal battery from nc to battery (–). Se also the operating instructions of the si...
Page 31: 15 First-Time Usage
31 uk 15 first-time usage if you want to create your own configuration of the system and do not need the example of installation pay attention to the next steps. Please take notice of the important terms concerning the alarm panel. You can now put the alarm panel into operation. 1. Connect the 12v b...
Page 32: 16 Programming
32 uk 16 programming 16.1 program mode all input in program mode is made via the keypad. The lcd display gives you information about your input. For further information about the programming items, see page 30. Proceed as follows to change an item: 1. Via the keypad, enter the three-digit number of ...
Page 33
33 uk 16.2 overview of program menu country setting (000 n ) important: if you change the country setting, all system settings are reset to the country settings of the new country. Menu item setting (n) meaning 000 0 uk – great britain 1 i – italy 2 ee – spain 3 p – portugal 4 nl – netherlands 5 fr ...
Page 34
34 uk internal alarm (025 n ) menu item setting meaning 025 0 local alarm following 1 until deactivated alarm on failed activation (027 n ) menu item setting meaning 027 0 internal alarm 1 local alarm hide state display (028 n ) menu item setting meaning 028 0 never hide 1 hide after 180 secs. 2 hid...
Page 35
35 uk system auto active following alarm (040 n ) menu item setting meaning 040 0 never 1 once 2 twice 3 three times 4 always siren delay (041 n ) menu item setting meaning 041 0 no delay 1 1.5 min delay 2 3 min delay 3 5 min delay 4 10 min delay 5 15 min delay 6 20 min delay siren duration (042 n )...
Page 36
36 uk length of access code (056 n ) menu item setting meaning 056 0 4-digit code 1 6-digit code battery test (057 n ) menu item setting meaning 057 0 off 1 on bvvo tamper reset (058 n ) menu item setting meaning 058 0 reset by user 1 reset by installer siren tamper (059 n ) menu item setting meanin...
Page 37
37 uk forbikobler entry time (068 n ) menu item setting meaning 068 0 2 seconds 1 3 seconds 2 4 seconds 3 5 seconds 4 10 seconds 5 20 seconds 6 30 seconds 7 60 seconds 8 120 seconds 9 255 seconds forbikobler door lock (069 n ) menu item setting meaning 069 0 time lock 1 pulse lock zone behaviour at ...
Page 38
38 uk alarm behaviour at internal d (077 n ) menu item setting meaning 077 0 control unit 1 loudspeaker and control unit 2 local alarm 3 external alarm (siren and dialler) in a partitioned system 0 control unit 1 local alarm 2 external alarm (control unit + siren +dialler) exit time at internal d (0...
Page 39
39 uk control unit alarm (087 n ) menu item setting meaning 087 0 not activated 1 activated confirm alarm (089 n ) menu item setting meaning 089 0 confirm off 1 confirm on event memory (090 n ) menu item setting meaning 090 0 print memory 1 page backwards 3 page forwards exit memory toggle between d...
Page 40
40 uk 108 dynamic test call (108 n ) menu item setting meaning 108 0 off 1 on 109 three way call – uk only(109 n ) menu item setting meaning 109 0 off 1 on 110 download mode (110 n ) menu item setting meaning 110 0 local pcs 1 remote pc 112 call until response - download (112 n ) menu item setting m...
Page 41
41 uk 125 no signal „closed“ (125 n ) menu item setting meaning 125 0 off 1 no signal „closed“ when more than 1 zone is blocked language setting for osd menu (126 n ) menu item setting meaning 126 0 lang = english 1 long = italian 2 lang. = spanish 3 lang = port 4 lang = dutch 5 lang = french 6 lang...
Page 42
42 uk 25 alarm partition c 26 alarm partition d 30 active pulse 1 31 active pulse 2 32 active pulse 3 33 active pulse 4 34 inactive pulse 1 35 inactive pulse 2 36 inactive pulse 3 37 inactive pulse 4 behaviour of additional switch output 2 (152 nn ) menu item setting meaning 152 see setting for swit...
Page 43
43 uk user reset after confirmed alarm (164 n ) menu item setting meaning 164 0 user/installer 1 user/user 2 installer/installer duration of active pulse 1 2 3 4 (170 n n n n ) menu item setting meaning 170 00 latched output 01 – 12 pulse duration in seconds switch output active stable (171 n n n n ...
Page 44
44 uk fast format channel 1 (191 nn ) menu item setting meaning 191 00 not used 01 fire to follow 02 panic to follow 03 burglary to follow 04 active/inactive to follow 05 alarm cancellation 06 technical alarm 11 network fault 12 sabotage to follow 13 active to follow 14 inactive to follow 15 zone lo...
