Bacchus BCS2000 Installation Manual

Other manuals for BCS2000: Installation Manual

Summary of BCS2000

  • Page 1

    Installation manual bcs2000/3000 supplies needed for installation 1. 3/8” and 5/8” copper tubing. 2. 1/4” copper water supply 3. 1/4” condensate vinyl drain tube/tube clamps 4. Provide 120v 15a circuit for indoor evaporator, and 120v/230v 30a, single or three phase (dependent upon your condensing un...

  • Page 2

    5. Repeat the same procedure from the 5/8” suction line of the condensing unit. Solder to a 5/8” run of a 5/8” x ½” x ½” tee. Run ½” copper to the suction line connections in each evaporator. 6. Power from disconnect (recommended) 12-2/with ground to the condensing unit. 7. Check low pressure contro...

  • Page 3

    5. The first port on the left includes two pieces of 18-2 that should be connected to each slave module in both evaporators at #1 and #2 terminals. These connections will shut down the system if there is ever a high water condition in either evaporator. They are connected parallel to each safety flo...

  • Page 4

    9. Locate the nearest water supply. Shut off water supply to the line and braze in the cps water supply compression adapter. Connect the water filter to the fitting and run ¼” copper from the filter thru the evaporator ceiling opening and cap, and attach to the water solenoid inlet in each evaporato...

  • Page 5

    Can be mounted up to 75 feet from the microprocessor inside the evaporator. 2. Mount the humidity sensor (xh10p) to a discreet side wall location @ 6ft. From the floor. Bring the two lead wires from the sensor, and attach to the + and – lead wires indicated. White lead to the #2 terminal, and red le...

  • Page 6

    Charging the system 1. Evacuate and pressure test the system. This can be accomplished by charging with nitrogen to 75 lbs and checking your gauges for any sign of a leak. Evacuate the system to 500 microns. 2. Charge the system with r134a until the sight glass goes clear. Initial charge will be 6.3...

  • Page 7

    This will prevent any possible mold build up. 4. Check the operation of the condensate pump, and make sure the water misting fitting is acting properly, by allowing water to flow thru it. Clean with vinegar if clogged and change the water filter. 5. Check the electronic controller for any alarm cond...

  • Page 8

    Compressor 1/2 hp 115v .65 hp 115v 1 hp 115v 1 ½ hp hp/voltage 208/230-1v electrical compressor rla 10a 11a 8a 12.1a compressor lra 53a 51a 43a 49a cond. Unit mfs 20a 30a 15a 17.6a cond. Unit mca 13.4a 13.4a 11.3a 12.1a btu capacity 40f 4857 6250 10200 (100 amb) 12,185 suc, 110 amb. Phone: 937-665-0...