Ebac CD425 Owner's Manual

Summary of CD425

  • Page 1

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 ebac model cd425 dehumidifier owner’s manual ebac commercial ltd st helens trading estate bishop auckland co. Durham dl14 9ad telephone: (01388) 664400 fax: (01388) 662590 website: www.Ebacuk.Com cd425 owners manual.

  • Page 2

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 introduction dehumidifiers remove moisture from the air that is circulating through the unit. The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and condensation within the room, or other enclosed spaces where the de...

  • Page 3

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 specifications m odel : cd425 h eight : 1190mm w idth : 1100mm d epth : 460mm w eight : 160 kg a irflow : 3000 m 3 /hr p ower s upply : 380-415v, 3 ph, 50hz p ower 6.0 kw (max) f inish : vinyl coated steel r efrigerant t ype /q ty : r407c (2.5kg) cd...

  • Page 4

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 installation positioning: position the dehumidifier unit in the centre of the room to be conditioned if at all possible. Using a spirit level ensure the unit is level in both directions. Failure to do so may result in the drain tray overflowing and ...

  • Page 5

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 operation the operation of the dehumidifier is to remove moisture from the air by having it condense on the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns to the conditioned space slightly warmer and d...

  • Page 6

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 routine maintenance warning: ensure that the power cord to the machine has been disconnected before carrying out routine maintenance on items 1, 2, 4, 5, and 6. To ensure continued full efficiency of the dehumidifier, maintenance procedures should b...

  • Page 7

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 repairs 1. Should an electrical component fail, consult the factory service center to obtain the correct replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. C...

  • Page 8

    Drawing no. :- tpc127a issue :- 1 date :- 26/06/03 troubleshooting s ymptom c ause r emedy little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils 4. Loose electrical wiring 5. Fuse blown 1. Tighten fan 2. Replace the fan motor 3. See routine maintenance sectio...

  • Page 9

    Cd425 owners manual drawing no. :- tpc127a issue :- 1 date :- 26/06/03 cd425 spare parts list n umber d escription p art n umber q uantity 1 compressor 3944919 1 2 axial fan 3040119 1 3 12v 100ma filament 3034522 1 4 condenser coil 3020725 1 5 evaporator coil 3020733 3 6 reversible filter dryer 3020...