Eaton Power Xpert 9395P Installation And Operation Manual - page 17
Eaton Power Xpert
™
9395P Sync Control Installation and Operation Manual
S
P-164000502 Rev 1
3-1
Chapter 3
Installation
W
A
R
N
I
N
G
S
Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation. Risk
of electrical shock.
S
Shut down all sources of power to the Eaton 9395P UPS or SSBM system before connecting the control
wiring to the Eaton Sync Control enclosure and UPS. Hazardous voltages exist inside the UPS or SSBM and
in the Eaton Sync Control enclosure. Check all terminal conductors with a known serviceable voltmeter before
connecting the wiring.
A
V
E
R
T
I
S
S
E
M
E
N
T
!
S
Seul le personnel qualifié, comme les électriciens agréés, peut effectuer l’installation électrique. Risque
d’électrocution.
S
Couper toutes les sources d’alimentation de chaque UPS avant de connecter le câblage de commande à
l’enveloppe du module Sync Control et à l’UPS d’Eaton. Des tensions dangereuses sont présentes dans l’UPS
ou le SSBM et dans l’enveloppe du Sync Control d’Eaton.
Once the Eaton Sync Control has been moved to its installed location, unpacked, and
inspected, it is ready for installation and wiring.
Use the applicable procedure from the following list to install the Eaton Sync Control
to the UPS:
S
With an Eaton 9395P UPS, proceed to paragraph 3.1.
S
With an Eaton 9395 SSBM, proceed to paragraph 3.2.
3.1
Installation and Wiring with an Eaton 9395P UPS
NOTE
When installing wiring connections, conduit must be installed between the Eaton Sync Control and the
UPS cabinet.
To install and wire:
1.
Install the Eaton Sync Control panel to the selected mounting location.
See Figure 2‐1 on page 2-2 for mounting hole dimensions and Figure 2‐2 on
page 2-3 for conduit entrance locations.
2.
Unfasten the front door latches and swing the door open.
3.
Complete all control wiring interconnections using Table 3‐1 for wiring
requirements.
Figure 3‐1 shows the Eaton Sync Control TB1 terminal block and ground terminal
locations. Figure 3‐2 shows the TB1 terminal block wiring detail.
Figure 3‐5 shows the typical locations of the UPS TB3, TB6, and X-Slot
®
Communication bays. Figure 3‐3 shows the TB6 detail.
Refer to the applicable Eaton 9395P UPS Installation and Operation Manual listed
in paragraph 1.3 on page 1-4 for UPS cabinet terminal locations and assignments,
termination requirements, conduit landing locations, and terminal access
instructions.