Page 45
45 uk entry delay group 2 (202 n ) see 201 entry delay group 3 (203 n ) see 201 entry delay group 4 (204 n ) see 201.
Page 46
46 uk 16.3 settings in program menu 000 country settings use this setting to configure the burglar alarm centre for the local country. When you load the country settings, all user-defined settings are discarded. If you only want to set the language of the control unit display, use menu item 126 (lan...
Page 47
47 uk after entering the zone name, enter the zone property. Zone properties are explained on pages 19 and 20 of these instructions. Enter the zone property as follows: 1. Enter the zone property via the keypad as follows: 00 nu – not used 01 pa – panic 02 fr – fire 03 na – immediate 04 24 – 24 hour...
Page 48
48 uk 4. Apart from the zone properties and zone attributes, you can make further settings for some zone properties. For example, for an “entry/exit” zone and an “entry to follow” zone, you have to define the entry delay time, and for a “shock sensor” zone, you have to define the sensitivity.. Enter...
Page 49
49 uk 022 changing the volume for internal alarm for changing the zone termination for the inputs of the burglar alarm centre. From the program level, do the following: 1. On the control unit, enter: 022 2. The lcd display shows: 022:chimevol=5 3. Via the keypad, select from the following items and ...
Page 50
50 uk 027 alarm on failed activation to change the property of the alarm on failed activation, proceed as follows: 1. On the control unit, enter: 027 2. The lcd display shows: 027:internal 3. Via the keypad, select from the following items and press: 0 internal if activation fails, the alarm is issu...
Page 51
51 uk 030 panic silent to change the property of the silent panic alarm: 1. On the control unit, enter: 030 2. The lcd display shows: 030:pa audible 3. Via the keypad, select from the following items and press: 0 pa audible when a panic alarm is triggered, the alarm centre generates a local alarm. 1...
Page 52
52 uk acknowledge the message. 1 engreset off if a system error is displayed, you have to enter the program code to acknowledge the message. Note: some events always require you to enter the program code. These are: failure/fault of a control unit failure of 12v power supply low battery in the alarm...
Page 53
53 uk 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 037 sabotage report deactivated to change this feature, proceed as follows: 1. On the control unit, enter: 037 2. The lcd display shows: 037:day tamp off 3. Via the keypad, select from the following...
Page 54
54 uk 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 040 system rearm to change the property of the siren duration: 1. On the control unit, enter: 040 2. The lcd display shows: 040:rearm=never 3. Via the keypad, select from the following items and pre...
Page 55
55 uk 042 siren duration to change the property of the siren duration: 1. On the control unit, enter: 042 2. The lcd display shows: 042:bell on=20 3. Via the keypad, select from the following items and press: 1 bell on=1.5 if an alarm is triggered, the local alarm is activated for 1.5 minutes. 2 bel...
Page 56
56 uk 045 entry/exit delay tone volume to change the property of the entry/exit delay tone volume: 1. On the control unit, enter: 045 2. The lcd display shows: 045:ee vol=5 3. Via the keypad, select from the following items and press: 0 ee vol=off entry/exit delay tone off 1-9 ee vol=1 / 2 / 3 / 4 /...
Page 57
57 uk 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 050 csid code to be able to use the remote reset function, you must set the alarm centres to installer reset (function 33 to 1) and assign the cs...
Page 58
58 uk 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 054 bvvo monitoring to change the property of the bvvo monitoring: 1. On the control unit, enter: 054 2. The lcd display shows: 054: bvvo sup off...
Page 59
59 uk 058 bvvo sabotage reset proceed as follows to change the property of the bvvo sabotage reset: 1. On the control unit, enter: 058 2. The lcd display shows: 058: bvvotamp off 3. Via the keypad, select from the following items and press: 0 bvvotamp off the user can carry out a reset in case of ta...
Page 60
60 uk changes its zone property during internal activation to entry/exit and starts the delay time if the zone triggers and during active internal activation. 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installe...
Page 61
61 uk alarm and the external siren are activated. 2 b=full on alarm, the control units, the internal signalling, the external sirens and the telephone dialler are activated. 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and...
Page 62
62 uk 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 068 forbikobler entry time this function sets the time that the forbikobler system allows for entry. An optional output for a door lock can be connected during this time. To change the property of t...
Page 63
63 uk 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 071 entry to follow behaviour on internal active (c) to change the zone property of the entry to follow zone at internal active (c): 1. On the co...
