Eden RCE10E Installation And Use Manual - R C E 1 0 E
R C E 1 0 E
I N S T A L L A T I O N A N D
U S E G U I D E
1.3.3 Night Function (Economy).
Put the selector switch C to the Moon position.
The Comfort temperature is reduced by 4°C in the heating mode and
increased by 3°C in the cooling mode. This function allows energy
consumption to be reduced at night or when there is no-one in the room.
1.4.0 WARNING OF DIRTY FILTER
During normal fan coil operation a filter retains the impurities present in
the air. This filter must be cleaned periodically otherwise fan coil efficiency
suffers. The FILTER LED warns that the filter must be cleaned by blinking
slowly once every 5 seconds. Refer to the instructions given in the Fan
Coil operating and maintenance manual. When the LED blinks:
- cut off the electricity supply to the fan coil;
- clean the filter.
After cleaning, reconnect the fan coil to the power supply and keep the
key SW1 pressed for 5 seconds; the LED blinks quickly for 5 seconds
and then goes out. The appliance starts operating as normal.
1.4.1 Alarm indication
If the appliance is malfunctioning, the Filter LED comes on with a fixed
red light.
If this happens, contact the firm that installed the appliance.
1.4.2 Information given by the LEDs
1.2.0 DESCRIPTION OF UNIT CONTROLS
The following controls are be found on the unit (Fig. 1):
1.2.1 Setpoint knob (A).
This is used to change the desired temperature value (Setpoint) by +/-
5°C in relation to the preset Comfort value. The Comfort value is 20°C
when the appliance is in the heating mode and 25°C in the cooling mode.
The temperature may therefore be regulated between 15 and 25°C when
heating and between 20 and 30°C when cooling.
1.2.2 Adjustment scale (A).
This consists of points arranged in a circle and a central area shown as
Comfort. Turn the knob to the left to decrease the temperature (each
point = 1°C less) and to the right to increase the temperature (each point
= 1°C more).
1.2.3 Setting switch (C)
OFF: appliance switched off. The antifreeze function remains active.
ON: appliance in operation with temperature adjusted according to
the settings
MOON: appliance operates in the Economy mode (night function).
1.2.4 Setting switch (D)
A: Automatic. The appliance automatically varies the fan speed of
rotation to optimise the Comfort state.
1: First speed. The fan (when on) always operates at minimum speed.
2: Second speed. The fan (when on) always operates at medium
speed.
3: Third speed. The fan (when on) always operates at maximum speed.
1.2.5 Setting switch (E)
UMBRELLA (summer): appliance operates in the cooling mode.
SNOWMAN (winter): appliance operates in the heating mode;
HEATING ELEMENT: appliance operates in the heating mode using
the additional heating element;
NOTE: if the appliance has been programmed during installation for
automatic or centralised switching between Heating and Cooling, the
selector switch E may only be used for switching on the additional heating
element. The Umbrella and Snowman positions are ignored.
1.2.6 MODE LED (F): this indicates the mode of operation of the
appliance (see below for details).
1.2.7 FILTER LED (G): this indicates that the fan coil filter is dirty. It is
also used to indicate an alarm in progress (see below).
1.2.8 HIDDEN BUTTON (SW1) (to be used during installation) for editing
parameter programming.
1.3.0 USING THE UNIT
1.3.1 Cooling: put the selector switch E to the Umbrella symbol (summer)
Put the selector switch D to A (automatic).
Put the knob A to Comfort (25°C).
Put the selector switch C to ON.
The Mode LED first blinks with a green light, which then remains fixed.
The fan coil starts to cool the room. The fan speed of rotation is adjusted
automatically for maximum efficiency.
Upon reaching the Comfort temperature the Mode LED blinks with a
yellow light once every 5 sec. Use knob A to change the temperature
as desired. Use the selector switch D to change the motor speed of
rotation manually.
1.3.2 Heating: put the selector switch E to the Snowman symbol (winter)
Put the selector switch D to A (automatic).
Put the knob A to Comfort (20°C).
Put the selector switch C to ON.
The Mode LED first blinks with a red light, which then remains fixed.
The fan coil starts to heat the room. The fan speed of rotation is adjusted
automatically for maximum efficiency.
Upon reaching the Comfort temperature the Mode LED blinks with a
yellow light once every 5 sec. Use knob A to change the temperature
as desired. Use the selector switch D to change the motor speed of
rotation manually. If the additional heating element is installed, put the
selector switch E to the Heating Element position to switch it on.
Red continuous:
alarm
Red blinking
1sec ON, 1 sec OFF:
dirty filter
LED MODE
Colour
System status
Red continuous:
Active heat valve and fan
Red blinking with fan on:
heat valve OFF, the fan is about to
stop
Red blinking with fan off:
heat valve ON, the fan is about to
start
Green continuous:
active cool valve and fan
Green blinking with fan on:
cool valve OFF, the fan is about to
stop
Green blinking with fan off:
cool valve ON, the fan is about to
start
Orange blinking
setpoint reached, Comfort mode
1sec ON, 5sec OFF:
Orange blinking
setpoint reached, Economy mode
1sec ON, 1sec OFF:
LED FILTER