Eaton Powerware 9355 User Manual

Manual is about: (500 VA – 60 kVA)

Summary of Powerware 9355

  • Page 1

    Powerware 9355 ups 10/15 kva user’s guide ®.

  • Page 2

    Class a emc statements fcc part 15 note this equipment has been tested and found to comply with the limits for a class a digital device, pursuant to part 15 of the fcc rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a c...

  • Page 3

    Requesting a declaration of conformity units that are labeled with a ce mark comply with the following harmonized standards and eu directives: s harmonized standards: iec 62040-1-1 and iec 62040-2; iec 60950 third edition s eu directives: 73/23/eec, council directive on equipment designed for use wi...

  • Page 4

    Special symbols the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock - indicates that a risk of electric shock is present and the associated warning should be observed. Caution: refer to operator’s manual - refer to your o...

  • Page 5

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com i table of contents 1 introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 safety warnings 5 . . . . . . . . . . . . . . . . . . . . ....

  • Page 6

    Table of contents eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com ii 9 operation 67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control panel functions 67 . . . . . . . . . . . . . . . ....

  • Page 7

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 1 chapter 1 introduction the powerware ® 9355 uninterruptible power supply (ups) is a true online, double-conversion three-phase system that can be used to prevent loss of valuable electronic information and mini...

  • Page 8

    Introduction eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 2 providing outstanding performance and reliability, the powerware 9355 ups’s unique benefits including the following: s online ups design with pure sine wave output. The ups filters and regulates in...

  • Page 9

    Introduction eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 3 the following options for the powerware 9355 are available: s remote monitor panel (rmp) the optional rmp provides monitoring of the operational status and alarm condition of the ups from virtually...

  • Page 10

    Introduction eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 4.

  • Page 11

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 5 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and batteries. P...

  • Page 12

    Safety warnings eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 6 consignes de sécurité consignes de sÉcuritÉ importantes conserver ces instructions ce manuel contient des consignes de sÉcuritÉ importantes d a n g e r ! Cet onduleur contient des tensions morte...

  • Page 13

    Safety warnings eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 7 advertencias de seguridad instrucciones de seguridad importantes guarde estas instrucciones este manual contiene instrucciones de seguridad importantes p e l i g r o este sie contiene voltajes m...

  • Page 14

    Safety warnings eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 8.

  • Page 15

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 9 chapter 3 ups setup this chapter describes: s equipment inspection s floor loading and clearances s unloading the cabinet(s) the instructions are intended for the chief operator/system supervisor, electrical co...

  • Page 16

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 10 floor loading when planning the installation, consider the ups weight for floor loading. The strength of the installation surface must be adequate for point and distributed loadings. The approximate ...

  • Page 17

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 11 unloading the cabinet(s) the following tools are required for unloading the cabinet(s): s 15 mm wrench or socket s 7 mm nut driver or socket c a u t i o n the ups and ebm are heavy (see page 10). Unl...

  • Page 18

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 12 2. Remove the four m4 screws securing the stabilizing bracket to the cabinet rear panel and remove the bracket (see figure 3). Retain the hardware for later use. Note be sure to retain the stabilizin...

  • Page 19

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 13 note hold the back of the cabinet so that the bolts can be removed easily without the cabinet rolling backward. 5. Remove the two m10 bolts securing the front shipping bracket and remove the bracket....

  • Page 20

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 14 note be sure to support the front and back of the cabinet when rolling it off the pallet to prevent tipping. 7. Slowly roll the cabinet toward the rear of the pallet. Once the pallet tilts, continue ...

  • Page 21

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 15 two-high ups cabinets to remove a two-high ups from the shipping pallet: 1. Remove the m10 bolt securing the vertical bracket to the pallet (see figure 6). 2. Remove and retain the three m4 screws se...

  • Page 22

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 16 4. Repeat steps 1 through 3 to remove the vertical bracket on the other side. 5. Remove the front cover from the bottom cabinet to access the front shipping bracket. Press and release the handle latc...

  • Page 23

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 17 8. Reinstall the front cover removed in step 5. Hang the top edge of the cover on the cabinet first, then lower the bottom edge and snap into place. Note be sure to support the front and back of the ...

  • Page 24

    Ups setup eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 18 10. With the cabinet supported, slowly pull the pallet away from the cabinet (see figure 10). Figure 10. Removing the pallet 11. Roll the cabinet to the desired location. 12. Continue to the followin...

  • Page 25

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 19 chapter 4 ups installation the powerware 9355 has the following power connections: s 3-phase (l1, l2, and l3), neutral, and ground connection for rectifier/bypass input s 3-phase (l1, l2, and l3), neutral, and...

