Cabletron Systems MMAC-M3FNB Overview And Setup Manual - Chapter 2
INSTALLATION REQUIREMENTS AND SPECIFICATIONS
Page 2-1
CHAPTER 2
INSTALLATION REQUIREMENTS
AND SPECIFICATIONS
This chapter describes the following:
•
Site guidelines that must be met before installing an
MMAC-M3FNB onto your network
•
MMAC configuration guidelines
•
Operating specifications for the MMAC-M3FNB enclosure and
power supply module
2.1
SITE GUIDELINES
The following guidelines must be followed when you select a site for
the MMAC-M3FNB. If not, unsatisfactory network performance may
result.
•
An unrestricted free surface area of 8.3" (21.1 cm) high,
19" (48.3 cm) wide, and 17" (43.2 cm) deep is needed for
the MMAC-M3FNB enclosure.
The unit should be mounted
to allow the free flow of air around the chassis.
•
If the MMAC-M3FNB is to be placed on a shelving unit, the
shelf must be able to support 35 lb (15.9 kg) of static weight.
•
A USA standard 3 prong power receptacle must be located
within 2.13 m (7 ft.) of the site.
•
The temperature of the location must be maintained between
5
°
and 40
°
C (41
°
to 104
°
F). Temperature changes of greater
than 10
°
C (18
°
F) per hour must not occur.
The handles provided on the fan tray and power supply
are for installation only; they are not designed to
support the full weight of the chassis, and should not
be used as carrying handles.