Banner DF-G1-NR-2M Quick start manual - page 11
Method
Action
Result
SET Button
•
Present sensing condition
•
Click the SET rocker button
Threshold Condition Accepted
Displays read "wInd SEt" then
alternate "PASS" with % Offset10;
Sensor returns to Adjust mode
Threshold Condition Not Accepted
Displays read "wInd SEt" then
alternate "FAIL" with minimum %
Offset10 for sensing condition; Sensor
returns to Adjust mode
Remote Input
•
Present sensing condition
•
Single-pulse the remote input
T
3. Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to Run
Display: Red - Signal Level; Green -
Window Center (see
Figure 5
on page
11 for instructions on how to display
upper and lower thresholds)
Remote Input
No action required; sensor returns to
Run mode automatically
Figure 5. Upper and Lower Thresholds
Light SET
•
Sets a threshold a programmable % offset below the presented condition
•
Changes output state on any condition darker than the threshold condition
•
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
•
Recommended for applications where only one condition is known, for example a stable light background with
varying darker targets
•
See
Program Mode
on page 5 for programming the Offset Percent setting
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset below the
presented condition. When a condition darker than the threshold is sensed, the output either turns ON or OFF, depending
on the LO/DO switch setting (see LO/DO Switch in
Top Panel Interface
on page 3).
10 See
Troubleshooting
on page 16 for more explanation of the % Offset displayed after the Window SET method
DF-G1 Expert
™
Dual Display Fiber Optic Light Receiver
P/N 172436 Rev. C