Eaton Powerware 9155 User manual

Other manuals for Powerware 9155: Reference Manual, User Manual, User Manual, User Manual, User manual
Manual is about: (500 VA – 60 kVA)

Summary of Powerware 9155

  • Page 1

    Powerware 9155 parallel ups 8–15 kva user's guide ®.

  • Page 2: Class A Emc Statements

    Class a emc statements fcc part 15 note this equipment has been tested and found to comply with the limits for a class a digital device, pursuant to part 15 of the fcc rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a c...

  • Page 3

    Requesting a declaration of conformity units that are labeled with a ce mark comply with the following harmonized standards and eu directives: s harmonized standards: iec 62040-1-1 and iec 62040-2; iec 60950 third edition s eu directives: 73/23/eec, council directive on equipment designed for use wi...

  • Page 4: Special Symbols

    Special symbols the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock - indicates that a risk of electric shock is present and the associated warning should be observed. Caution: refer to operator's manual - refer to your o...

  • Page 5

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality i table of contents 1 introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 safety warnings 3 . . . . . . . . . . . . . . ...

  • Page 6

    Table of contents eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality ii.

  • Page 7

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 1 chapter 1 introduction a parallel system with up to three uninterruptible power supplies (upss) can be installed to provide a parallel capacity and/or redundant system. This load sharing system pro...

  • Page 8

    Introduction eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 2.

  • Page 9: Save These Instructions

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 3 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and...

  • Page 10: Consignes De Sécurité

    Safety warnings eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 4 consignes de sécurité consignes de sÉcuritÉ importantes conserver ces instructions ce manuel contient des consignes de sÉcuritÉ importantes d a n g e r ! Cet onduleur contient des t...

  • Page 11: Advertencias De Seguridad

    Safety warnings eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 5 advertencias de seguridad instrucciones de seguridad importantes guarde estas instrucciones este manual contiene instrucciones de seguridad importantes p e l i g r o este sie contie...

  • Page 12

    Safety warnings eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 6.

  • Page 13: Inspecting The Equipment

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 7 chapter 3 ups setup this chapter describes: s equipment inspection s floor loading and clearances s unloading the cabinet(s) the instructions are intended for the chief operator/system supervisor, ...

  • Page 14: Floor Loading

    Ups setup eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 8 floor loading when planning the installation, consider the ups weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The ...

  • Page 15: Unloading The Cabinet(S)

    Ups setup eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 9 unloading the cabinet(s) the following tools are required for unloading the cabinet(s): s 15 mm wrench or socket s 7 mm nutdriver or socket c a u t i o n the ups and extended battery modu...

  • Page 16

    Ups setup eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 10 3. Remove the front cover from the bottom cabinet to access the front shipping bracket. Press and release the handle latch at the bottom of the cover and then lift the cover up and off t...

  • Page 17

    Ups setup eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 11 note be sure to support the front and back of the cabinet when rolling it off the pallet to prevent tipping. 7. Slowly roll the cabinet toward the rear of the pallet. Once the pallet til...

  • Page 18

    Ups setup eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 12.

  • Page 19

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 13 chapter 4 parallel installation the powerware 9155 has the following power connections: s 2‐phase (l1 and l2), neutral, and ground connection for rectifier/bypass input s 2‐phase (l1 and l2), neut...

  • Page 20

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 14 w a r n i n g only qualified service personnel (such as a licensed electrician) should perform the ups installation and initial startup. Risk of electrical shock. To hardwire...

  • Page 21

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 15 5. Remove the parallel tie cabinet front cover (see figure 6). Parallel cabinet figure 6. Parallel tie cabinet front cover 6. Remove the internal cover to gain access to the ...

  • Page 22

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 16 7. Punch holes for the conduit (ac input, each ups output, and load connection) using a greenlee ® punch or similar device. 8. Verify that the parallel bypass breaker is in t...

  • Page 23

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 17 10. Verify that each ups battery circuit breaker is in the off position (see figure 9). On off ups wiring access cover conduit landing battery connector battery circuit break...

  • Page 24

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 18 note input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. Table 2. Ups terminal block wiring wire function terminal p...

  • Page 25

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 19 13. Hardwire the output terminations (tb1‐6 through tb1‐9) from each ups to the parallel tie cabinet (see figure 11). Ups 1 ups 2 ups 3 neutral line 1 line 2 line 1 line 2 li...

  • Page 26

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 20 15. Hardwire the load to the parallel tie cabinet (see figure 12). Line 1 line 2 neutral figure 12. Load connections.

  • Page 27

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 21 16. Wire the ac input to the bypass breaker (see figure 13). Line 1 neutral line 2 figure 13. Parallel ac input wiring 17. Verify the phase rotation for each ups and the bypa...

  • Page 28

    Parallel installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 22 figure 14. Parallel wiring diagram.

  • Page 29

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 23 chapter 5 installing options this section describes the powerware hot sync can bridge card. For other options, such as additional x-slot t cards, powerware lansafe t power management software, rem...

  • Page 30

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 24 powerware hot sync can bridge card the powerware hot sync can bridge card, shown in figure 16, can be installed to provide connectivity for operational mode control and metering...

  • Page 31

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 25 2. If you ordered a factory-configured parallel ups, remove the powerware hot sync can bridge card from the x-slot on the front of the ups. Retain the screws. Otherwise, remove ...