  • Page 26

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 20 4. Determine your equipment’s grounding requirements according to your local electrical code. 5. Verify that the ups battery circuit breaker is in the off position (see figure 11). Battery cir...

  • Page 27

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 21 10. Verify that the input circuit breaker is in the off position (see figure 12). 11. Remove the input isolation transformer wiring access cover and retain. Battery circuit breaker input circu...

  • Page 28

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 22 note input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. Note the powerware 9355 ups is a single-feed ups only. Table 1. Terminal bloc...

  • Page 29

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 23 ground figure 13. Ups terminal block (3-high shown) l1 l2 l3 n input l1 l2 l3 n ouput n figure 14. Input isolation transformer terminal block.

  • Page 30

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 24 13. For ups only installations, replace the ups wiring access cover and conduit landing plate. For ups installations with an input isolation transformer, replace the transformer wiring access ...

  • Page 31

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 25 * * figure 15. Ups wiring diagram.

  • Page 32

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 26 * * figure 16. Ups with extended battery modules wiring diagram.

  • Page 33

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 27 * * figure 17. Ups with input isolation transformer wiring diagram.

  • Page 34

    Ups installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 28.

  • Page 35

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 29 chapter 5 wall-mounted bypass switch installation this chapter describes installing the wall-mounted bypass switch with the ups. The wall-mounted bypass switch is a make-before-break (mbb) maintenance bypass s...

  • Page 36

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 30 w a r n i n g only qualified service personnel (such as a licensed electrician) should perform the ups installation and initial startup. Risk of electrical shock. To har...

  • Page 37

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 31 6. Remove the internal cover to gain access to the breakers (see figure 19). Internal cover figure 19. Internal cover.

  • Page 38

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 32 7. Punch holes for the conduit (ac input, ups output, load connection, and maintenance bypass contact wires) using a greenlee punch or similar device. 8. Verify that the...

  • Page 39

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 33 10. Verify that the ups battery circuit breaker is in the off position (see figure 21). 11. Remove the ups wiring access cover and one of the conduit landing plates and ...

  • Page 40

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 34 13. Hardwire the ups input terminations. See table 2 for specifications and figure 22 for a detailed view of the ups terminal block. Note input neutral must be wired for...

  • Page 41

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 35 ground maintenance bypass contacts tb2 figure 22. Ups terminal block (3-high shown).

  • Page 42

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 36 14. Hardwire the output terminations from the ups to the bypass cabinet (see figure 23). Neutral line 1 line 2 line 3 ground figure 23. Ups output to bypass cabinet wiri...

  • Page 43

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 37 15. Hardwire the load to the bypass cabinet (see figure 24). 16. Route the maintenance bypass wires through the conduit to the ups terminal block (see figure 22 on page ...

  • Page 44

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 38 18. Wire the ac input to the bypass breaker (see figure 25). Line 1 line 2 line 3 figure 25. Bypass ac input wiring 19. Verify the bypass input. 20. Reinstall the intern...

  • Page 45

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 39 not used not used not used red wire (open when breaker is open) bypass input black wire (common) from ups 1 output 225a 80a (4x) load blue wire (closed when breaker is o...

  • Page 46

    Wall-mounted bypass switch installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 40 * figure 27. Ups with input isolation transformer wiring diagram.

  • Page 47

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 41 chapter 6 stabilizing the cabinet note for seismic installations, you must order and install a powerware 9355 ups seismic kit; do not use the following instructions. Note for non-seismic installations, you mus...

  • Page 48

    Stabilizing the cabinet eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 42 4. Continue to one of the following sections: s “extended battery module installation” on page 45 to install optional ebms. S “communication” on page 49 to install ups communication opt...

  • Page 49

    Stabilizing the cabinet eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 43 m4 screws figure 30. Stabilizing bracket with two cabinets m4 screws figure 31. Stabilizing bracket with three cabinets.

  • Page 50

    Stabilizing the cabinet eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 44.

  • Page 51

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 45 chapter 7 extended battery module installation note a maximum of 22 battery strings can be installed in one configuration, including ups batteries (4 ebm-64 models or 3 ebm-96 models). Ups-32 models contain 2 ...

  • Page 52

    Extended battery module installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 46 ups battery connector rear ground strap ebm battery circuit breaker ebm battery connector ebm cable ups battery circuit breaker figure 32. Typical ebm installation (2-high ...

  • Page 53

    Extended battery module installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 47 8. Remove the top front covers of all cabinets. 9. Install the remaining ground straps between each cabinet (see figure 33). 10. Reinstall the top front covers removed in s...

