Bard CompleteStat CS9B-THO,CompleteStat CS9B-THOCCompleteStat CS9BE-THO,CompleteStat CS9BE-THOC Installation & Operation Manual

Summary of CompleteStat CS9B-THO,CompleteStat CS9B-THOCCompleteStat CS9BE-THO,CompleteStat CS9BE-THOC

  • Page 1

    Manual 2100-566d page 1 of 20 controller installation operation & quick start bard completestat™ cs9b-tho, cs9b-thoc cs9be-tho, cs9be-thoc manual: 2100-566d supersedes: 2100-566c file: tab 19 date: 11-05-13.

  • Page 2: Table of Contents

    Manual 2100-566d page 2 of 20 table of contents installation note ............................................................................ Page 3 controller installation ................................................ Page 3 controller connections ..................................................

  • Page 3

    2100-566d page 3 of 20 *install note: for optimum temperature sensor performance, the bard completestat tm must be mounted on an interior wall and away from any heat sources, sunlight, windows, air vents, air circulation obstructions, and/or any other cause of erratic or false temperature sensing. C...

  • Page 4

    2100-566d page 4 of 20 basic operation: home, main menu, and override screens navigate the menus & change settings by pressing a combination of various arrow buttons/the enter button. Push the: enter button to select and/or exit value editing up or down button to move among entries 2 right or left b...

  • Page 5

    2100-566d page 5 of 20 20. Enter button to highlight current economizer selection 21. Up/down buttons to choose from available economizer options: none = no economizer, or standard vent. Pkg. (erv/crv/mfad) en/dis (engage/disengage) = economizer in system 22. Enter button to select/save appropriate ...

  • Page 6

    2100-566d page 6 of 20 9. Enter button to save choice 10. Left button (3x) to home screen. System enable – to enable heating / cooling from home screen, press: 1. Right button to access the main menu screen 2. Down button through entries to highlight system 3. Enter button to select system and enter...

  • Page 7

    2100-566d page 7 of 20 sequence of operation: conventional 1h/1c, 2h/1c, 1h/2c, or 2h/2c without economizer operation g y/o y1 y2 w1/e w2 o/b d a fan only x 1 st stage cooling x x 2 nd stage cooling (if employed) x x x 1 st stage heating x x 2 nd stage heating (if employed) x x x dehumidification x ...

  • Page 8

    2100-566d page 8 of 20 sequence of operation: two-stage heat pump, no economizer operation g y/o y1 y2 w1/e w2 o/b d a fan only x 1 st stage cooling x x 2 nd stage cooling x x x 1 st stage heating x x x 2 2 nd stage heating x x x x 2 3 rd stage heating x x x x 3 x 2 emergency heat x x x 3 dehumidifi...

  • Page 9

    2100-566d page 9 of 20 wiring diagram table wiring diagram no. Unit type (note a) completestat™ model cs9b(e)- completestat™ system type system stages setting economizer setting use with bard units ventilation system vent control type 1 a/c tho, thoc a/c 2h/2c none 1 or 2-stage a/c w/ or w/o elec. H...

  • Page 10

    2100-566d page 10 of 20 wiring diagram 1: conventional 1h/1c, 1h/2c, 2h/1c, or 2h/2c, with or without dehumidification and ventilation. Wiring diagram 2: conventional 1h/1c, 2h/1c with honeywell w7459a control economizer, with or w/o dehum. Remove jumper for 2-stg. Heat (15kw or more) field-installe...

  • Page 11

    2100-566d page 11 of 20 wiring diagram 3: conventional 1h/1c, 2h/1c with honeywell w7220 jade tm control economizer, with or w/o dehum. Wiring diagram 4: conventional 1h/2c, 2h/2c with honeywell w7459a control economizer remove jumper for 2-stg. Heat (15kw or more) field-installed wires and jumpers ...

  • Page 12

    2100-566d page 12 of 20 wiring diagram 5: conventional 1h/2c, 2h/2c with honeywell w7220 jade tm control economizer wiring diagram 6: heat pump 2h/1c, 3h/1c, with or without dehumidification and ventilation. Remove jumper for 2-stg. Aux. Heat (15kw or more) factory-installed wires and jumpers field-...

  • Page 13

    2100-566d page 13 of 20 wiring diagram 7: heat pump 2-stage, with or without dehumidification and ventilation. Wiring diagram 8: heat pump 1-stage, with honeywell w7459a control economizer, with or w/o dehum. Ch*s-series heat pumps use “dh” dehumidification terminal field-installed wires and jumpers...

  • Page 14

    2100-566d page 14 of 20 wiring diagram 9: heat pump 1-stage, with honeywell w7220 jade tm control economizer, with or w/o dehum. Wiring diagram 10: heat pump 2-stage, with honeywell w7459a control economizer, with or w/o dehum. Completestat programmed for damper/economizer: en/dis field-installed wi...

  • Page 15

    2100-566d page 15 of 20 wiring diagram 11: heat pump 2-stage, with honeywell w7220 jade tm control economizer, with or w/o dehum. Wiring diagram 12: gas/electric 1h/1c with or without dehumidification and ventilation package ch*s-series heat pumps use “dh” dehumidification terminal 3 field-installed...

  • Page 16

    2100-566d page 16 of 20 wiring diagram 13: gas/electric 1h/2c with or without dehumidification and ventilation package wiring diagram 14: gas/electric 1h/1c with honeywell w7459a control economizer, with or w/o dehum. Wire not used on mfad ventilation option 3 w**g-series uses “a” terminal for venti...

  • Page 17

    2100-566d page 17 of 20 wiring diagram 15: gas/electric 1h/2c with honeywell w7459a control economizer, with or w/o dehum. Wiring diagram 16: i-tec 2-stage heat pump series with no ventilation package completestat programmed for damper/economizer: en/dis 2 wire for dehumidification units only 1 fiel...

  • Page 18

    2100-566d page 18 of 20 wiring diagram 17: i-tec 2-stage heat pump series with crv ventilation package wiring diagram 18: i-tec 2-stage hp series with erv ventilation package & 8403-067 co 2 detector (fully modulating) wire not needed if aux. Heat strip is 10kw or less 2 wire for dehumidification un...

  • Page 19

    2100-566d page 19 of 20 wiring diagram 19: q-tec qa**/q**a-series 1-stage air conditioners, with or without ventilation and dehumidification wiring diagram 20: q-tec qh**/q**h series 1-stage heat pump, with or without ventilation and dehumidification q-series with factory installed thermostat had no...

  • Page 20

    2100-566d page 20 of 20 wiring diagram 21: qw*s-series 2-stage heat pump, with or without ventilation and dehumidification bard completestat tm should be fully operational at this point. For further controller enhancement or operation detail, please consult the advanced programming section. Q-series...