  • Page 32

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 26 note if you are installing another x-slot card, be sure to install the powerware hot sync can bridge card in x-slot 2. 4. Loosely install the powerware hot sync can bridge card ...

  • Page 33

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 27 ups #1 ups #2 ups #3 figure 19. Can bridge card wiring.

  • Page 34

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 28 8. Secure the powerware hot sync can bridge card with the screws removed in step 2. 9. On the bottom cover (and also the middle cover if 3-high), remove a knockout tab in the to...

  • Page 35

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 29 11. Reinstall the front covers, starting with the bottom cabinet (see figure 21). Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into p...

  • Page 36

    Installing options eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 30

  • Page 37

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 31 chapter 6 stabilizing the cabinet note for seismic installations, you must order and install a powerware 9155 ups seismic kit; do not use the following instructions. Note for non-seismic installat...

  • Page 38

    Stabilizing the cabinet eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 32 4. Continue to one of the following sections: s “extended battery module installation” on page 35 to install optional ebms. S “operation” on page 39 to start up the paralle...

  • Page 39

    Stabilizing the cabinet eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 33 m4 screws figure 24. Stabilizing bracket with two cabinets m4 screws figure 25. Stabilizing bracket with three cabinets.

  • Page 40

    Stabilizing the cabinet eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 34.

  • Page 41

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 35 chapter 7 extended battery module installation note a maximum of 22 battery strings can be installed in one configuration, including ups batteries (4 ebm-64 models or 3 ebm-96 models). Ups-32 mode...

  • Page 42

    Extended battery module installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 36 ups battery connector rear ground strap ebm battery circuit breaker ebm battery connector ebm cable ups battery circuit breaker on off figure 26. Typical ebm i...

  • Page 43

    Extended battery module installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 37 8. Remove the top front covers of all cabinets. Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet. 9...

  • Page 44

    Extended battery module installation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 38.

  • Page 45: Control Panel Functions

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 39 chapter 8 operation this chapter contains information on how to use the powerware 9155, including front panel operation, ups startup and shutdown, and configuring the ups for extended battery modu...

  • Page 46

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 40 the following table shows the indicator status and description. Indicator status description green on the ups is operating normally. Flashing s the ups is starting up or is shut down and...

  • Page 47

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 41 the following table shows the basic menu structure. Table 3. Menu map for display functions main menu submenu display information or menu function ups status system normal / battery floa...

  • Page 48

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 42 user settings the following table displays the options that can be changed by the user. Note changes to the output voltage or frequency options should be made before turning on the ups; ...

  • Page 49

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 43 table 4. User settings (continued) default setting available settings description modem config modem installation set modem call events event #0 call modem: no set modem init string atz0...

  • Page 50

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 44 table 4. User settings (continued) default setting available settings description synchronization window ±0.5 through ±3.0 hz (0.1 hz increments) ±2.0 hz unsynchronized transfer to bypas...

  • Page 51: Parallel Ups Startup

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 45 parallel ups startup w a r n i n g only qualified service personnel (such as a licensed electrician) should perform the ups installation and initial startup. Risk of electrical shock. Ve...

  • Page 52

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 46 6. Configure the ups for parallel operation through the front panel: s press any button on the front panel display to activate the menu options. S using the button, scroll to the setting...

  • Page 53

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 47 9. Shut down each ups: s press the button on the front panel display and then press the button to select the turn ups on/off menu. S press the button to select the ups off option; press ...

  • Page 54

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 48 17. Select the system on option; press the button. 18. Confirm the selection. Press and hold the button for three seconds, until the ups stops beeping. The ups goes to bypass mode for fi...

  • Page 55

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 49 configuring the ups for ebms note each ups in a parallel system must have its own ebm and the same number of ebms to ensure consistent runtimes. To ensure maximum battery runtime, config...

  • Page 56: Parallel System Shutdown

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 50 parallel system shutdown to remove power to the parallel ups system output: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front ...

  • Page 57: Individual Ups Shutdown

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 51 individual ups shutdown to shut down a single ups in the parallel system: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front pa...

  • Page 58

    Operation eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 52 restarting the parallel system to restart the parallel system: 1. Verify that all ups breakers on the parallel tie cabinet are in the off position. 2. Switch on utility power where the u...

  • Page 59

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 53 chapter 9 parallel bypass to switch the parallel ups to maintenance bypass from normal mode: 1. From any ups, set the system to internal bypass mode: s using the button on the front panel display,...

  • Page 60

    Parallel bypass eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 54 to return to normal mode from maintenance bypass: 1. Verify that all ups breakers on the parallel tie cabinet are in the off position. 2. Switch on utility power where the upss are...

  • Page 61

    Eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 55 chapter 10 troubleshooting the powerware 9155 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the cont...

  • Page 62

    Troubleshooting eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 56 action possible cause alarm or condition overtemperature led is on. 1 beep every second. Ups internal temperature is too high or the fan has failed. If you have an optional mainten...

  • Page 63: Silencing The Alarm

    Troubleshooting eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 57 action possible cause alarm or condition check parallel board the ups is not recognizing another parallel unit. From the ups status menu, select the units on can bus option and ver...

  • Page 64: Service and Support

    Troubleshooting eaton powerware ® 9155 parallel ups (8–15 kva) user's guide s 164201592 c www.Eaton.Com/powerquality 58 service and support if you have any questions or problems with the ups, call your local distributor or the help desk at one of the following telephone numbers and ask for a ups tec...

  • Page 66

    *164201592c* 164201592 c.