  • Page 54

    Extended battery module installation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 48.

  • Page 55

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 49 chapter 8 communication this section describes the: s db-9 communication port s x-slot cards s remote monitor panel and industrial relay card (irc) s powerware lansafe t power management software s remote emer...

  • Page 56

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 50 installing communication options and control terminals to access and install the communication options and control terminals: 1. Remove the front covers of all cabinets, starting with the top cab...

  • Page 57

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 51 figure 36. Installing communication cables 3. On the bottom cover (and also the middle cover if 3-high), remove a knockout tab in the top edge of the cover for each cable: with wire cutters, cut ...

  • Page 58

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 52 4. Route the cable(s) to the approximate location of the cover access holes. 5. Connect the cables to the appropriate location. See “communication options” on page 53 or “control terminals” on pa...

  • Page 59

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 53 communication options the powerware 9355 has serial communication capabilities through the db-9 communication port or through an x-slot card in one of the available bays. In addition, the powerwa...

  • Page 60

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 54 the cable pins are identified in figure 39 and the pin functions are described in table 3. See figure 34 on page 49 for the communication port location. 3 8 7 9 1 6 2 4 5 figure 39. Communication...

  • Page 61

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 55 s industrial relay card - is used to indicate the operating status of the ups using the customer’s monitoring equipment and to connect an optional rmp. The irc uses four isolated normally-open or...

  • Page 62

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 56 remote monitor panel the optional rmp can be installed to monitor the operation of the ups from virtually any location within your facility, up to 152.4m (500 ft) from the ups. You can surface-mo...

  • Page 63

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 57 mounting slots (6 places) note matches mounting holes on a single- or double-gang electrical box. Cable exit openings for 1/2” conduit or provided strain relief (3 places) dimensions are in mm [i...

  • Page 64

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 58 to install an rmp: note if mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud within the wall. Do not use hollow wall anchors. The rmp can also be mounted to a single-...

  • Page 65

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 59 6. To check the operation of the rmp, ensure that the ups is supplying the load via the inverter or bypass. If the indicators on the rmp show the appropriate status, then it is operating correctl...

  • Page 66

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 60 industrial relay card the irc uses normally-open or normally-closed dry relay contacts to indicate the ups status as listed in table 5. Figure 44 shows an irc. Plug-in terminal block j1 to rmp ca...

  • Page 67

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 61 table 5. Irc wire terminations irc terminal function remarks j2-1 nc j2-2 com normal mode j2-3 no j2-4 nc j2-5 com bypass mode j2-6 no yp j2-7 nc j2-8 com battery mode j2-9 no y j2-10 nc j2-11 co...

  • Page 68

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 62 control terminals the cables should be connected to the control terminals with a mating connector. Input and output terminals have a functional isolation from terminal to terminal. They are conne...

  • Page 69

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 63 remote emergency power-off repo is used to shut down the ups from a distance. This feature can be used for shutting down the load and the ups by thermal relay, for instance in the event of room o...

  • Page 70

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 64 relay output contacts the ups incorporates a programmable relay output with potential free contacts for remote alarm indications (see figure 34 on page 49). An additional four relay outputs can b...

  • Page 71

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 65 table 6. Programmable signal inputs signal description disable bypass operation if active, the automatic transfer to the static bypass is prevented. Charger off if active, the battery charge func...

  • Page 72

    Communication eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 66.

  • Page 73

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 67 chapter 9 operation this chapter contains information on how to use the powerware 9355, including front panel operation, ups startup and shutdown, and configuring the ups for extended battery modules (ebms). C...

  • Page 74

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 68 the following table shows the indicator status and description. Indicator status description on the ups is operating normally. Green flashing s the ups is starting up or is shut down and waiting for ...

  • Page 75

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 69 the following table shows the basic menu structure. Table 7. Menu map for display functions main menu submenu display information or menu function ups status ups off / system normal / ups supporting ...

  • Page 76

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 70 user settings the following table displays the options that can be changed by the user. Note changes to the output voltage or frequency options should be made before turning on the ups; otherwise, th...

  • Page 77

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 71 table 8. User settings (continued) default setting available settings description audible alarms normal sound/disabled normal sound battery charging abm cycling/constant abm cycling automatic battery...

  • Page 78

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 72 table 8. User settings (continued) default setting available settings description site wiring fault notice enabled/disabled enabled reset custom event settings 0 through 32 total: 0/32 auto output co...

  • Page 79

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 73 normal mode startup to start up the ups: 1. Verify that the maintenance bypass switch is in the ups position (see figure 47 on page 81). 2. If an optional wall-mounted bypass cabinet is installed: s ...

