CADDX NX-148 Installation Manual

Other manuals for NX-148: User Manual, User Manual
Manual is about: lcd keypad

Summary of NX-148

  • Page 1

    Table of contents entering the program mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 selecting the module to program . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 programming a location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 nx-148 libr...

  • Page 2

    2 entering the program mode to enter the program mode, press [ u ]-[8]. At this time, the lcd screen will prompt you for the programming code. Next, enter the "go to program code" (factory default is [9]-[7]-[1]-[3]). If the "go to program code" is valid, the lcd screen will prompt you for the devic...

  • Page 4

    4 [ u ]-[9]-[2] programming custom messages in the keypad notes: the messages (custom, zone, and shutdown) are transferred to other lcd keypads after this mode is exited. All keypads must be addressed and enrolled for this to happen. Set the keypad numbers with [ u ]-[9]-[4] prior to programming cus...

  • Page 5

    5 open 75 9/25 17:57 p3 u [ u ]-[9]-[4] set keypad number and partition 1) enter [ u ]-[9]-[4] the lcd screen will prompt for a code. 2) enter [program code] the lcd will now prompt you for the keypad number followed by [ u ]. The current keypad number will be displayed in the lower right hand corne...

  • Page 6

    6 [ u ]-[0] adjust keypad tone 1) press [ u ]-[0] the lcd screen will prompt you to use the scroll keys located on the right of the display to raise or lower the tone. 2) use the up scroll key to raise the tone. Use the down scroll key to lower the tone. The keypad will emit a continuous tone to all...

  • Page 7

    7 4) enter a partition number. Note: the default allows access to all partitions. The first keypress will remove access to the partition. To reestablish access, press the partition number again. When completed, press [ u ]. The lcd screen will prompt you for the next user code. 5) if another user co...

  • Page 8

    8 ready 12345678 armed 1234-678 system ready type code to arm 12-45-78 disarm --3 67- arm 12-4- -78 disarm - - 3-56- - arm displays in the partitioning master mode armed and ready status the lcd screen will display the armed and ready status of all eight (8) partitions if any or all of the areas is ...

  • Page 9

    9 area 5 ready type code to arm service required type u 2 for help control over current control siren trouble control box tamper control phone trouble control fail to communicate control ground fault control loss of time control power trouble control low battery expansion aux comm fail area 5 is sel...

  • Page 10

    10 expansion power trouble expansion low battery expander box tamper expansion over-current expansion trouble expansion siren trouble zone tamper, press u zone low battery, press u zone lost, press u zone trouble, press u the main power to an expansion power supply is not on. An expansion power supp...

  • Page 11

    11 nx-124 maximum wire run (note: these numbers are for one keypad at the end of the wire. When connecting more than one keypad to the end of the wire, a heavier gauge wire will be required.) when connected to nx-8 when connected to nx-320 length in feet wire gauge wire gauge 250' 24 22 500 20 18 10...

  • Page 12

    Specifications operating power 12 vdc regulated supplied by nx-8 or nx-320 operating temperature 32 to 120 degrees f current draw 110 ma maximum 75 ma without sounder lcd keypad dimensions 6.4" wide 5.3" high 1.0" deep shipping weight 2 lbs. Five year limited warranty caddx controls, inc. Guarantees...