Bard CompleteStat CS9B-THO,CompleteStat CS9B-THOCCompleteStat CS9BE-THO,CompleteStat CS9BE-THOC Installation & Operation Manual - page 9
2100-566D
Page 9 of 20
Wiring Diagram Table
Wiring
Diagram
No.
Unit Type
(Note A)
CompleteStat™
Model CS9B(E)-
CompleteStat™
System Type
System
Stages
Setting
Economizer
Setting
Use with Bard
Units
Ventilation System
Vent
Control
Type
1
A/C
THO, THOC
A/C
2H/2C
None
1 or 2-Stage A/C w/
or w/o Elec. Heat
CRV, ERV, MFAD
On/Off
2
A/C
THO, THOC
A/C
2H/2C
EN/DIS
1-Stage A/C with or
w/o Elec. Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
3
A/C
THO, THOC
A/C
2H/2C
EN/DIS
1-Stage A/C with or
w/o Elec. Heat
ECONWM Factory "T" or "W" Economizer w/JADE
W7220 Control
On/Off
4
A/C
THO, THOC
A/C
2H/2C
EN/DIS
2-Stage A/C with or
w/o Elec. Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
5
A/C
THO, THOC
A/C
2H/2C
EN/DIS
2-Stage A/C with or
w/o Elec. Heat
ECONWM Factory "T" or "W" Economizer w/JADE
W7220 Control
On/Off
6
HP
THO, THOC
HP
1 Stage
None
1-Stage HP with or
w/o Elec. Heat
CRV, ERV, MFAD
On/Off
7
HP
THO, THOC
HP
2 Stage
None
2-Stage HP with or
w/o Elec. Heat
CRV, ERV, MFAD
On/Off
8
HP
THO, THOC
HP
1 Stage
EN/DIS
1 & 2-Stage HP
with or w/o Elec.
Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
9
HP
THO, THOC
HP
1 Stage
EN/DIS
1-Stage HP with or
w/o Elec. Heat
ECONWM Factory "T" or "W" Economizer w/JADE
W7220 Control
On/Off
10
HP
THO, THOC
HP
2 Stage
EN/DIS
2-Stage HP with or
w/o Elec. Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
11
HP
THO, THOC
HP
2 Stage
EN/DIS
2-Stage HP with or
w/o Elec. Heat
ECONWM Factory "T" or "W" Economizer w/JADE
W7220 Control
On/Off
12
Gas/Electric
THO, THOC
A/C
1H/1C
None
1-Stage A/C with
Gas Heat
CRV, ERV, MFAD
On/Off
13
Gas/Electric
THO, THOC
A/C
1H/2C
None
2-Stage A/C with
Gas Heat
CRV, ERV, MFAD
On/Off
14
Gas/Electric
THO, THOC
A/C
1H/1C
EN/DIS
1-Stage A/C with
Gas Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
15
Gas/Electric
THO, THOC
A/C
1H/2C
EN/DIS
2-Stage A/C with
Gas Heat
EIFM Factory "E" Economizer w/W7459 Control
On/Off
16
I-TEC HP
THO, THOC
HP
2 Stage
None
2-Stage HP with or
w/o Elec. Heat
None
On/Off
17
I-TEC HP
THO, THOC
HP
2 Stage
None
2-Stage HP with or
w/o Elec. Heat
CRV, ERV
On/Off
18
I-TEC HP
THO
HP
2 Stage
None
2-Stage HP with or
w/o Elec. Heat
Modulating ERV, use –THO plus 8403-067 CO2
controller
Modulating
19
Q-TEC QA
THO, THOC
A/C
2H/1C
None
1-Stage A/C with or
w/o Elec. Heat
CRV, ERV
On/Off
20
Q-TEC QH
THO, THOC
HP
1 Stage
None
1-Stage HP with or
w/o Elec. Heat
CRV, ERV
On/Off
21
QWS
THO, THOC
HP
2 Stage
None
2-Stage Geo/Water
Source HP
CRV, ERV
On/Off
Note A; Either THO or THOC version can be used. For THO the vent output "A" limits vent operation to Occupied periods. For THOC the vent output "A" operates vent based on CO2 level.