  • Page 80

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 74 starting the ups on battery note before using this feature, the ups must have been powered by utility power at least once. To start the ups on battery: 1. Verify that the maintenance bypass switch is...

  • Page 81

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 75 internal bypass startup to start the ups in internal bypass mode: 1. Verify that the maintenance bypass switch is in the ups position (see figure 47 on page 81). 2. If an optional wall-mounted bypass...

  • Page 82

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 76 ups maintenance bypass startup to start the ups in maintenance bypass: 1. Verify that the maintenance bypass switch is in the bypass position (see figure 47 on page 81). 2. If an optional isolation t...

  • Page 83

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 77 configuring the ups for ebms to ensure maximum battery runtime, configure the ups for the correct number of ebms: 1. Press any button on the front panel display to activate the menu options. 2. Using...

  • Page 84

    Operation eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 78 ups shutdown to shut down the ups: 1. Press any button on the front panel display to activate the menu options. 2. Press the button on the front panel display and then press the button to select the ...

  • Page 85

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 79 chapter 10 ups maintenance this section explains how to: s care for the ups and batteries s recycle used batteries or ups s use the maintenance bypass switch ups and battery care for the best preventive mainte...

  • Page 86

    Ups maintenance eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 80 when to replace batteries when the indicator flashes and the lcd panel displays battery failure, the batteries may need replacing. Contact your service representative to order new batteries. Ch...

  • Page 87

    Ups maintenance eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 81 using the ups maintenance bypass switch the ups maintenance bypass switch is located on the back of the ups (see figure 47). The maintenance bypass switch is used to bypass the ups during maint...

  • Page 88

    Ups maintenance eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 82 to transfer the load from the ups to maintenance bypass: 1. Turn the maintenance bypass switch to the bypass position. The battery circuit breaker trips, and the ups is now bypassed, with the l...

  • Page 89

    Ups maintenance eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 83 using the wall-mounted bypass cabinet to transfer the load from the ups to maintenance bypass (wall-mounted operation): 1. Transfer the ups to bypass mode: s press any button on the front panel...

  • Page 90

    Ups maintenance eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 84 5. Press any button on the front panel display to activate the menu options. 6. Using the button on the front panel display, scroll to the control menu option and press the button. 7. Press the...

  • Page 91

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 85 chapter 11 specifications this section provides the following specifications: s model list s dimensions and weights s environmental and safety specifications s technical specifications s model specifications s...

  • Page 92

    Specifications eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 86 table 10. Dimensions and weights dimensions (h × w × d) weight 2-high ups 32.2” × 12” × 33.5” (81 × 30 × 85 cm) 381 lb (173 kg) 3-high ups-32 47.8” × 12” × 33.5” (121.5 × 30 × 85 cm) 587 lb (266...

  • Page 93

    Specifications eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 87 table 12. Technical specifications technology online, double-conversion topology with static bypass switch and 3-position maintenance bypass switch. Frequency independent operation. Input voltag...

  • Page 94

    Specifications eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 88 table 13. Model specifications 10 kva model output voltage (line–line) 208 208 208 220 output voltage (line–neutral) 120 120 120 127 input voltage 208 480 (with input isolation transformer) 600v...

  • Page 95

    Specifications eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 89 table 14. Battery specifications battery type 9 ah sealed, valve-regulated lead acid (vrla), maintenance-free, minimum 3-year float service life at 25°c (77°f), voltage 192 vdc (96 cells per str...

  • Page 96

    Specifications eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 90

  • Page 97

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 91 chapter 12 troubleshooting the powerware 9355 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do ...

  • Page 98

    Troubleshooting eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 92 action possible cause alarm or condition overtemperature led is on. 1 beep every second. Ups internal temperature is too high or the fan has failed. Turn the maintenance bypass switch to the se...

  • Page 99

    Troubleshooting eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 93 service and support if you have any questions or problems with the ups, call your local distributor or the help desk at one of the following telephone numbers and ask for a ups technical repres...

  • Page 100

    Troubleshooting eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 94.

  • Page 101

    Eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 95 chapter 13 limited warranty warrantor: the warrantor for the limited warranties set forth herein is eaton power quality corporation, a delaware corporation (“eaton”). Limited warranty: this limited warranty (t...

  • Page 102

    Limited warranty eaton powerware ® 9355 ups (10/15 kva) user’s guide s 164201594 rev c www.Powerware.Com 96 end-user’s obligations: in order to receive the benefits of this warranty, the end-user must use the product in a normal way; follow the product’s operators and maintenance manual; and protect...