Page 64
64 uk key switch (see command) 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 073 alarm behaviour for internal (c) to change the alarm property for internal active (c): 1. On the control unit, enter...
Page 65
65 uk 076 behaviour of exit mode internal (d) to change the property of the exit mode for internal active (d): 1. On the control unit, enter: 076 2. The lcd display shows: 076: d=low tone 3. Via the keypad, select from the following items and press: 0 d=low tone the acoustic signal during the exit d...
Page 66
66 uk 079 exit delay time internal d to change the property of the exit delay time for internal active d: 1. On the control unit, enter: 079 2. The lcd display shows: 079: exit d=10 3. Via the keypad, select from the following items and press: 1 exit d=10 exit delay time for internal active d: 10 se...
Page 67
67 uk 081 relay output op1 to change the behaviour of relay output op1 on the alarm centre pcb: 1. On the control unit, enter: 081 2. The lcd display shows: 081: bell 3. Via the keypad, select from the following items and press: 00 bell this output is activated at local and external alarms. Set the ...
Page 68
68 uk 15 set comp1 this output is active for 10 seconds after the system has been activated. 16 unset comp1 this output is active for 10 seconds after the system has been deactivated or after an alarm has been deactivated. 17 system alarm this output is activated when the alarm centre has detected a...
Page 69
69 uk 33 unset 4 this output is activated for a definable time period (command 170) if the alarm centre is deactivated completely (a) or internally (b), (c) or (d) (command 171). 34 fire this output is activated if a fire alarm is triggered. The output remains active until the alarm is deactivated. ...
Page 70
70 uk 087 control unit alarm to change the properties of the connected control units: 1. On the control unit, enter: 087 2. The lcd display shows: 087:dual key off 3. Via the keypad, select from the following items and press: 0 dual key off if the function is deactivated, no alarm can be emitted by ...
Page 71
71 uk 3. The lcd display shows: 101: comms=off 4. Via the keypad, select from the following items and press: 0 comms=off the alarm centre does not use any communication devices. 1 comms=single single report. The alarm centre reports to a programmed telephone number (command 115) with an access numbe...
Page 72
72 uk 105 test call to change the properties of the test call: 1. On the control unit, enter: 105 2. The lcd display shows: 105:day hour=00 3. Via the keypad, select from the following items and press: 00 off a nn day hour daily test call to the alarm centre at the required time 01-24. B nn month da...
Page 73
73 uk 109 three way call – uk only to change the settings of the three way call: 1. On the control unit, enter: 109 2. The lcd display shows: 109:threewayoff 3. Via the keypad, select from the following items and press: 0 threewayoff three way call is switched off. 1 threewayon three way call is swi...
Page 74
74 uk the alarm centre interprets a call as a message from a remote pc. 10 to 90 seconds later, the remote pc calls again once and the alarm centre answers immediately on the first call. (set command 112 to a larger number of calls than other end devices on the line) 4. Confirm your input. On the co...
Page 75
75 uk 118 remotetel no 1 to change the settings: 1. On the control unit, enter: 118 2. The lcd display shows: 118:dl tel no 1 3. Via the keypad, enter the telephone number. Use key a to enter a 4-second pause (shown by a comma). U 4. Confirm your input. On the control unit, enter: . 5. The control u...
Page 76
76 uk 125 no signal „closed“ to change the settings: 1. On the control unit, enter: 125 2. The lcd display shows: 125:omit > 1 off 3. Via the keypad, select from the following items and press: 0 omit >1 off 1 omit >1 on the alarm centre does not transmit the „closed“ signal if more than 1 zone is lo...
Page 77
77 uk 129 deactivate external to change the settings: 1. On the control unit, enter: 129 2. The lcd display shows: 129:extunset off 3. Via the keypad, select from the following items and press: 0 extunset off the user must first enter the entry zone and thereby start the entry time before he is able...
Page 78
78 uk 143 contact id report rst to change the settings: 1. On the control unit, enter: 143 2. The lcd display shows: 143:mode=bas+res 3. Via the keypad, select from the following items and press: 0 mode=basic all reports with numbers as in the „cid code“ column apart from those marked with a # (see ...
Page 79
79 uk 153 additional outputs additional output 3 154 additional outputs additional output 4 155 additional outputs additional output 5 156 additional outputs additional output 6 157 additional outputs additional output 7 158 additional outputs additional output 8 159 inverting additional outputs you...
Page 80
80 uk 162 confirm external sirens to change the settings: 1. On the control unit, enter: 162 2. The lcd display shows: 162:conf ext off 3. Via the keypad, select from the following items and press: 0 conf ext off external siren is on for unconfirmed alarm (command 89=1) 1 conf ext on external siren ...
