Air Conditioning & Refrigeration
When ordering this product, you must specify
3 codes. These 3 codes will build up a part number.
Codes must be listed in the following sequence:
Code A- Model Number
Code B- Number of Zones
Code C- Input Power Type
For example, to order a 4-zone, 120VAC Ammonia
Monitor, you would order a: AGM300-11-1
Remote Display Modules, options and accessories
must be ordered as separate line items.
SPECIFICATIONS
NDIR, Multi-Zone Sample Draw Systems
Refrigerants:
HGM300 Model
CFC:
R-11, R-12, R-113, R-114, R-502,
HFC:
R-404a (HP62), R-407a, R-407c
(AC9000), R-134a, R-410a (AZ20),
R-507 (AZ50), R-508b (SUVA95)
HCFC:
R-22, R-123, R-124, R-500, R-503,
R-401a (MP39), R-402a (HP80),
R-40b (HP81), R-408a, R-409a, R-23
HALON:
1301
Measuring Range: 0 to 10,000 ppm
AGM300 Model
Ammonia (NH
3
- also known as R-717)
Measuring Range: 25 to 10,000 ppm
Inputs:
4 point standard, expandable to 16 points in
4 point increments
Output Signal:
3 SPDT, 5 Amp, 240 VAC rated alarm relays
and 1 SPDT, 5 Amp, 240 VAC rated system
fault relay, plus a Digital Display w/ an optional
dual 4-20 mA DC analog output
Detector Type:
Non-dispersive infrared
Sensitivity:
All gases 1 ppm
HGM300
All gases ±10 ppm from 0 to 100 ppm,
Accuracy:
±10% of reading from 100 to 10,000 ppm
AGM300
± 10 ppm from 25 to 100 ppm
Accuracy:
± 10% of reading from 100 to 10,000 ppm
Front Panel Display:
Green LED indicates when unit is operating
properly, Red LED indicates when any monitored
point is above its alarm setting, Yellow LED
indicates a clogged sample line or other
system fault
Response Time:
5 to 120 seconds, depending on sample tube
length and gas concentration
Max. Monitoring Distance: Up to 500 feet from measuring point to
monitor
Power:
120 VAC, 60 Hz (Standard)
240 VAC, 50 Hz (Export)
240 VAC, 60 Hz (Domestic)
Size/Weight:
17" L x 12" W x 5.5" D / 15 lbs
(43.18cm L x 30.48cm W x 13.97cm D / 6.8 Kg)
SPECIFICATIONS REMOTE
DISPLAY
MODULES
RDM800 Model
Compatible with HGM300 Model
ADM800 Model
Compatible with AGM300 Model
Inputs:
Accepts from one to four inputs via RS-485
from up to four HGM300 Refrigerant Monitors
Display:
Backlit LCD displays the measured point in ppm
Trend Mode / Data logging:
User may select a graphical display of the
ppm trend for any measured point
(100 data entries per point)
Output Signal Floating Ground: 2 SPDT, 5 Amp, 240 VAC assignable alarm relays
Alarm Indications:
Channel display flashes, red light flashes,
alarm signal sent via RS-485
Input Fault Indication:
Yellow light flashes and the LCD indicates
location of input fault
Max. Monitoring Distance:
Maximum of 4,875 wiring feet from the
furthest HGM300 to the RDM800 Display
Power:
240VAC / 50/60 Hz, 120 VAC/60Hz
Size/Weight:
11" L x 10" W x 3" D / 5 lbs (wall mounted)
28cm x 25.4cm x 7.6cm/2.3Kg
ORDERING INFORMATION for Monitors
OPTIONS / ACCESSORIES
PART NO.
DESCRIPTION
3015-4121
120VAC surge protector
3015-4122
230VAC surge protector
3015-4123
4-20 mA dc surge protector (two required)
3015-3133
Dual 4-20 mA dc output kit
3015-3069
External Visual alarm 120VAC
3015-3070
External Audible alarm 120VAC
3015-3076
External Audible / Visual alarm 120 VAC
3015-3423
Annual maintenance kit
3015-3235
Air sample tubing (250’per roll for standard refrigerants)
0304-2742
Air sample tubing (Ammonia only)
ORDERING INFORMATION for Remote Display Modules
3015-2875
RDM800 120VAC / 60 Hz
3015-2885
RDM800 240VAC / 50/60 Hz
3015-4195
ADM800 120VAC / 60 Hz
3015-4196
ADM800 240VAC / 50/60 Hz
Code A
Model Number
HGM300
For use with CFC, HFC, HCFC and Halon Refrigerants
AGM300
For use with Ammonia Refrigerants
Code B
Number of zones and connection type
-11
4 Zones with metal tube fittings
-12
8 Zones with metal tube fittings
-13
12 Zones with metal tube fittings
-14
16 Zones with metal tube fittings
Code C
Input Power Type
-1
120VAC / 60 Hz (Standard)
-2
240VAC / 50 Hz (Export Applications Only)
-3
240VAC / 60 Hz (Domestic Applications Only)
System design supports compliance to the refrigerant monitoring
requirements of ANSI / BSR ASHRAE 15. Certified in compliance to UL
#3101-1, CE #EN613262, and EN61010-1.