AP040092EN _DE1 Quick-Start-Guide
www.eaton.eu
Page 5
General
This Quick-Start-Guide gives a short introduction into the handling of the Variable Speed Starters DE1 (VSS). It
is assumed that the measures described in the installation leaflet, which is supplied with the product, have
been taken into account.
Variable Speed Starter
DE1
IL040005ZU
Configuration module
DXE-EXT-SET
IL040020ZU
Please see manual MN040011EN for more detailed information.
Variable Speed Starters can be used for a plurality of applications as it comes out of the box. In default the
following functions are available:
DE1-12……. (0,25 … 2,2 kW)
o
Mains supply 1~ 200 (-10 %) … 240 V (+10 %)
o
Motor feeder 3~ 0 - 200 … 240 V
DE1-34…… (0,37 … 7,5 kW)
o
Mains supply 3~ 380 V (-10 %) … 480 V (+10 %)
o
Motor feeder 3~ 400 ... 480 V
Protective functions
o
Motor feeder short circuit proof and ground fault proof
o
Motor protection set to rated current of the device
o
Protected against
Overvoltage
Undervoltage
Overtemperarture
Speed reference 0…10 V, corresponds to an output frequency of 0…50 Hz (60 Hz in USA and in Variant
DE1…N01)
3 digital inputs (High-Signal 10 … 24 V, either coming from DE1 itself or from an external source, e.g.
PLC)
o
Forward (FWD)
o
Reverse (REV)
o
Fixed frequency 1 (FF1), set to 20 Hz
Fault message via a potential-free contact (up to 230 V~) between terminals 13 and 14. Switching con-
ditions:
o
ON
No fault
AND
START command (FWD or REV) present
o
OFF
In case of fault: directly
After removal of the START command (FWD or REV). In case the motor ramps to
stop (P-05 = 1 = Default) the contact opens at speed zero.
Ramp times set to 5 s.