*INSTALL NOTE: For optimum temperature sensor performance, the Bard CompleteStat
TM
must be mounted on an
interior wall and away from any heat sources, sunlight, windows, air vents, air circulation obstructions, and/or any other
cause of erratic or false temperature sensing.
Controller Installation: Mounting Controller
1.
Complete rough-in wiring using a minimum 18 AWG solid-conductor control wiring, see Low Voltage Wiring
Diagrams in this Manual for exact number of conductors.
2.
Turn the hex screws in the bottom and top of the controller clockwise (inward) until they clear the cover.
Remove base plate from controller.
3.
Route completed wiring through base plate.
4.
With the embossed “UP” arrows of the base plate pointing in the appropriate direction, fasten the base plate to
the desired wall location. A vertical/horizontal 2x4 wall handybox can be used for CO
2
-Sensing CompleteStat™,
and a vertical-only 2x4 wall handybox can be used for Non-CO
2
-Sensing CompleteStat™.
5.
Make appropriate control wire connections (see Low-Voltage Wiring Manual) to terminal blocks.
6.
Replace controller over base plate, being careful not to pinch/dislodge connections.
7.
Turn hex screws in bottom/top of controller counter-clockwise (outward) to secure cover.
Controller Connections: Terminal legend
Terminal
Function
Type
Form
D
Dehumidification
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs D, A, W2
Power
A
Ventilation Call
Output
24VAC SPST RELAY
W2
2
nd
Stage Heating
Output
24VAC SPST RELAY
W1/E
1
st
Stage Heating/Emer. Heat
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs W1/E, Y2, Y1
Power
Y2
2
nd
Stage Compressor
Output
24VAC SPST RELAY
Y1
1
st
Stage Compressor
Output
24VAC SPST RELAY
Y0
Economizer
Output
24VAC SPST RELAY
SC
24VAC to Relay Outputs YO, O/B, G
Power
O/B
Reversing Valve
Output
24VAC SPST RELAY
G
Indoor Blower
Output
24VAC SPST RELAY
IN9
Not Used
ROS
Remote Occupancy Sensor
Input
Dry Contact (Input to GND)
GND
REM
Remote Temperature Sensor
Input
10K Type II Thermistor
+B
Communications
-A
Communications
OAT
Outdoor Air Temperature Sensor
Input
10K Type II Thermistor
LAT
Leaving Air Temperature Sensor
Input
10K Type II Thermistor
GND
Control Ground
L
Lockout Alarm
Input
Dry Contact (Input to GND)
Com
24VAC Common
Power
24V
24VAC Hot
Power