Ecotck Monica Plus Freestanding Installation Manual - Flashing Options
7
Flashing Options
Decktite - For all Steel Roof Profiles
Please circle the flashing option to be used. When considering an alternative method please consult
your local council.
Seismic Restraint
All installation scenarios for Monica Plus require the use of hold-down anchors (one on each side)
Fixing to Concrete Floor
Minimum M8 expansion anchors (M10 recommended) or min M8 epoxy- set anchors.
Approved Anchors: Expansion Anchors-Ramset Dynabolt and Trubolt, Hilti HAS.
Epoxy-set Anchors – Ramset Epcon, Ramset Chemset and Hilti HVU.
Fixing to Timber Floor Framing
Minimum 14g x 60 screws (6.3mm diameter) or M10 X 90 coach-screws. These shall be fixed a minimum
of 40mm into the centre-line of the existing floor joists. If screws cannot be installed directly into an
existing floor joist, solid blocking between joists (min size 90x45) shall be provided.