Page 81
81 uk 2. The lcd display shows: 171: set 1 abcd 3. Via the keypad, enter the activation level. A = overall active, b, c and d for internal active b, c or d. 4. To confirm, press: 5. The lcd display shows: 170: set 2 abcd 6. In the same way, enter activation level 2 via the keypad. 7. Continue until ...
Page 82
82 uk 3. Use the keypad to define: 00 =off 01 =on 4. To confirm, press: 5. The lcd display shows: 175: pa 2 on 6. In the same way, enter the fire 2 option via the keypad. 7. Continue until all outputs are entered. 8. The control unit acknowledges your input with a double “beep” tone and shows instal...
Page 83
83 uk 2. The lcd display shows: 185:ksautorstoff 3. Via the keypad, select from the following items and press: 0 ksautorstoff the user must manually reset any triggered zones. 1 ksautorston the system automatically resets zone types km or kf when the user activates using the key switch. 4. Confirm y...
Page 84
84 uk 4. Confirm your input. On the control unit, enter: . 5. The control unit acknowledges your input with a double “beep” tone and shows installer mode. 192 fast format channel 2 see command 191. Default setting: panic to follow 193 fast format channel 3 see command 191. Default setting: burglary ...
Page 85
85 uk 16.4 programming partitions if you are using a partitioned system then you can use the following commands for programming the partitions. 1. Use the commands 01 to 16 and x17 to x32 to assign a partition to each zone. - each zone belongs to partition a (factory setting). - press key a to assig...
Page 86
86 uk 16.5 examples for a partitioned system the following example shows a building with an entry area and two office areas. The two office areas are occupied by two different companies. The entry area is used by both companies. With a partitioned system, two separate alarm centres are simulated by ...
Page 87
87 uk 16.6 test functions 090 event memory the alarm centre stores the last 250 events. Each event is stored with date and time. The event memory can be viewed via the program menu. 1. On the control unit, enter: 090 2. The lcd display shows the latest events first. 3. You can page forwards and back...
Page 88
88 uk fire z -- rstr zone nn fire alarm reset soak fail z -- zone nn sensor test failed bell tamper rst siren tamper alarm reset bell tamper siren tamper alarm triggered system rearmed system automatically rearmed system startup system supplied with power and started tamper z -- zone nn has triggere...
Page 89
89 uk 097 walk test if the walk test is activated, you can trigger all zones of the alarm centre to check their function. Activate the walk test and then trigger all zones in sequence. You should also test the tamper contact. Proceed as follows: 1. On the control unit, enter: 097 . 2. The lcd displa...
Page 90
90 uk 16.7 sia report mode reason event sia code cid code (1) alarm confirm bv 139 burg ba 130 burg restore br 130‡ duress ha 121 exit timeout ea - expander tamper 133 sia rst 137 expander tamper restore tr: 137‡ fire fa 110 fire restore fr 110‡ forbi interface tamper 133 sia rst 137 forbi interface...
Page 91
91 uk telco2 fault restore lr - zone omit bb 573 summary event sia code cid code ac lost at 301 ac restore ar 301‡ alarm abort bc 406 anti mask zone open (2) bt 380 anti mask zone tamper (2) bt 380 anti mask zone restored (2) bj 380 aux trouble yp - aux restored yq - batt missing ym 311 batt restore...
Page 92: 17 Technical Data
92 17 technical data voltage supply external voltage supply: 230v ac +/-10% (ambient temperature 20°c) external power consumption: 1.0a maximum internal voltage supply: 19vac / -10% internal power supply: 2.0a maximum cpu power consumption: 150ma maximum power consumption of control unit: 35ma maxim...
Page 93: 18 Troubleshooting
93 uk 18 troubleshooting the alarm centre shows no reaction although mains and battery power are present. Check mains and battery connections and the three fuses. Replace fuses with fuses of similar rating if necessary. The display shows one or more open zones (although all alarm contacts seem to be...
Page 94
94 19 index of programming functions account name ............................................... 49 additional entry delay .................................. 69 additional outputs ........................................ 78 alarm behaviour for internal (c).................. 64 alarm behaviour for i...
Page 95
95 uk line loss report............................................. 72 measuring the resistance............................. 89 no signal „closed“........................................ 76 number of home „beep“ calls ..................... 83 panic reset ................................................
Page 96: 20 System Plan
96 20 system plan this system plan provides information on components installed in your alarm system, their location and functioning, as well as any modifications. The system plan is always a component on the alarm system and should be stored in a safe place. Zone description fully active a internal...