Eden RCE10E Installation And Use Manual - R C E 1 0 E
TEMPERATURE CONTROLLER FOR FAN COIL UNIT
R A N G E
R C E 1 0 E
I N S T A L L A T I O N A N D
U S E G U I D E
2.1.0 GENERAL DESCRIPTION
The unit consists of 2 parts: the installation base and the control
unit (see Fig. 2):
The installation base is wall mounted or fixed to a 503 module using two
screws. The base has screw terminals for the electrical connections.
The control unit is fixed onto the base by an automatic coupling system
(fig. 6).
The base terminals have the following functions (fig. 2):
M1 Auxiliary output (auxiliary heating element)
M2 Cooling valve output
M3 Heating valve output (or primary heating element)
M4 Phase for power outputs
M5 Fan speed 3 output
M6 Fan speed 2 output
M7 Fan speed 1 output
M8 Power supply input (Phase 230 Vac)
M9 Power supply input (Neutral 230 Vac)
M13 Remote air sensor input (AIR)
M14 Water sensor input (AQ)
M15 Analog and digital input common (Neutral)
M16 Centralised S/W switching input
M17 Economy input
M18 Window contact input
2.0 INSTALLER GUIDE
Fig. 2
2.2.0 TECHNICAL DATA
Power supply: 230Vac +/-10%, 50 60Hz
Absorption: 0.8 VA +/- 15%
Outputs
Fan: TRIAC 250Vac, 3(2.5)A max
Valves: TRIAC 0.6A
Auxiliary output: TRIAC 0.6A max
Temperature adjustment range:+15...+30°C selectable with software
parameters and knob (A) +/- 5°K
Proportional band: selectable between: 2,3,4,5 °K
Neutral area (dead zone): selectable between: 3,4,5°K
Temperature sensors: NTC type sensors 10K +/- 0.3°K @ 25°C with
double insulated cable, section 0.5 mm2 min, 1.5mm2 max, maximum
length 20 m.
Adjustment precision during normal operation: +/- 0.5°C in relation to
25°C room temperature setpoint
Maximum variation in precision with room temperature: +/-0.3°C from
10 °C to 30°C
Antifreeze temperature: 4°C
Factory configuration: see Default parameters table
Storage temperature: -20 ... +55°C
Working temperature: +0 . +50°C, 0 . 95 % r.h.
Housing protection rating: IP30
Connections: screw terminals for wires with section of 1.5 sq. mm.
CE conformity: LVD 73/23: standard EN 60730-1
EMC:EN 55014-1 (or EN 50081-1)
EN55014-2 (or EN 50082-1)
Size: 122 x 68 x 29 mm (WxHxD) - fig. 4
Weight: 120 grams
2.3.0 INSTALLATION
2.3.1 Installation position
The controller must be located 1.5 m from the floor in a position where
there is good circulation of air.
It must not be affected by:
- currents or dead areas behind doors or in corners;
- hot or cold air from ducts;
- sunlight, household electrical appliances or unheated (non-cooled)
areas, such as outside walls behind the thermostat, embedded pipes or
flues (fig. 3).
Fig. 4
Fig. 3
Control unit interior
Terminal block with all connections
L N
I
II
III
M
4
5
2
1
4
3
18
8
7
6
9
15
14
13
17
16
OFF
A
ON
COM
FORT
-
+
122
68
29
1,50 m
1 2 3 4 5 6 7 8 9
13 14 15 16 17 18
Auxiliary
heating
element
Cooling valve
Heating valve
Power supply 2
30
Va
c
±10% - 50-60 Hz
Motor
Air sensor
W
ater sensor
Neutral common
Summer/winter SW
ECONOMY
Window