Eaton PowerXL DE1 series Quick Start Manual - Disclaimer

Other manuals for PowerXL DE1 series: Manual, Manual
Manual is about: Variable speed starter Variable Speed Starter VSS / Configuration module

Summary of PowerXL DE1 series

  • Page 1

    Powerxl™ de1 quick-start-guide ap040092en title de1 quick-start-guide product powerxl™ de1 level 2 1 – fundamental – no previous experience necessary 2 – basic – basic knowledge of variable speed starter recommended 3 – advanced – basic knowledge of variable speed starter required 4 – expert – good ...

  • Page 2: Content

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 2 content danger! - dangerous electrical voltage! ........................................................................................................ 3 disclaimer ...................................................................................

  • Page 3

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 3 danger! - dangerous electrical voltage! Disconnect the power supply of the device. Ensure that devices cannot be accidentally restarted. Verify isolation from the supply. Cover or enclose any adjacent live components. Follow the engineering instr...

  • Page 4: Disclaimer

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 4 disclaimer the information, recommendations, descriptions, and safety notations in this document are based on eaton’s experience and judgment and may not cover all contingencies. If further information is required, an eaton sales office should be...

  • Page 5: General

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 5 general this quick-start-guide gives a short introduction into the handling of the variable speed starters de1 (vss). It is assumed that the measures described in the installation leaflet, which is supplied with the product, have been taken into ...

  • Page 6: Environmental Conditions

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 6 environmental conditions with the exception of de1-34016…… all sizes of the variable speed starter de1 can be used in the temperature range between -10 °c and +60 °c without any derating. Derating for de1-34016…. See manual mn040011en. Vss can be...

  • Page 7

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 7 in default the variable speed starter trips once a fault is detected and has to be reset. It is also possible to acti- vate the function “auto-restart”, which resets the vss automatically up to 9 times (number of resets can be selected) and resta...

  • Page 8: Status Leds

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 8 status leds the leds on the front of the variable speed starter indicate operating status and faults run (green) o off = fault or de1 not supplied o flash every 2 s = ready, no start signal (fwd/rev) o on = run status (red) o off = de1 ok o flash...

  • Page 9

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 9 configuration module dxe-ext-set dxe-ext-set is an optional module, which can be plugged onto the front of the variable speed starter. It is used for simple modification of selected parameters without using a pc or keypad. All sizes of de1 use th...

  • Page 10

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 10 designation settings function ramp 0,1 s / 1 s / 3 s / 5 s / 10 s / 15 s / 30 s / 60 s / 120 s / 180 s selection of ramp times. Values are equal for ac- celeration and deceleration ramp fixed freq 0 … 100 % f-max setting of fixed frequency 1 wit...

  • Page 11: Motor Protection

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 11 motor protection the internal motor protection protects the motor against overload. In default the motor protection is set to the device’s rated current. It can be set to values between 10 and 100 % of the rated current by using the potentiomete...

  • Page 12

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 12 functions of the signals at the control terminals fwd / rev o selection of the direction of rotation with high signal o both signals at the same time = motor coasts to stand still (xor) ff1 o h = selection of fixed frequency 1 o the speed change...

  • Page 13

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 13 configuration of the control terminals in default variable speed starters are configured for terminal mode (p-12 = 0). The following information refers to this mode only. Settings of p-12 different from zero may lead to other terminal configurat...

  • Page 14

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 14 mode 3 one direction 1 direction (fwd) speed reference via potentiometer (0 … 10 v) fixed frequency ff1. Details see mode 0 external fault (extflt). Details see mode 1 mode 4 digital reference (1) 1 direction (fwd) speed reference via fixed freq...

  • Page 15

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 15 mode 8 machine control (1) 2 directions, selected with dir. (l = fwd, h = rev) speed reference via potentiometer (0 … 10 v) fixed frequency ff1. Details see mode 0 enabling of the variable speed starter with start hint: in case of wire break at ...

  • Page 16: Full Parameter Access

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 16 full parameter access in case access to additional parameters is needed, this can be achieved by using: the optional keypad dx-key-led (v1.2 and above) the parameter software drivesconnect. Free download: http://www.Drive-support-studio.Com/ots/...

  • Page 17

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 17 configuration of the analog input in case an analog input is needed (p-15 = 0 / 1 / 3 / 8 / 9), this functionality is assigned to terminal 4. A configuration of the analog input can be done as follows: voltage- or current input signal (p-16 = ai...

  • Page 18: Dc Braking

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 18 dc braking parameter p-25 defines the operation of the dc braking. In default dc braking is disabled. Dc-braking before start can be activated, to bring spinning motors to stand still before the variable speed starter starts. This is to prevent ...

  • Page 19: Modbus

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 19 modbus variable speed starters de1 can be connected to a modbus network. In this case the following parameter set- tings are necessary: p-12 = 3 (processdataaccess) p-34 (pdp-address) to be set to the de1’s address in the modbus network p-35 (rs...

  • Page 20: Parameter List

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 20 parameter list pnu swd address access run designation range default description p-01 20.1 - r/w f-max f min …300.0 hz 50/60 hz sets the upper limit for the speed of the motor. This can be set to any value between “f-min” and 5x the “motor nom fr...

  • Page 21

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 21 pnu swd address access run designation range default description and temperature, and forced ventilation may be required. P-12 928.0 y r/w processdataaccess 0…13 0 defines who has control for commands and reference values. 0 = terminal control. ...

  • Page 22

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 22 pnu swd address access run designation range default description selection via a digital control signal. P-22 5.3 - r/w f-fix3 f min … f max 40 hz preset fixed frequency 3 value can be adjusted between f-min (p-02) and f-max (p-01). Selection vi...

  • Page 23

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 23 pnu swd address access run designation range default description 2 = 38.4 kbit/s 3 = 57.6 kbit/s 4 = 115.2 kbit/s p-36 362.0 y r/w modbus rtu0 com timeout 0…8 0 modbus rtu0 com timeout time between a communication loss and the resulting action. ...

  • Page 24

    Ap040092en _de1 quick-start-guide www.Eaton.Eu page 24 pnu swd address access run designation range default description the heatsink is active. P00-15 852.0 (…7) y r dc-link0 log (…link7 log) dc link voltage log, recording the most recent 8 samples of the dc bus voltage prior to a vss trip condition...